Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
3. Press the DISPLAY button.
V and the current selected dLt value will be
displayed. 1 - Normal is the default value.
4. Press the UP/DOWN arrow button to select the
Table 19 Selectable target temperature range
Parameter
1
2
3
desired dLt value 1,2 or 3 as per the below table.
Normal
65-80
in VIP °F (18-
mode 26 °C)
Narrow
Wide
Table 20 dLt (UnOccupied Delta range)
ttt
Not
68-76
°F (20-
21 °C)
62-85
°F (16-
29 °C)
Parameter
1
2
3
(Target
Temperat
ure)
Norma Aggres Minim
l
sive
al
InVIP 62-85
mode °F (16-
29 °C)
65-80
°F (18-
26 °C)
60-85
°F (15-
29 °C)
dLt
DeltaUnoc 40 °F
60 °F
20 °F
(Unoccupi cupied
ed Delta)
For example, if you want to use the Aggressive values,
set the tt value to 2.
DeltaJust
Rented
20 °F
10 °F
30 °F
15 °F
10 °F
0 °F
5. Press the DISPLAY button to save the value.
tt will display and the D1-528 will beep and OUTSIDE
will start to blink on the display indicating that the
value needs to be stored.
DeltaMoti
onScan
6. Press the F/C button to save the tt value.
Str will appear.
For example, if you wanted to use the minimal dLt
setting, set the dLt value to 3.
7. Press the DISPLAY button to save the change.
The D1-528 will reset.
5. Press the DISPLAY button to save the value.
dLt will display and the D1-528 will beep and
OUTSIDE will start to blink on the display (if is not
already blinking) indicating that the value needs to
be stored.
dLt (UnOccupied Delta)
If the room is unoccupied, the D1-528 will use a Normal,
Aggressive or Minimal temperature control band to save
energy defined in the dLt parameter.
6. Press the F/C button to save the dLt value.
Str will appear.
7. Press the DISPLAY button to save the change.
The D1-528 will reset.
• If the room is fully unoccupied, the
DeltaUnOccupied values will be used.
• If the room had just been rented but has not
become occupied yet, the DeltaJustRented
values will be used.
Uot (Unoccupied Time)
The Uot unoccupied time parameter provides 2
groupings of 3 different unoccupied timeouts to save
energy.
• If the room is occupied, but the room entry
door was opened and closed and the D1-528 is
timing down the unoccupied timeout scanning
for motion the DeltaMotionScan values will be
used.
• If the D1-528 is actively receiving room entry
door position from wired switch connected to
an input on the D1-528 or a wireless battery
powered S551.RF switch monitor, the D1-528
uses the 10/2, 5/2 or 30 /10 minutes
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select dLt
for 4 seconds to enter into service
unoccupied timeout defined in Table 21, “Uot
(Unoccupied Time) range” ,
For example, if Uot is set to value 2 and the
room enter door opens and closes and no
motion is detected, the room will go
parameter.
unoccupied after 5 minutes if the room is
Rented or 2 minutes if the room is not rented.
ºF ºC
• If room entry door position is not being
monitored and only the D1-528 motion sensor
is being used for motion only occupancy
control logic, the D1-528 uses the 2.5/24.5,
1.5/12.5 or 8.5 /33.5 hour bright/dark motion
only timeout defined in table.
A
DISPLAY
21
31-00721-01
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RLV3100 Digital Thermostat Installation Guide

Honeywell Lyric T5 Wi-Fi Thermostat Installation Guide