Honeywell D1-528 Direct Thermostat Installation Guide
INNCOM DIRECT D1-528 THERMOSTAT INSTALLATION GUIDE
ABOUT THIS GUIDE
WARNING
D1-528 thermostat is a half-wave rectifier device.
If we connect it with another half-wave rectifier
device or use the same transformer, INNCOM D1-
528 thermostat risks being damaged by short
with C, COM, GND or other equivalent
connections.
This Guide provides information about the Installation
details of the INNCOM Direct D1-528 thermostat to the
system integrator, technicians, and end-users. All the
electrical engineers and technicians working with the
product must have basic training on HVAC Sensors,
Smart sensors, and Room Controllers and their
application.
INTRODUCTION
GENERAL SAFETY
INFORMATION
D1-528 thermostat utilize a CC2520 2.4 Ghz IEEE
802.15.4 RF transceiver in their role as part of the
Integrated Room Automation System (IRAS). The
integration of the radio on-board the PCBA, along with
other component changes, makes for a simpler, more
efficient, and more cost-effective device.
Follow the safety instructions provided in this manual
while doing any operation such installation, mounting,
or starting.
• In the case of any modification, except by Honeywell,
the operation and safety warranties become void.
Features
The D1-528 thermostat provides
• Observe all applicable local standards and
regulations.
• Accurate temperature measurement ± 1 °F
• Use only Honeywell supplied or approved
accessories.
• Multiple load actuating options from
24 VAC
• Motion sensor for occupancy detection
CERTIFICATION AND
REGULATION
• RF transceiver for wireless 2.4 Ghz guestroom and
backhaul network communications
• External temperature sensor support.
Waste Electrical and
Electronic Equipment (WEEE)
•At the end of the product life, dispose of the
packaging and product in an appropriate
recycling center.
• Do not dispose of the device with the usual domestic
refuse.
• Do not burn the device.
FCC Part 15 compliant
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
•
This device may not cause harmful interference, and
• This device must accept any interference received,
including interference caused by undesired
operation.
Power Supply Guidelines and
Requirements
D1-528 thermostat uses 24 VAC/VDC power from a UL
Listed Class- 2 transformer or IEC 61558 listed
transformer.
31-00721-01
2
| General | Details |
|---|---|
| Name | Honeywell D1-528 Direct Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.63 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Smart Color Touchscreen Programmable Thermostat RTH9590 User Manual