fluctuations.  
For example, in the case of HI 2 hysteresis, when the temperature is set to 20°C, the boiler will be  
switched on at 19.8°C, and switched off at 20.2°C. In the case of HI 4 hysteresis, when the  
temperature is set to 20°C, the boiler will be switched on at 19.6°C, and switched off at 20.4°C.  
The hysteresis change mode is signaled by a flashing HI. Turn the knob to the left or right to set the  
desired hysteresis.  
HI 2 – ±0,2 °C (preset),  
HI 4 – ±0,4 °C,  
HI P – PWM operating mode (see chapter “PWM operating mode”).  
Confirm your choice by pressing the button. AURATON Libra will proceed to change the next  
parameter.  
Changes in the delay  
The delay prevents too frequent activation of the actuator, e.g. due to temporary drafts (caused by  
opening the window, etc.).  
GeneralDetails
NameAURATON Libra U Wireless Digital Room Thermostat User Manual
MakeAURATON
LanguageEnglish
FiletypePDF (Download)
File size0.3 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
AURATON Libra Room Thermostat User Manual
AURATON Libra Room Thermostat User Manual
AURATON Cetus P Wired Thermostat User Manual
AURATON Cetus P Wired Thermostat User Manual
19810-102 Digital Room Thermostat Libra Auraton Weekly User Manual
19810-102 Digital Room Thermostat Libra Auraton Weekly User Manual
AURATON Apus Set Wireless Thermostat with Electronic Radiator Head User Manual
AURATON Apus Set Wireless Thermostat with Electronic Radiator Head User Manual

AURATON Libra U Wireless Digital Room Thermostat User Manual