4. Walk around the room and if your motion is detected
by the D1-528 motion sensor, the D1-528 will beep
and increase the displayed value. As long as you
move around to different locations the D1-528 will
beep continuously and increase the displayed value.
When the motion stops, the beeping will stop and the
and the displayed value will remain at its last value.
The Plr test will timeout after 60 seconds.
report balcony position and that has been bound
to the same Room ID, PAN ID and RF Channel as
the D1-528.
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select Uln
for 4 seconds to enter into service
parameter.
Door Test (dor)
Use dor to test the reporting of room entry door position
(if entry door monitoring is required/installed).
ºF ºC
NOTE:
A wired door switch must be connected to a low
voltage input of the D1-528 or S541.RF wireless
battery powered door position sensor installed
that has been bound to the same Room ID, PAN ID
and RF Channel as the D1-528.
A
DISPLAY
3. Press the DISPLAY button start the test.
V 00.h will appear on the display.
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select dor
for 4 seconds to enter into service
4. Open the window/balcony door and the displayed
value will increase by one (i.e., v 01.h) and the D1-528
will continue to beep as long as the window is open.
parameter.
5. Close the window/balcony and the beeping stops and
the display will remain at the last number of detected
openings.
The test will not automatically time out.
6. Press the F/C button to exit service parameter mode.
ºF ºC
Measured Room Humidity (rH)
Displays the humidity value detected by the built-in
humidity sensor in the D1-528.
A
DISPLAY
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select rH
for 4 seconds to enter into service
3. Press the DISPLAY button to start the door test.
V 0 will appear on the display.
parameter.
4. Open the door and the D1-528 will show dor at the
top of the display and also beep.
5. Close the door and the beeping stops and the display
will return to V X , where X is the number of times the
door was detected open.
The door test will not automatically time out.
6. Press the F/C button to exit service parameter mode.
ºF ºC
Window Test (Uln)
Use Uln to test the reporting of Window or Balcony
position reporting.
A
DISPLAY
NOTE:
There must be either a wired window/balcony
3. Press the DISPLAY button to start the humidity
reporting.
V XX % RH will appear on the display, where XX is the
measured humidity.
The humidity test will timeout after 60 seconds.
switch connected to a low voltage input of the D1-
528 or an S541.RF wireless battery powered door
position sensor installed has been configured to
31-00721-01
26
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RLV3100 Digital Thermostat Installation Guide

Honeywell Lyric T5 Wi-Fi Thermostat Installation Guide