INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
For example, if you have selected HVAC Type 1 FCU-4,
Fan speed options 1-Low, 2 -Low/High and 3 –
Low/Med/High will be available.
Setup Fan Speed
The Fan speed is normally set when the D1-528 is
initialized during installation. The Fan speed can be
set/changed anytime using the FAn parameter.
5. Press DISPLAY to store the setting, the D1-528
beeps to confirm it is set.
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select FAn
for 4 seconds to enter into service
The OUTSIDE symbol will start blinking on the
D1-528 display, indicating that the changes made
need to be saved/committed.
parameter.
6. Press the F/C button.
Str (store) appears on the display indicating that the
changes made need to be stored.
7. Press DISPLAY to store the changes.
D1-528 will reset (the display will go blank then turn
back on).
ºF ºC
Tune Energy Savings
The tt, dLt, Uot, UrS and Urt parameters allow you to
select 3 different levels of energy savings, Normal,
Aggressive or Minimal.
A
DISPLAY
tt (Selectable target temperature range)
3. Press the DISPLAY button.
V 0 will be displayed.
Room temperature is maintained between the lower and
upper values. The value of tt selects Normal, Aggressive
or Minimal energy savings.
4. Press the UP/DOWN arrow button to set the fan
speed by selecting a value 1, 2 or 3:
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select tt
for 4 seconds to enter into service
Table 18 Fan Speed
Value
Function
Low speed (single speed)
Low / High
parameter.
1
2
3
Low /Medium / High
ºF ºC
Based on the HVAC type selection from the HAC
menu, you will be limited to which of the 3 Fan values
can be selected.
Value 1, 2 or 3 (Low, Low/High, Low/Med/High) will be
available when using:
A
DISPLAY
1 - FCU-4
2 - FCU-2 with elec heat
3 - FCU-2 without elec heat
3. Press the DISPLAY button.
V and the current selected tt will be displayed.
1 - Normal is the default value.
4. Press the UP/DOWN arrow button to select the
Value 1, or 2 (Low, Low/High) will be available when
using:
desired tt value 1,2 or 3 per the table.
4-PTAC
5-HP-B W2 assist
6-HP-B W2 replace
7-HP-O W2 assist
8-HP-O W2 replace
Value 1 (Low) will be the only option when using:
9-Y1/2W1/2 G AHU
10- 2nd Stage Heat Pump B-AHU
11- 2nd Stage Heat Pump O-AHU
31-00721-01
20
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual