Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
• For any CBL32 device, press a button on the
device 2 times quickly (Tap-Tap), then press
the button for 4-7 seconds to accept the Bind.
The CBL32 device should RESET and
broadcast a “0x00031” Sound Buzzer VFI. If
the D1-528 receives this it will beep as
feedback that the bind was successful.
• For a CBL8 S217.RF, L208.RF or other CBL8
RF device or S5-bus connected, non-RF CBL8
devices press any button on the device to
accept the bind/configuration. The device
should RESET, but will not provide any audible
feedback.
5. Unplug the 10 pin harness, then remove the D1-528.
REPLACING D1-528
This section provides information for replacing a D1-
528 that were previously installed and working but
require replacement.
NOTE:
You must replace the D1-528 with another D1-
528 thermostat P/N D1-528-24. You can’t replace
with a battery powered D1-529 thermostat P/N
D1-529-6V
If you have already deployed the property key to all of
the installed D1-528’s, the installed D-578 Edge Router
must be placed into Property Key Deployment mode to
make sure the new D1-528 gets the property key from
the D-578 Edge Router.
6. Connect the existing 10 pin harness to the 10 pin
connector on the new/replacement D1-528, and
power up the D1-528.
If replacing with an existing, already initialized and
configured D1-528 (i.e., from another room or your
spares have previously been configured and it is
displaying Set and a temperature value), Re-Boot the
D1-528 to initial factory state.
1. Remove the cover of the D578 edge router and press
the Blue bind button switch 6 times (press-press-
press-press-press-press) to place it into key deploy-
ment mode.
2. The Red D3 LED will begin to rapidly blink. The D-578
will remain in key deployment mode for 10 hours, but
you can exit the D-578 out of key deployment mode
after configuring the new D1-528 by pressing the
Blue bind button switch 6 times again.
a. Enter service mode by pressing the F/C button
for 4 seconds. The display will change to rid
indicating service mode is entered.
b. Press the DOWN arrow button until the rUn ser-
vice parameter is reached.
3. Disconnect power from the existing D1-528. Open
the circuit breaker powering D1-528.
c. Press DISPLAY button. P and 0 will be dis-
played.
4. Remove the 2 screws that affix the D1-528 to the
mounting plate, lift upward and pull the D1-528 off
of the mounting plate.
d. Press the DOWN arrow button until P 255 is
displayed, then press DISPLAY button to initi-
ate the reboot. The D1-528 display will go blank
as it reboots. It will take a short time for the D1-
528 to start up after the reboot. rid will appear
on the display.
Now with either a new out of the box D1-528 or the one
you just factory booted, rld should be displayed on the
D1-528.
7. Do the Initial Configuration.
It may take 1-2 minutes for the new D1-528 after the
start up to receive the property key from the D-578
and to begin communication with the D-578 and
Niagara/RBM. Until that occurs, the room will be
offline in the RBM.
31-00721-01
34
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual