REGIN RCFD-230C Fan Coil Room Thermostat Instructions
EN
INSTRUCTION
RCFD-230C …
Technical Data
3. Place the back plate over the electrical wallbox and fasten it on the
wall using the mounting holes.
Supply voltage
230 V ~ (207…253 V ~ 50/60 Hz)
< 2 VA
4. Clip the display back onto the back plate.
Power consumption
Protection class
Ambient humidity
IP30
Wiring
10…90 %RH (non-condensing)
Ambient temperature
Measuring range, temperature
Sensor element, temperature
Accuracy, temperature
Display
0…50 °C
0…50 °C
NTC
Terminal Description
L
Supply voltage
N
Supply voltage
±0.5 K
FAN1
FAN2
FAN3
Heat
Cool
GND
DI
230 V AC Relay 1
Built-in
230 V AC Relay 2
Display type
LED-backlit LCD
NTC
230 V AC Relay 3
Output signal, temperature
Setpoint adjustment
Mounting
230 V AC Relay 4
5…35 °C
230 V AC Relay 5
Room (flush-mounted with screw dis-
tance cc 60 mm)
GND (for DI)
IN20013 REV. C, 2022-06-15
Digital input for presence detection, hotel key card etc
Analogue input for external PT1000 sensor, change-over
Installation
Fan-coils, 2- or 4-pipe
Temp
GND
Note! More information about the product can be found in the manual,
Digital inputs (DI)
Digital outputs (DO)
1 x Closing potential-free contact
Agnd for terminal Temp
3 x Relay outputs for 3-step fan control,
230 V AC, Max. 5 A
Serial communication port, Com N
Caution! Read and understand the instruction before using the product.
2 x Relay outputs for On/Off valve ac-
tuators, 230 V AC, Max. 5 A
A
B
Serial communication port, Com A
Serial communication port, Com B
Analogue inputs (AI)
Change-over function
Communication port
Internal serial port, type
1 x PT1000
Automatic
1
Caution! Ensure that the installation complies with local safety
regulations.
Warning! Before installation or maintenance, the power supply must first
be disconnected in order to prevent potentially lethal electric shocks! In-
stallation or maintenance of this unit should only be carried out by quali-
fied personnel. The manufacturer is not responsible for any eventual
damage or injury caused by inadequate skills during installation, or through
removal of or deactivation of any security devices.
RS485
Internal serial port, built-in protocol Modbus (RTU)
Internal serial port, communication 9600 bps (4800…38400 bps)
speed
Internal serial port, parity
Internal serial port, stop bit
Cable connection
Even (Even, Odd, None)
1 (1 or 2)
Function
Screw terminals max. 1.5 mm2 (AWG
16)
The room thermostat regulates the heating and/or cooling in a room via
on/off outputs for 2- or 4 pipe installations, and has a function for three-
speed fan control. The large LCD touch screen displays status and is also
used to access all parameters, such as setpoint, hysteresis, fan speed etc.
Dimensions, external (WxHxD)
95 x 95 x 50.5 mm
The unit has a built-in temperature sensor for controlling the room
temperature. The change-over function can be controlled using an
external PT1000 sensor or via a digital input connected to any potential
free contact. Functions such as mould protection and automatic valve
exercise ensures a proper functionality and a problem free installation
over time.
Installation
1. Separate the back plate from the display part with a small screw
driver. Insert the screw driver in the grooves at the bottom of the
unit.
Figure 1 4-pipe wiring
2. Connect the wires to the terminals.
RCFD-230C
1 (5)
| General | Details |
|---|---|
| Name | REGIN RCFD-230C Fan Coil Room Thermostat Instructions |
| Make | REGIN |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.26 MB |

Regin RCFD-230C Manual: Questions and Answers
What does the DI terminal on the Regin RCFD-230C mean?
DI is a digital input for presence detection, hotel key card etc. It accepts one closing potential-free contact. Instructions, p. 1
What do the Heat and Cool terminals control?
Heat and Cool are relay outputs for On/Off valve actuators, each rated 230 V AC with a maximum of 5 A.
| Terminal | Function |
|---|---|
| Heat | 230 V AC Relay 4, On/Off valve actuator |
| Cool | 230 V AC Relay 5, On/Off valve actuator |