AFRISO RT 10 D 230 Room Thermostat Instruction Manual
ELECTRICAL WIRING DIAGRAM
ELECTRICAL CONNECTION WITH WB 10 D
INSTALLATION AND OPERATING MANUAL
953.001.0174 5 Version: 09.2024
Thermostat electrical connection
N
L
NTC
Room thermostat RT 10 D 230
Lindenstraße 20,
74363 Güglingen
Telephone +49 7135 102-0
Service +49 7135102-211
Telefax +49 7135102-147
CAUTION!
SERVICE MENU
The service menu of the thermostat contains advanced settings that modify its operation. To enter the service menu, first switch
You may only use the product if you have fully read and understood these operating instructions. Instruction is also available
on AFRISO websites on the Internet.
off the thermostat using the button
service menu are shown below.
. Then press and hold the
and
buttons for 5 seconds. The functions available in the
WARNING
Do not make any modifications to the product.
Default
Name
Description of the functions
Possible settings
setting
Verify that the product is not exposed to water.
Work on electrical circuits may only be performed by trained, qualified electricians.
Mains voltage (AC 230 V) can cause serious injury or death.
00: No external NTC sensor (thermostat operates on the
basis of the temperature indication from the internal sensor)
01: The thermostat operates on the basis of temperature
readings from an external NTC sensor (measurement from
the internal sensor is ignored)
Disconnect the mains voltage supply before performing the work and ensure that it cannot be switched on.
SEN
Temperature sensor selection
00
PRODUCT DESCRIPTION
02: The thermostat works on the basis of temperature
readings from an internal as well as an external sensor
Each room thermostat RT 10 measures the actual ambient temperature on an ongoing basis and compares the reference
temperature to the actual temperature and switches the output to obtain the required reference temperature. In addition
to the reference temperature, you can store timer programs (for example, Day/Night). The display shows various values (for
example, temperature, time, heating mode).
External sensor temperature
limitation (only active at setting 02
in SEN parameter)
OSV
DIF
5÷99°C
1÷9°C
42°C
2°C
An additional NTC temperature probe can be connected to the RT 10 room thermostat (not included in scope of delivery) which
can be used as a floor temperature sensor or as an alternative room temperature sensor, depending on the configuration.
Hysteresis of external sensor
(only active at settings 01 or 02
in SEN parameter)
MOUNTING
Limitation of the maximum
temperature that can be set
SVH
SVL
ADJ
FRE
5÷99°C
5÷99°C
35°C
5°C
a
Limitation of the minimum
temperature that can be set
b
a
Correction of the measured
temperature indication
-5÷+5°C
0,0°C
00
a
b
Anti-freeze function
00: Deactivated | 01: Activated
b
00: When the power supply is restored
the thermostat automatically switches off
01: When the power supply is restored
the thermostat switches on automatically
b
PON
Operation aſter power loss
00
DFI
Hysteresis of internal sensor
Relay operation mode
Factory settings
0,5÷3°C
1°C
-
OPT
FAC
Function inactive
The mounting site of the RT 10 room thermostat must provide protection from the weather. Room thermostat RT 10 is designed
for wall mounting in a standard Ø60 mm electrical box. The room thermostat RT 10 must be mounted at eye level, at least 30
cm away from doors and windows. The room thermostat RT 10 is fixed by means of the fixing holes on the back of
the housing.
08: Cancel | 00: Restore factory settings
08
1
2
| General | Details |
|---|---|
| Name | AFRISO RT 10 D 230 Room Thermostat Instruction Manual |
| Make | AFRISO |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.12 MB |

AFRISO RT 10 D 230 Room Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Electrical wiring diagram Electrical connection with WB 10 D Installation and operating manual Thermostat electrical connection Caution! Service menu contains advanced settings that modify operation. You may only use the product if you have fully read and understood these operating instructions. Work on electrical circuits may only be performed by trained, qualified electricians. Each room thermostat RT 10 measures the actual ambient temperature and compares it to the reference temperature. The mounting site of the RT 10 room thermostat must provide protection from the weather.
- Page 2: Use of the room thermostat RT 10 NTC sensor function description The thermostat will switch off the control output when the temperature measured by the additional NTC sensor exceeds the set temperature. This function protects the floor in an underfloor heating system from overheating. Setting date and time involves pressing specific keys to adjust the displayed time. To activate the keyboard lock, hold down a key for 5 seconds. Manual mode allows temperature setting until the mode key is pressed again. The anti-freeze function sends a heating signal when a temperature drop below 5°C is detected. The week can be divided into 5, 6, or 7 working days with configurable time intervals. Technical specifications include dimensions, weight, and electrical parameters. The product complies with Low Voltage Directive, EMC Directive, and RoHS II Directive. Decommissioning involves disconnecting the product from power and returning it to an appropriate collecting point.