INSTALLER/CONFIGURATION MENU  
4) Energy Management Recovery: (this step is skipped if  
configured to be non-programmable).  
9) System Mode Configuration – This thermostat is configured  
for Heat and Cool withAuto changeover (SYSTEM switch with  
Cool Off HeatAuto) default. It can also be configured for Heat  
and Cool (Cool Off Heat), Heat only with fan (Off Heat), Heat  
only without fan, Auto only (Auto Off), and Cool only (Cool  
Off).  
Energy Management Recovery (E) On enables the ther-  
mostat to start heating or cooling early to make the building  
temperature reach the program setpoint at the time you  
specify. Heating will start 5 minutes early for every 1° of  
temperature required to reach setpoint.  
10)Select Backlight Display – The display backlight improves  
display contrast in low lighting conditions. When the "C" termi-  
nal is powered, selecting backlight CdL ON will keep the light  
on continuously. Select backlight OFF will keep the light on  
momentarily after any key is pressed. When the "C" terminal  
is not powered, the light will be on momentarily after any key  
is pressed no matter whether the backlight is selected ON or  
OFF.  
Example: If E On is selected and have your heating pro-  
grammed to 65° at night and 70° at 7 AM. If the building  
temperature is 65°, the difference between 65° and 70° is  
5°. Allowing 5 minutes per degree, the thermostat setpoint  
will change to 70° at 6:35 AM. Cooling allows more time per  
degree, because it takes longer to reach set temperature.  
5, 6 & 7) Cycle Rate Selection – The factory default settings  
with SS/HP switch in SS position for Heat is medium  
cycle (ME) and Cool is fast cycle (FA). For Heat Pump  
(HP), the default setting is fast cycle (FA).  
11)Select Temperature Display Adjustment 4 LO to 4 HI.  
Allows you to adjust the room temperature display up to 4°  
higher or lower. Your thermostat was accurately calibrated  
at the factory, but you have the option to change the display  
temperature to match your previous thermostat. The current  
or adjusted room temperature will be displayed on the left  
side of the display.  
To change cycle rate, press the  
or  
key.  
Cycle rate differentials for different settings are:  
Fast  
FA  
Medium  
ME  
Slow  
SL  
MODE  
12)Select F° or C° Readout – Changes the display readout to  
Heat (SS)  
Cool (SS)  
0.4°F  
1.2°F  
0.6°F  
1.8°F  
1.7°F  
Centigrade or Fahrenheit as required.  
Heat Pump (HP)  
1.2°F  
1.7°F  
13)Select Filter Replacement Reminder and Set Run Time.  
Select the "Change Filter" reminder On or OFF. If selected  
On, press MENU to select the time period from 25 to 1975  
hours in 25 hours increments. In a typical system, 200 hours  
(default) of run time is approximately 30 days. After the se-  
lected time of blower operation, the thermostat will display  
"Change Filter" as a reminder to change or clean your air  
filter. When "Change Filter" is displayed, press MENU but-  
ton to clear the display and restart the time to the next filter  
change.  
8) Select Compressor Lockout CL OFF or ON – Selecting  
CL ON will cause the thermostat to wait 5 minutes between  
cooling cycles. This is intended to help protect the compres-  
sor from short cycling. Some newer compressors already  
have a time delay built in and do not require this feature. Your  
compressor manufacturer can tell you if the lockout feature  
is already present in their system. When the thermostat  
compressor time delay occurs, it will flash the setpoint for  
up to five minutes.  
5
GeneralDetails
NameWHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual
MakeWHITE RODGERS
LanguageEnglish
FiletypePDF (Download)
File size0.51 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual
White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual
White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual
White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual
White-Rodgers 1F56N-444 Thermostat User Manual
White-Rodgers 1F56N-444 Thermostat User Manual
White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual
White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual
White-Rodgers M30 Thermostat Instruction Manual
White-Rodgers M30 Thermostat Instruction Manual
WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual
WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual
White Rodgers 1F78-151 Non Programmable Thermostat Instructions
White Rodgers 1F78-151 Non Programmable Thermostat Instructions
WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual
WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F95-1277 Universal Thermostat Owner’s Manual
WHITE-RODGERS 1F95-1277 Universal Thermostat Owner’s Manual

WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual