Home > SMART TEMP > SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

and run before heat or cool calls from the W & Y relays.  
43 Thermostat response to  
changes in room  
0: Very Fast  
1: Fast  
Temperature Ver 4.04+  
2: Normal  
3: Slow (Default)  
4: Very Slow  
44 Firmware Ver 41.1 +  
2 Pipe heating threshold  
45 Firmware Ver 41.1 +  
2 Pipe cooling threshold  
Range 5 to 50 (default 30c)  
Range 5 to 50 (default 20c)  
t
Temperature calibration  
Offset Ver 4.04+  
-9.9c to +10c 0.0 (Default)  
This permits you to apply a correction offset factor to the  
room (or remote) temperature sensor used by the SMT-131.  
0: NO  
r
Factory Reset  
1:Yes (Exit to initiate)  
Modbus Data Addendum 1  
The SMT-131 has integrated Modbus RTU communications. Using a Modbus master controller  
such as the Smart Temp 770-HMI many of the SMT-131 thermostat features can be centrally  
controlled and monitored.  
Modbus is a simple protocol that is extremely popular due to its robustness and simple  
implementation. It is also a “forgiving” protocol and will tolerate many installation errors. This  
being stated however; correct wiring practices should be used to achieve maximum reliability.  
See page 10 for details on wiring Modbus networks.  
The SMT-131 Modbus data is within the “40XXX” range, this being holding registers. Depending  
on your choice of Modbus Master you may need to enter the address using the full address - such  
as “40012” or by selecting “Holding Registers” and entering the address simply as “12”.  
These modbus registers are shown as Base “1” (PLC addressing) format. Depending on your  
modbus master addressing format you may need to subtract 1 from these values to convert to  
base “0” (protocol addressing) format.  
Note - The Modbus data layout may seem unorganised in this document, for example 0-10v for  
heat and cool is at register 40040 & 40041 while the 0-10V output for the fan is at register 40068.  
This is done to maintain backwards compatibility with the SMT-131 version 1 ModBus registers.  
All the new functions added to version 2 of the SMT-131 have their Modbus registers at the end  
of the version 1 SMT-131 Modbus register list.  
Page 18  
 
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual