Home > SMART TEMP > SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

The 3 x 0-10V (40040 (Heat), 40041 (Cool) & 40068 (Fan)), outputs can be controlled by Modbus  
at any time without restriction.  
To permit Modbus to control the output first enter 1000 in the register you wish to override, it is  
then unlocked from SMT-131 control and you are then permitted to enter the value you wish  
the selected output to be; such as 0=relay OFF and 1 1=relay ON or 63 should you wish the 0-10v  
to output 6.3v.  
To return the output to SMT-131 control simply enter 1001 into the register.  
Please Note - Writing to the relays or 0-10V output via Modbus bypasses the SMT-131 internal  
memory protection logic. Changing these values regularly via Modbus may reduce the  
thermostats memory life to only a few years. Using this function will void the SMT-131  
warranty for the memory chip within the thermostat.  
40035  
40036  
40037  
40038  
40039  
Read Only  
Read Write  
(3.09+)  
W relay status  
0 = Off (under thermostat control)  
1 = Energised (under thermostat control)  
1000 = Held OFF by Modbus  
1001 = Held ON by Modbus  
Read Only Y Relay Status  
Read Write  
(3.09+)  
0 = Off (under thermostat control)  
1 = Energised (under thermostat control)  
1000 = Held OFF by Modbus  
1001 = Held ON by Modbus  
Read Only High Fan Relay  
Read Write Status  
(3.09+)  
0 = Off (under thermostat control)  
1 = Energised (under thermostat control)  
1000 = Held OFF by Modbus  
1001 = Held ON by Modbus  
Read Only Medium Fan Relay  
Read Write Status  
(3.09+)  
0 = Off (under thermostat control)  
1 = Energised (under thermostat control)  
1000 = Held OFF by Modbus  
1001 = Held ON by Modbus  
Read Only Low Fan Relay  
Read Write Status  
(3.09+)  
0 = Off (under thermostat control)  
1 = Energised (under thermostat control)  
1000 = Held OFF by Modbus  
1001 = Held ON by Modbus  
40040  
40041  
40042  
Read Only 0-10V Heat Value  
Read Write  
(3.09+)  
Value / 10 (e.g. 7.3V = 73)  
(To write add 10 e.g. - to write 7.3v send  
1073  
Read Only 0-10V Cool Value  
Read Write  
(3.09+)  
Value / 10 (e.g. 2.1V = 21)  
(To write add 10 e.g. - to write2.1v send 1021  
Read Only  
Permitted Modes  
(ver 2.1+ only)  
0 = Auto (Heating and cooling called)  
1 = Heat Only Mode  
2 = Cool Only Mode  
Values below only apply to version 2 hardware only, Firmware version 3+  
40043  
40044  
40045  
Read  
Write  
Read  
Write  
Read  
Write  
/
/
/
2 pipe mode  
changeover  
Thermostat  
Displaying  
0 = Heat  
1 = Cool  
0 = Deg C  
1 = Deg F  
Buttons shown on  
display  
0: Both mode and fan buttons show (default)  
1: Show mode but hide fan button  
2: Show fan but hide mode button  
Page 22  
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual