Home > EPH CONTROLS > EPH CONTROLS CDTP2 Hardwired Room Thermostat Instruction Manual
EPH CONTROLS CDTP2 Hardwired Room Thermostat Instruction Manual
Boiler Plus
Page 1 of 2
Operating Instructions
CDTP2 Room Thermostat Hardwired
Contents
1. Factory default settings
2. Specifications & wiring
3. Mounting
CAUTION!
4. Installation
5. Wiring diagram
6. Frost protection
Before commencing any work on the electrical
connections, you must first disconnect the thermostat
from the mains. None of the 230V connections must be
live until the installation has been completed and the
housing is closed. Only qualified electricians or authorised
service staff are permitted to open the thermostat.
7. Button / symbol description
8. Resetting the thermostat
9. Keypad lock and unlock
10. Setting the date, time and operating mode
11. Factory default program settings
12. Adjusting the program settings for 5/2d
13. Temporary override (Manual)
14. Permanent override (Hold)
15. Adjusting the switching differential
16. Installer menu
There are parts that may carry mains voltage behind the
cover. The thermostat must not be left unsupervised
when open. (Prevent non specialists and especially
children from gaining access to it.)
Important: Keep this document
Prior to setting the thermostat, it is neccessary to complete all required settings described in this section.
1. Factory default settings
5°C
6. Frost protection
Contacts:
Volt Free
Frost protection is built into this thermostat, it is pre fixed at 5°C and is not
adjustable.
Temperature indicator:
Switching differential:
In built frost protection:
Blue backlight activated :
Clock:
°C
0.4°C
5°C
It will only be activated when the thermostat is in the stand by mode and
the room temperature falls below 5°C.
for 10 secs after any button is pressed
24 hours
Off
Keypad lock:
Operating mode:
5/2 day
7. Button / Symbol description
Keypad lock symbol
Heating ON symbol
Current programme
2. Specifications & wiring
Power supply:
230Vac 50Hz
Power consumption:
Temp. control range:
Ambient temperature:
Contact rating:
8 VA
5 ... 35°C
0 ... 50°C
8A 230Vac
Day of the week
Dimensions:
84 x 84 x 30mm
NTC 10K Ohm @ 25°C
Adjustable from 0.2/0.4/0.6/0.8/1.0˚C
Only operational in stand by mode
Temperature sensor:
Switching differential:
Frost protection:
Program
P3
Standby symbol
Reset button
Set point increase
Set point decrease
OK button
3. Mounting
The mounting height should be 1.5 meters above the floor level.
The thermostat should be wall mounted in the room where the heating is to
be controlled.
Hold button
Standby button
Set button
The place of installation should be chosen so that the sensor can measure the
room temperature as accurately as possible.
Choose the mounting location to prevent direct exposure to sunlight or other
heating / cooling sources when mounted.
8. Resetting the thermostat
The unit can be fitted to:
1. Recessed conduit boxes
2. Surface mounting boxes
3. Directly on walls.
It is necessary to reset the thermostat prior to initial programming.
RESET
Press the
‘NO’will appear on the screen.
Press the button.
button on the side of the thermostat.
4. Installation
Slacken the fastening screw on the bottom of the thermostat with a philips
head screwdriver.
‘YES’will appear on the screen.
The thermostat is hinged and can be opened 180 degrees.
Mount the unit as described in section 3.
Press the ‘OK’button to return to normal operation.
Wire the thermostat according to the wiring diagram.
Close the thermostat and tighten the fastening screw.
OFF
9. Keypad lock and unlock
To lock the keypad, press and hold the
will appear on the screen. The keypad is now locked.
To unlock the keypad, press and hold the and buttons for 5 seconds.
will disappear from the screen. The keypad is now unlocked.
and
buttons for 5 seconds.
5. Wiring diagram
3 2 1 L N
INTERNAL WIRING DIAGRAM CDTP2
ON COM OFF
MAINS
SUPPLY
If mains voltage output is required, terminals L & 2 must be electrically linked.
EPH Controls Ireland
EPH Controls UK
20221006_CDTP2_Opins_PK
| General | Details |
|---|---|
| Name | EPH CONTROLS CDTP2 Hardwired Room Thermostat Instruction Manual |
| Make | EPH CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.19 MB |

EPH CONTROLS eTRV-HW Smart Cylinder Thermostat User Guide

EPH CONTROLS eTRV-HW Smart Hot Water Thermostat Instruction Manual

EPH CONTROLS eTRV Smart Radiator Thermostat Instruction Manual

EPH CONTROLS 20221026 RFRA – RF Room Thermostat Instruction Manual

EPH Controls CDT2-24 24V Room Thermostat Installation Guide

EPH CONTROLS RFCA RF Cylinder Thermostat Instruction Manual

EPH CONTROLS PR092K7 RF Cylinder Thermostat Instruction Manual

EPH CONTROLS COMBIPACK2 Smart Thermostat with Automation and Optimum Start Instructions

EPH CONTROLS RFC RF Cylinder Thermostat Instruction Manual

EPH CONTROLS RFR RF Room Thermostat Instruction Manual

EPH Controls CDTP2 Hardwired Manual: Questions and Answers
EPH Controls CDTP2 Hardwired specifications
| Power supply | 230Vac 50Hz |
| Maximum load | 8A 230Vac |
| Sensor | NTC 10K Ohm @ 25°C |
| Operating temperature | 0 ... 50°C |
| Dimensions | 84 x 84 x 30mm |
| Power consumption | 8 VA |
What does the keypad lock symbol mean on a thermostat display?
The thermostat's keypad is locked and won't respond to button presses. Instruction Manual, p. 1
Can I adjust the frost protection temperature on EPH Controls thermostats?
No, frost protection is fixed at 5°C and cannot be adjusted. It activates only in standby mode when room temperature drops below 5°C. Instruction Manual, p. 1
How do I reset the EPH Controls CDTP2 Hardwired to factory settings?
Press the reset button on the thermostat side.
- Press the RESET button on the side.
- When 'NO' appears, press the button.
- 'YES' will appear on the screen.
- Press OK to return to normal operation. Instruction Manual, p. 1
EPH Controls CDTP2 Hardwired compared with other EPH Controls thermostats
| Specification | EPH Controls CDTP2 Hardwired | EPH Controls CDT2-24 | EPH Controls CRTP2 | EPH Controls CP4B |
|---|---|---|---|---|
| Power supply | 230Vac 50Hz | 24Vac 50Hz | 2 x AA Alkaline Battery | 2 x AA Alkaline Batteries |
| Maximum load | 8A 230Vac | 7A 24Vac | 8A 230Vac | 8A 230Vac |
| Sensor | NTC 10K Ohm @ 25°C | NTC 10K Ohm @ 25°C | NTC 10K Ohm @ 25°C | NTC 100K Ohm @ 25˚C |
| Operating temperature | 0 ... 50°C | 0 ... 50°C | 0 ... 50°C | 0 … 45˚C |
| Dimensions | 84 x 84 x 30mm | 84 x 84 x 30mm | 84 x 84 x 30mm | 130 x 99 x 25mm |