GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual

Outside Low Limit Thermostat  
TLOS Series - Installation Instructions  
INTRODUCTION  
The single point outside air low limit thermostat incorporates a precision  
thermistor temperature sensor and provides a Form C relay output (NO/NC)  
with an adjustable setpoint. All probes are constructed to provide excellent  
heat transfer, fast response and are potted to resist moisture penetration. A  
hinged and gasketed weatherproof Polycarbonate enclosure is provided for  
ease of installation.  
BEFORE INSTALLATION  
Read these instructions carefully before installing and commissioning  
the thermostat. Failure to follow these instructions may result in product  
damage. Do not use in an explosive or hazardous environment, with  
combustible or flammable gases, as a safety or emergency stop device or in  
any other application where failure of the product could result in personal  
injury. Do not exceed the device ratings.  
MOUNTING  
Select a suitable mounting spot on an exterior wall where the temperature sensor is best protected from direct exposure to sunlight, wind, etc.  
preferably on a north facing wall. Do not mount the sensor near opening windows, supply/exhaust air louvres or other known air disturbances.  
Avoid areas where the sensor is exposed to vibrations or rapid temperature changes.  
The temperature sensor provides a connection hole for 1/2" conduit. Run a length of conduit through exterior wall and seal. Use 14-24 AWG  
shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as  
motors. Make all connections in accordance with national and local codes.  
Figure 1  
The temperature sensor installs directly on an exterior wall using the two integrated  
mounting holes provided on the enclosure. Select the best mounting technique based  
on the exterior wall material. The two mounting holes are suitable for a #10 size screw  
(not supplied). The sensor fitting must be pointing down. See Figure 1.  
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on  
the latch on the right side of the enclosure. At the same time pulling on the cover, as  
illustrated in Figure 2.  
A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw  
the EMT connector or cable gland connector in until tight. See Figure 3. It is recommended  
that weatherproof conduit or cable gland fittings be used. An optional 1/2" NPT to M16  
thread adapter and cable gland fitting is available.  
Figure 2  
Make wiring connections as per the“wiring”illustrations on Page 2.  
Swing door closed until securely latched. For added security, two screws are provided  
that may be installed in the integrated screw tabs. See Figure 4.  
Figure 3  
Figure 4  
Thread adapter and  
cable gland fitting  
Conduit Connection  
Page 1  
IN-GE-TLOSXXX-004  
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com  
GeneralDetails
NameGREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual
MakeGreystone
LanguageEnglish
FiletypePDF (Download)
File size0.18 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual
GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual
GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual
GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual

GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual
Get the free PDF manual for the GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Greystone TLOSF24X01 TLOS Manual: Questions and Answers

Greystone TLOSF24X01 TLOS specifications

Power supply12 to 28 Vac/dc
DifferentialLow: 1.1°C (2°F) Mid: 2.8°C (5°F) High: 5.6°C (10°F)
Power consumption50 mA max

Full specifications, page 2

Where is the setpoint potentiometer on Greystone TLOSF24X01?

On the PCB inside the enclosure. Turn it to set the desired temperature. Instruction Manual, p. 2

How do I connect Greystone TLOSF24X01 TLOS to a 24 Vdc power supply?

Connect the positive terminal to PWR and the common to COM. Pull at least six inches of control wire into the enclosure first.

  1. Deactivate the 24 Vdc power supply before making connections.
  2. Pull at least six inches of control wire into the enclosure.
  3. Connect DC positive to the PWR terminal.
  4. Connect supply common to the COM terminal.
  5. Set the jumper for setpoint differential (Low, Mid, or High).
  6. Turn the setpoint potentiometer to the desired temperature setting. Instruction Manual, p. 2

What is the adjustable setpoint range of Greystone TLOSF24X01 TLOS?

-4 to 10°C (25 to 50°F). Instruction Manual, p. 2