Take care to ensure excess wiring is not trapped between the cases half’s when closing - push  
excess wires into the wall cavity. Never press on the LCD when closing the SMT-131 as it may  
crack. Always press on the SMT-131 plastic case only.  
DIP Switch Settings  
Switch  
Sw1  
Sw2  
Function  
On  
3 Fan Speed  
Heat Pump  
Off  
1 Fan Speed  
Heat Cool  
Indoor Fan Mode  
Equipment Type  
HP Mode (Sw2= ON)  
HC Mode (Sw2=OFF)  
Sw3  
Rev Valve Heat (B)  
HE Fan With Heat  
Rev Valve Cool (O)  
HG No Fan In Heat  
Sw4  
Sw5  
Sw6  
Sw7  
Sw8  
2 / 4 pipe mode  
Comp Protection Delay  
Klixon Mode  
2 pipe mode  
5 Min Anti Cycle  
On  
4 pipe Mode  
Immediate Comp start  
Off  
Ventilation Mode  
Door Station (Optional)  
Permitted  
Fitted  
Not Permitted  
Door Station Not Used  
Note: The SMT-131 reads the switch settings on power up only. If you change any DIP switch  
settings you must power cycle before these changes will take effect.  
It is expected that only qualified people will make adjustment to these dip switch settings.  
Knowledge of the HVAC system under the control of the SMT-131 is essential prior to making  
adjustment to these DIP switch settings.  
Caution Incorrect adjustment of these DIP switch settings could cause HVAC  
equipment damage. This would NOT be covered by warranty.  
Wiring HVAC Control  
Terminal Designations  
Terminal  
C
Function  
24V Neutral  
R
24V Active - This voltage is switched back through the relays  
Indoor Fan High Speed (NOT Used in Single fan speed mode - Sw 1 = OFF)  
Indoor Fan Medium Speed (NOT Used in Single fan speed mode - Sw 1 = OFF)  
Indoor Fan Low Speed (Used in single & three fan speed mode)  
Compressor or Cool - (Based on Sw 2 setting)  
Hi  
Med  
Low  
Y
W - O/B  
Reversing Valve or Heat - (Based on Sw 2 setting)  
A1 Cool  
A2 Heat  
0-10V Output for Cooling (Typically used to control modulating valves)  
0-10V Output for Heating (Typically used to control modulating valves)  
0-10V Modulating Output for Indoor DC Fan  
A3 Fan  
Com 0V  
0V terminal - Used for 0-10V, sensor or digital inputs ground reference  
Modbus Data A  
Modbus Data B  
A
B
SI  
Remote temperature sensor input (Remote / average / Modbus data use)  
Digital (Switched input) for forced un-occupied or initiate doorbell function  
Window Contact - Forces SMT-131 OFF if window open > 5 min (Adjustable)  
Door Switch Monitors room door status for occupancy detection (see page 11)  
PIR (Movement sensor) input for occupancy detection (see page 11)  
DI  
WC  
DS  
PIR  
Page 5  
       
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual