REGIN RCFD-230C Fan Coil Room Thermostat Instructions

EN  
INSTRUCTION  
RCFD-230C …  
Technical Data  
3. Place the back plate over the electrical wallbox and fasten it on the  
wall using the mounting holes.  
Supply voltage  
230 V ~ (207…253 V ~ 50/60 Hz)  
< 2 VA  
4. Clip the display back onto the back plate.  
Power consumption  
Protection class  
Ambient humidity  
IP30  
Wiring  
10…90 %RH (non-condensing)  
Ambient temperature  
Measuring range, temperature  
Sensor element, temperature  
Accuracy, temperature  
Display  
0…50 °C  
0…50 °C  
NTC  
Terminal Description  
L
Supply voltage  
N
Supply voltage  
±0.5 K  
FAN1  
FAN2  
FAN3  
Heat  
Cool  
GND  
DI  
230 V AC Relay 1  
Built-in  
230 V AC Relay 2  
Display type  
LED-backlit LCD  
NTC  
230 V AC Relay 3  
Output signal, temperature  
Setpoint adjustment  
Mounting  
230 V AC Relay 4  
5…35 °C  
230 V AC Relay 5  
Room (flush-mounted with screw dis-  
tance cc 60 mm)  
GND (for DI)  
IN20013 REV. C, 2022-06-15  
Digital input for presence detection, hotel key card etc  
Analogue input for external PT1000 sensor, change-over  
Installation  
Fan-coils, 2- or 4-pipe  
Temp  
GND  
Note! More information about the product can be found in the manual,  
Digital inputs (DI)  
Digital outputs (DO)  
1 x Closing potential-free contact  
Agnd for terminal Temp  
3 x Relay outputs for 3-step fan control,  
230 V AC, Max. 5 A  
Serial communication port, Com N  
Caution! Read and understand the instruction before using the product.  
2 x Relay outputs for On/Off valve ac-  
tuators, 230 V AC, Max. 5 A  
A
B
Serial communication port, Com A  
Serial communication port, Com B  
Analogue inputs (AI)  
Change-over function  
Communication port  
Internal serial port, type  
1 x PT1000  
Automatic  
1
Caution! Ensure that the installation complies with local safety  
regulations.  
Warning! Before installation or maintenance, the power supply must first  
be disconnected in order to prevent potentially lethal electric shocks! In-  
stallation or maintenance of this unit should only be carried out by quali-  
fied personnel. The manufacturer is not responsible for any eventual  
damage or injury caused by inadequate skills during installation, or through  
removal of or deactivation of any security devices.  
RS485  
Internal serial port, built-in protocol Modbus (RTU)  
Internal serial port, communication 9600 bps (4800…38400 bps)  
speed  
Internal serial port, parity  
Internal serial port, stop bit  
Cable connection  
Even (Even, Odd, None)  
1 (1 or 2)  
Function  
Screw terminals max. 1.5 mm2 (AWG  
16)  
The room thermostat regulates the heating and/or cooling in a room via  
on/off outputs for 2- or 4 pipe installations, and has a function for three-  
speed fan control. The large LCD touch screen displays status and is also  
used to access all parameters, such as setpoint, hysteresis, fan speed etc.  
Dimensions, external (WxHxD)  
95 x 95 x 50.5 mm  
The unit has a built-in temperature sensor for controlling the room  
temperature. The change-over function can be controlled using an  
external PT1000 sensor or via a digital input connected to any potential  
free contact. Functions such as mould protection and automatic valve  
exercise ensures a proper functionality and a problem free installation  
over time.  
Installation  
1. Separate the back plate from the display part with a small screw  
driver. Insert the screw driver in the grooves at the bottom of the  
unit.  
Figure 1 4-pipe wiring  
2. Connect the wires to the terminals.  
RCFD-230C  
1 (5)  
GeneralDetails
NameREGIN RCFD-230C Fan Coil Room Thermostat Instructions
MakeREGIN
LanguageEnglish
FiletypePDF (Download)
File size0.26 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

REGIN RCFD-230C Fan Coil Room Thermostat Instructions
Get the free PDF manual for the REGIN RCFD-230C Fan Coil Room Thermostat Instructions and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Regin RCFD-230C Manual: Questions and Answers

What does the DI terminal on the Regin RCFD-230C mean?

DI is a digital input for presence detection, hotel key card etc. It accepts one closing potential-free contact. Instructions, p. 1

What do the Heat and Cool terminals control?

Heat and Cool are relay outputs for On/Off valve actuators, each rated 230 V AC with a maximum of 5 A.

TerminalFunction
Heat230 V AC Relay 4, On/Off valve actuator
Cool230 V AC Relay 5, On/Off valve actuator