ELKO ep TER-4 Double Thermostat Owner’s Manual
EN
TER-4
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Double thermostat with a range of −40 .. +110 °C
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
Made in Czech Republic
02-8/2023 Rev.: 0
Characteristics
Symbol
• Used for temperature monitoring in switchboards, heating or cooling systems,
engines, liquids, open spaces, etc.
18
A1
16
26 28
• Double thermostat for temperature monitoring and regulation over a wide range.
• Rough and fine temperature setting for each thermostat.
• Galvanically isolated power supply AC/DC 24 – 240 V.
• 2× input for temperature sensor NTC 12 k/25 °C.
T1
T1
T2
T2
• Setting the independent or dependent function of thermostats.
• Selection of heating/cooling function.
A2
15
25
• Selectable hysteresis (sensitivity) of switching.
• Two output contacts (separate for each thermostat).
Connection
1.
sensor sensor
2.
Un
A1 A2 T1 T1 T2 T2
Description
1. Supply voltage indication
13
12
2. Thermostat contact indication /
sensor failure (T1)
5
16 15 18 28 25 26
3. Sensor fault indication
1
4. Thermostat contact indication /
sensor failure (T2)
Temperature sensors
6
2
3
4
5. DIP switch
7
8
9
6. Fine temperature setting (T1)
7. Rough temperature setting (T1)
8. Fine temperature setting (T2)
9. Rough temperature setting (T2)
10. Output contact 1 (16-15-18)
11. Output contact 2 (28-25-26)
12. Supply voltage terminals (A1-A2)
13. Sensor connection terminals (T1/ T2)
Temperature sensors for range –20 .. +80 °C (–4 °F .. 176 °F)
TC-0 sensor, 10 cm (3.94´), double insulation, polyamide cable end
TC-3 sensor, 3 m (118.11´), double insulation, polyamide cable end
TC-6 sensor, 6 m (236.22´), double insulation, polyamide cable end
TC-12 sensor, 12 m (472.44´), double insulation, polyamide cable end
11
10
Temperature sensors for range –40 .. +125 °C (-40 °F .. 257 °F)
TZ-0 sensor, 11 cm (4.34´), double silicone insulation, stainless steel cable end
TZ-3 sensor, 3 m (118.11´), double insulation silicone, stainless steel cable end
TZ-6 sensor, 6 m (236.22´), double insulation silicone, stainless steel cable end
TZ-12 sensor, 12 m (472.44´), double insulation silicone, stainless steel cable end
Description of DIP switch
Independent/dependent
function of thermostats
Function IND
Function Heat
DEP
Cool
2.5
Heating/cooling function
Hysteresis of thermostat T1
Hysteresis of thermostat T2
Hysteresis 1 0.5
Hysteresis 2 0.5
2.5
HAL.230V
M
M
Type of load
cos φ ≥ 0.95
AC5a
uncompensated
AC5a
compensated
AC1
AC2
AC3
AC5b
800W
AC6a
x
AC7b
AC12
Contact material
AgNi, 16A
x
250V / 16A
250V / 5A
250V / 3A
230V / 3A (690VA)
250V / 3A
250V / 10A
M
M
K
Type of load
DC3
AC13
AC14
AC15
DC1
DC5
DC12
DC13
DC14
Contact material
AgNi, 16A
24V / 6A
250V / 6A
250V / 6A
250V / 6A
24V / 16A
24V / 4A
24V / 16A
24V / 2A
24V / 2A
1 / 2
| General | Details |
|---|---|
| Name | ELKO ep TER-4 Double Thermostat Owner’s Manual |
| Make | ELKO ep |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.63 MB |

ELKO ep TEV-1 Thermostat Owner’s Manual

ELKO ep TER-4 Double Thermostat Owner’s Manual Overview
Summary of Contents
- Page 1: Double thermostat with a range of −40 .. +110 °C Used for temperature monitoring in switchboards, heating or cooling systems, engines, liquids, open spaces, etc. Double thermostat for temperature monitoring and regulation over a wide range. Rough and fine temperature setting for each thermostat. Galvanically isolated power supply AC/DC 24 – 240 V. 2× input for temperature sensor NTC 12 k/25 °C. Setting the independent or dependent function of thermostats. Selection of heating/cooling function. Selectable hysteresis (sensitivity) of switching. Two output contacts (separate for each thermostat).
- Page 2: Technical parameters Each thermostat has its own sensor, rough and fine temperature setting, selectable hysteresis, and its separated output contact. The desired temperature is set as the sum value of the selected rough and fine temperature setting. The device monitors the fault state of each sensor (short circuit or interruption) - if a sensor malfunction occurs, the yellow LED lights up and the corresponding red LED flashes. The device can also be operated as a simple thermostat (with one sensor). Independent function of thermostats: The device acts as two separate simple thermostats. Dependent function of thermostats: Thermostats are connected in series - i.e., thermostat T1 is blocked by thermostat T2. This device is constructed for connection in 1-phase network AC/DC 24 – 240 V and must be installed according to norms valid in the state of an application. Installation, connection, setting, and servicing must be carried out by qualified electrician staff only. Ensure correct installation by perfect air circulation so that during continuous operation and a higher ambient temperature, the device does not exceed the maximum allowed operating temperature. The product must be treated as electronic waste at the end of its life.