GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual
Glass Low Limit Thermostat
TLGL Series - Installation Instructions
INTRODUCTION
The low limit glass thermostat incorporates
a
precision thermistor
temperature sensor and provides a Form C relay output (NO/NC) with an
adjustable setpoint. The sensor is encapsulated in a 31.75mm L x 9.525mm W
x 9.525mm H (1.25" x 0.375" x 0.375") Aluminum probe. Standard wire length
is 1.5 m (5'). All probes are constructed to provide excellent heat transfer, fast
response and are potted to resist moisture penetration.
BEFORE INSTALLATION
Read these instructions carefully before installing and commissioning
the temperature sensor. Failure to follow these instructions may result in
product damage. Do not use in an explosive or hazardous environment,
with combustible or flammable gases, as a safety or emergency stop
device or in any other application where failure of the product could
result in personal injury. Do not exceed the device ratings.
MOUNTING
The glass thermostat installs directly onto any window where the enclosure can be mounted nearby. Select a suitable location on an exterior
window where both the probe and the enclosure can be mounted. On one side of the probe apply epoxy compound and press firmly against
the glass. See Figure 1. Use whatever means available (electrical tape will do) to secure the probe to the window while the epoxy sets.
Unroll the sensing cable probe, being careful not to kink the wire. Secure the enclosure to the wall with two #10 x 25 mm (1”) self tapping screws
(not provided). Tighten screws until the enclosure is tight against the wall and ensure that there is no movement of the enclosure as shown in
Figure 1.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the right side of the enclosure, at the same time
pulling on the cover, as illustrated in Figure 2.
Figure 1
A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw
the EMT connector or cable gland connector in until tight. See Figure 3. It is recommended
that weatherproof conduit or cable gland fittings be used. An optional 1/2" NPT to M16
thread adapter and cable gland fitting is available.
Make wire connections as per the“Wiring”illustrations on Page 2.
Swing door closed until securely latched. For added security, two screws are provided
that may be installed in the integrated screw tabs. See Figure 4.
Figure 2
Figure 3
Figure 4
Thread adapter and
cable gland fitting
EMT Connector
Page 1
IN-GE-TLGLXXX-003
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
| General | Details |
|---|---|
| Name | GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual |
| Make | Greystone |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.2 MB |

GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual

GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual

GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual

GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual

Greystone TLGLF24X01 Manual: Questions and Answers
Greystone TLGLF24X01 specifications
| Power supply | 12 to 28 Vac/dc |
| Operating temperature | -10 to 50°C (14 to 122°F),53.7 mm |
| Power consumption | 50 mA max |
What is the adjustable setpoint range for Greystone TLGLF24X01?
-4 to 10°C (25 to 50°F). Instruction Manual, p. 2
What do the PWR, COM, and NO/COM/NC terminals do on Greystone TLGLF24X01?
PWR receives DC positive or AC hot; COM is the supply common; NO/COM/NC carries relay output.
| Terminal | Function |
|---|---|
| PWR | DC positive or AC voltage hot side |
| COM | Supply common |
| NO/COM/NC | Relay output contacts |
How do I install Greystone TLGLF24X01 on a window?
Mount the probe and enclosure to an exterior window, secure the probe with epoxy, and fasten the enclosure with two screws.
- Apply epoxy to one side of the probe and press firmly against the glass
- Secure the probe with electrical tape while epoxy sets
- Mount the enclosure to the wall with two #10 x 25 mm self-tapping screws
- Tighten screws until enclosure is tight and has no movement Instruction Manual, p. 1