Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
410E - Read Major Version
410F - Read Minor Version
4145 - Read AGC Level. This will typically be 0.
You need not care about the values that appear. What is
important is that you see the reply values appearing and
the D1-528 beeping. This indicates the device getting
pinged is replying.
ºF ºC
If the Address you defined in step 4 remains displayed
and you never hear the D1-528 beep, the D1-528 is not
getting any replies from the device with the defined
Address.
A
DISPLAY
Verify you defined the correct target address, the target
actually exists and is powered and configured correctly:
3. Press the DISPLAY button.
• If pinging an RF device, is it set to the same Room ID,
PAN ID, RF Channel as the D1-528
V and the current selected RF Channel value will be
displayed. RF Channel 20 is the default value.
4. Press the UP/DOWN arrow button to select the
desired RF channel.
5. Press the DISPLAY button to store the new RF
Channel value.
• If pinging a wired S5 bus device, is it correctly
connected to the D1-528 S5 bus or the S5 bus of an
RF Device set to the same Room ID, PAN ID,RF
Channel as the D1-528.
6. Press the F/C button to stop and return to Pn6.
7. Press F/C again to exit service mode.
rF will display and the D1-528 will beep and
OUTSIDE will start to blink on the display indicating
that the value needs to be stored.
Contractor Mode (Ctr)
Ping Device (Pn6)
Use Pn6 to ping another device in the room from the
D1-528. This is done to make sure the D1-528 is
communicating with the other device.
Contractor mode configures the D1-528 to lock the
upper and lower target temperature to 69-75 °F, disable
motion only checkout and disables the unoccupied
timeout.
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select Ctr
for 4 seconds to enter into service
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select Pn6
for 4 seconds to enter into service
parameter.
parameter.
ºF ºC
ºF ºC
A
DISPLAY
A
DISPLAY
3. Press the DISPLAY button.
oFF will appear on the display by default.
To enable Contractor Mode:
3. Press the DISPLAY button.
V 0 will be displayed.
4. PresstheUP/DOWNarrowbuttontoselectthe
desired P5 address of the device you want to ping.
5. Press the DISPLAY button to start.
a. Press the UP arrow button to display on.
b. Press DISPLAY button.
The D1-528 will begin to send 4 commands, one after
the other, over and over, to read the following from
the target device and display the read values. Each
time a reply is received from each read command, the
D1-528 will beep and display the read value.
410D - Read Device Type
The D1-528 will beep, Ctr will appear on the
display and OUTSIDE will start blinking on the
display indicating that the change needs to be
stored.
31-00721-01
24
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual