Danfoss RT 9E Thermostat Installation Guide
Installation guide
Thermostat
RT 9E, RT 14E, RT 101E, RT 107E, RT 123E
089
Approvals and standards:
ATEX: EN 60079-0:2018; EN 60079-11:2012; IECEx: IEC 60079-0:2017;
IEC 60079-11:2011
UK-type Examination Certificate: BS EN IEC 60079-0:2018, BS EN IEC 60079-11:2018
Specific conditions of use:
The enclosure fascia has been coated with a layer of stainless steel to prevent the
accumulation of electrostatic charge. In order to ensure that there is no accumulation of
electrostatic charge on the enclosure, the end user shall ensure that the external metal
work of the enclosure is locally bonded to earth. Information on the durability of the
coating with regards to use of the equipment is contained within the instruction manual.
Fig. 1
Fig. 2
RT 9E
RT 14E
RT 101E
[°C]
[°C]
-45
[°C]
[°C]
[°C]
[°C]
-35
-25
-15
C
C
C
-5
A
A
B
B
A
B
RT 107E
RT 123E
[°C]
[°C]
[°C]
[°C]
C
C
A: Range setting
B: Diffential obtained
C: Differential setting
A
B
A
B
Fig. 3
Fig. 4
Fig. 5
AN179486440929en-001201 | 1
© Danfoss | Climate Solutions | 2024.01
| General | Details |
|---|---|
| Name | Danfoss RT 9E Thermostat Installation Guide |
| Make | Danfoss |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.41 MB |

Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide

Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide

Danfoss UT 72-UT 73 Universal Thermostat Installation Guide

Danfoss ECtemp 530 Electronic Thermostat Installation Guide

Danfoss 014G0251 Eco Radiator Thermostat User Guide

Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide

Danfoss RET230P Electronic Thermostat Instruction Manual

Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide

Danfoss RET1000 Series Electronic Thermostat User Guide

Danfoss RT 9E Manual: Questions and Answers
What do terminals START, STOP, and DIFF mean on the Danfoss RT 9E?
START is the make contact, STOP is the break contact, and DIFF is the differential. Installation Guide, p. 2
How do I set up the Danfoss RT 9E for my application?
Rotate the knob to set the minimum actuating temperature on the main scale. Then rotate the differential adjusting nut according to the nomogram for your model.
- Set the thermostat for minimum actuating temperature by rotating knob (5) and reading main scale (9).
- Set the differential adjusting nut (19) using the nomogram in fig. 3 for your model.
- Verify that maximum actuating temperature equals the temperature setting plus the differential. Installation Guide, p. 2
How do I install the bulb in a water tank with the Danfoss RT?
Use either a capillary stuffing box or a bulb pocket. If using a bulb pocket, follow the bulb fitting shown in fig. 4. Installation Guide, p. 2