Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
Set the Room ID
The thermostat will enter Initialization Mode and
display rId the first time it is turned on.
INITIAL CONFIGURATION
This section describes the initial installation and
configuration of new D1-528. If the system is already
configured and you need to replace the previously
configured D1-528, refer Replacing D1-528.
NOTE:
A new, uninitialized D1-528 by default is set to
ºF ºC
Room ID 00001, PAN ID 1, RF Channel 20, and has
all 5 relay outputs disabled.
NOTE:
To install and configure the D1-528 with the
A
DISPLAY
required Room ID, PAN ID and RF or to test the in
room functionality, you do not need a PC or
Honeywell JACE controller running Niagara
Service, Niagara Workbench, Honeywell Remote
Building Manager (RBM) or an installed and
configured D-578 Edge Router.
1. Press the DISPLAY button.
The default 5 digit Room ID value (00001) will scroll
across the screen from highest to lowest (left to right
most value).
Example of Room ID:
NOTE:
To control or view the operation of the D1-528 in a
room from RBM, you must have the Niagara
service running on a PC or Honeywell JACE
controller and the D-578 installed and configured
from Niagara Workbench EasyOnBoard feature.
Hi
Med
Lo
Room Id
0
0
3
01
20
40
01
38
21
101
2038
NOTE:
Refer to Honeywell document INNCOM Direct
34021
Gateway Configuration Guide - 31-00708 and
INNCOM Direct Dashboard User Guide 31-00707
for details of using Niagara Workbench and
installing and using Honeywell Remote Building
Manager (RBM).
NOTE:
The default Room ID is comprised of three fields:
highest digit, middle two digits, and lowest two
digits.
Prerequisites:
Scrolling will stop at the highest digit first. The default
value 0 and HI will be displayed.
• The D1-528 have been installed and powered up.
The initial configuration sequence is:
2. Press the UP/DOWN arrow button to set the value
(range is 0-6).
For the above 3 examples, you would set the HI value
to: 0 - 00101, 0 – 02038, 3 – 34021
3. Press POWER to continue.
1. Set the Room ID
2. RoomCopy
NOTE:
Copy the configuration from the D1-528 that has
The next 2 digits of the Room ID will displayed. 00
and MED will appear.
already been fully configured and proceed from
Deploy the Property Key.
Or else, continue with Setup HVAC Type.
4. Press the UP/DOWN arrow button to set the value
(range is 0-99).
For the above 3 examples, you would set the MED
value to: 01 - 00101, 38– 02038, 21 - 34021
5. Press POWER to continue.
3. Setup HVAC Type
4. Setup Fan Speed
The last 2 digits of the Room ID will be displayed. 01
and LOW will appear.
NOTE:
Prior to completing Initialization Mode, or pushing
the thermostat configuration from INCOMM
Direct Dashboard, the thermostat is configured
with factory defaults to disable any call for heat,
cool, or low, medium and high fan speeds to
protect the HVAC equipment.
6. Press the UP/DOWN arrow button to set the value
(range is 0-99).
For the above 3 examples, you would set the LOW
value to: 01 - 00101, 38– 02038, 21 - 34021.
13
31-00721-01
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual