CONFIGURATION MENU
Press the SYSTEM button until OFF is displayed, then press the
and
simultaneously
INSTALLER/CONFIGURATION MENU
Press Displayed
Button(s) (Factory Default)
Press or
to select
Step
Comments
1
System
MS 2
FA
SS1, HP2, HP1
Selects Single stage, Multi-stage, or Heat Pump
(Single stage or 2-stage) System Configuration
2
3
System
System
SL
Selects Fast or Slow Cycle Selection
CL
CL
Selects Compressor Lockout CL OFF or ON
(OFF)
(ON)
4
5
System
System
CDL
(ON)
CDL
Selects Backlight Display
(OFF)
FA
FA
Selects Fast Second Stage ON or OFF
(ON)
(OFF)
6
7
System
System
0 FLTR
50-1950 (increments of 50)
Selects filter replacement run time
0°F
4 LO to 4 HI
Selects Temperature Display Adjustment 4 LO to 4 HI
(Room Temperature)
8
9
System
System
°F
°C
Selects temperature display F° or °C selection
AU On
OFF
Selects AUTO Mode ON or OFF
(Not available on earlier models)
10
11
12
13
14
15
System
System
System
System
System
System
LR
LR 62 to LR89
LR 46 to LR 82
Selects Limited HEAT range
Selects Limited COOL range
Feature Not Available
(90)
LR
(45)
CA
CA
(OFF)
(ON)
(ON)
Selects Keypad Lockout
(OFF)
0
001 to 999
Selects Keypad lockout combination number
Press System to set code
Returns to the OFF position
3) Select Compressor Lockout CL OFF or ON – Selecting
CL ON will cause the thermostat to wait 5 minutes before
turning on the compressor if the heating and cooling system
loses power. It will also wait 5 minutes minimum between
cooling and heating cycles. This is intended to help protect
the compressor from short cycling. Some newer compres-
sors already have a time delay built in and do not require
this feature. Your compressor manufacturer can tell you if
the lockout feature is already present in their system. When
the thermostat compressor time delay occurs it will flash the
setpoint for about five minutes.
the light on continuously. Select backlight OFF will keep
the light on momentarily after any key is pressed. When the
C terminal is not powered, this selection has no effect.
5) Select (Fast) Second Stage ON or OFF – In the run mode,
if the setpoint temperature is manually raised by 3°F (2°C)
or more above the actual temperature with the , and the
fast second stage feature is enabled, FA ON, the second
stage will energize immediately. With FA OFF, second
stage will not energize until the setpoint temperature is 1°F
or more above actual temperature for more than ten min-
utes.
4) Select Backlight Display – The display backlight improves
display contrast in low lighting conditions. When the C
terminal is powered, selecting backlight CdL ON will turn
6
| General | Details |
|---|---|
| Name | White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual |
| Make | WHITE RODGERS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.24 MB |

White-Rodgers 1F56N-444 Thermostat User Manual

White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual

White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual

White-Rodgers M30 Thermostat Instruction Manual

WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual

White Rodgers 1F78-151 Non Programmable Thermostat Instructions

WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual

WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual

WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual

WHITE-RODGERS 1F95-1277 Universal Thermostat Owner’s Manual