Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
Using the rUn menu:
bL 2--- 0--- 2--- 0
IrA 2--- 1--- 0 ---0
CbL 2--- 0 ---1--- 2
APP 2--- 0--- 2--- 0
Per 1--- 0--- 0 ---2
1. Press and hold
mode.
2. Press the UP/DOWN arrow button and select rUn
for 4 seconds to enter into service
parameter.
3. Press the DISPLAY button.
Parameter 7: WAN (Wide Area Network) test.
P and 0 will appear.
4. Press the UP/DOWN arrow button to select the
desired parameter value from the rUn menu to test.
5. Press the DISPLAY button to initiate.
Use this test to verify that the D1-528 is communicating
through the D-528 edge router to Niagara (INNCOM
Direct) or TermDMS (IC3).
1. With P 7 on the display, press DISPLAY button to exe-
cute the WAN test. don will be appear on the display.
The D1-528 will send a 0000C commissioning test
request command to the D-578 edge router and
Niagara (in a INNCOM Direct installation) or Ter-
mDMS (in an IC3 installation). If Niagara/TermDMS
has the room online and communicating, a
6. Press the F/C button 2 times, to exit out of the rUn
menu.
Parameter 0 Value 0: Reset the D1-528
1. With P 0 displayed, press POWER button to display V
0. If the displayed value is not 0, change it to 0.
2. Press DISPLAY to execute.
Rst will appear on the D1-528 display and the
D1-528 will RESET
0000DXXXX scroll Room ID XXXXX message will be
sent back to the D1-528 and you should see the 5
digit Room # XXXXX scroll on the display.
Parameter 0 Value X: Reset remote device that has P5
address X (1-255)
This indicates the D1-528 is online.
If don remains on the display and no 5 digit room #
scrolls on the display, the D1-528 is not online.
Refer to the Troubleshooting section.
1. With P 0 displayed, press POWER button to display V
0.
2. Set the Value to the P5 address of another in-room
device and press DISPLAY.
Parameter 8: P5 Address Trace.
The D1-528 sends a 420 Reset command to the
defined P5 address.
Use this to make the D1-528 look at any commands it
receives from other devices in the same room and
display the “From” address that was in the command.
Parameter 1-4: Boot I/O Map 1, 2, 3 or 4 internally in
the D1-528. You do not need to press the POWER
button to view/set a value. With P on the display, just set
the P value to 1-4 and press DISPLAY to execute. The
D1-528 will internally activate the defined I/O Map 1, 2,
3 or 4.
1. With P 8 on the display, press DISPLAY.
The D1-528 will emit an audible click and display the
from P5 Address of any message it receives (via RF or
S5 bus).
For example, there is a device in the same room as the
D1-528 with an unknown address. When you press a
button on the device to make it send a command, “16”
appears on the D1-528 display and the D1-528 clicks.
So the device is using P5 address 16.
You will see the D1-528 Reset.
Parameter 5 Value X: Incremental reconfiguration.
1. With P 5 displayed, press POWER button.
V and 0 will appear.
2. Press the F/C button to exit, when finished with the
test.
2. Set the Value to the built-in incremental I/O Map #,
then press DISPLAY to execute. The D1-528 will
execute the defined I/O Map.
Parameter 9 Value X: View/Edit the NVRAM (non
volatile RAM) settings of a remote device.
NOTE:
Contact INNCOM Customer service for a list of the
available I/O Maps.
INNCOM devices have 255 bytes of NVRAM that control
certain aspects of the device. You can use the D1-528
Par 9 NVRAM feature to read or change the values of
these NVRAM locations of the target device. You can
normally do this remotely using RBM or IC3 dialog
command, but if this not available you can do this
locally in the room using the D1-528.
Parameter 6: Displays the 4 digit versions of its 5
software banks. With P 6 displayed, press DISPLAY to
execute. The 4 digit version x.x.x.x of the BootLoader
(bL), IRAS (IrA), CBL32 (CbL), AppMap (APP) and
Personality (Per) bank will be displayed.
Before you can use this feature, you must elevate the
user access privilege of the D1-528 by executing rUn
parameter 31 with value 41:
For example, it would look like the following.
1. Press and hold
mode.
for 4 seconds to enter into service
31-00721-01
28
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual