Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
Table 24. Run parameters
Run Menu Parameters rUn
The D1-528 has Run parameters that let you reset or
reboot the D1-528 and perform a range of in room tests.
The PIR, Door, Window tests can also be performed as
individual tests.
Parameter Value
Function
8
N/A
P5 Address Trace. After
executing displays the P5
source address of received
packets.
9
1...25
55
Edit the NVRAM of a remote
device.
ºF ºC
11
N/A
Run PIR sensor test. The buzzer
will sound as long as there is
motion detected and the LCD
counts the number of times the
application has increased the
motion counter.
A
DISPLAY
12
13
N/A
N/A
Run Door Test. The buzzer will
sound as long as the door is
open and the LCD counts the
number of times the door has
gone from closed to open.
WARNING
These are advanced features that should only be
used by an experienced user. If in doubt, contact
INNCOM customer service.
Run Window Test. The buzzer
will sound as long as the
window is open and the LCD
counts the number of times the
window had gone from closed
to open.
Table 24. Run parameters
Parameter Value
Function
16
0...25
5
Open remote bind window.
Cause the remote device whose
address matches the selected
value to open a 120 second
window for binding. Before
executing, select an address to
be taught by selecting the value
in the Adr menu and pressing
the F/C key.
0
0
Reset the D1-528
1..25
5
Reset remote device. The value
selected is the P5 address to
which the reset command will
be sent.
1
2
3
4
N/A
N/A
N/A
Boot IOMAP 1.
Boot IOMAP 2.
Boot IOMAP 3.
21
0...31
Process image. After executing
flashes the current value of the
room’s process image at the
offset specified by the value.
0...25
5
Boot IOMAP. The active IOMap
will be set to the value selected.
31
51
0...25
N/A
Miscellaneous functionality.
Read Measured temperature.
Read only value shows the
measured temperature to the
nearest 0.1 °F.
5
6
0...99
9
Incremental reconfiguration.
The operation performed will
depend on the selected value.
N/A
N/A
Scroll Versions. Displays the
major and minor versions of
each bank and the application
personality.
88
89
0.100 Read Humidity Level. Read only
value shows the measured
humidity level (%RH).
N/A
N/A
Read Measured temperature.
Read only value shows the
measured temperature to the
nearest 0.1 °F
7
WAN communication test.
Sends an event to the server.
The server in turn will reply with
a command that lets the room
ID scroll over the display of the
Thermostat.
255
Reboot the D1-528
27
31-00721-01
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual