GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual
Outside Low Limit Thermostat
TLOS Series - Installation Instructions
INTRODUCTION
The single point outside air low limit thermostat incorporates a precision
thermistor temperature sensor and provides a Form C relay output (NO/NC)
with an adjustable setpoint. All probes are constructed to provide excellent
heat transfer, fast response and are potted to resist moisture penetration. A
hinged and gasketed weatherproof Polycarbonate enclosure is provided for
ease of installation.
BEFORE INSTALLATION
Read these instructions carefully before installing and commissioning
the thermostat. Failure to follow these instructions may result in product
damage. Do not use in an explosive or hazardous environment, with
combustible or flammable gases, as a safety or emergency stop device or in
any other application where failure of the product could result in personal
injury. Do not exceed the device ratings.
MOUNTING
Select a suitable mounting spot on an exterior wall where the temperature sensor is best protected from direct exposure to sunlight, wind, etc.
preferably on a north facing wall. Do not mount the sensor near opening windows, supply/exhaust air louvres or other known air disturbances.
Avoid areas where the sensor is exposed to vibrations or rapid temperature changes.
The temperature sensor provides a connection hole for 1/2" conduit. Run a length of conduit through exterior wall and seal. Use 14-24 AWG
shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as
motors. Make all connections in accordance with national and local codes.
Figure 1
The temperature sensor installs directly on an exterior wall using the two integrated
mounting holes provided on the enclosure. Select the best mounting technique based
on the exterior wall material. The two mounting holes are suitable for a #10 size screw
(not supplied). The sensor fitting must be pointing down. See Figure 1.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on
the latch on the right side of the enclosure. At the same time pulling on the cover, as
illustrated in Figure 2.
A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw
the EMT connector or cable gland connector in until tight. See Figure 3. It is recommended
that weatherproof conduit or cable gland fittings be used. An optional 1/2" NPT to M16
thread adapter and cable gland fitting is available.
Figure 2
Make wiring connections as per the“wiring”illustrations on Page 2.
Swing door closed until securely latched. For added security, two screws are provided
that may be installed in the integrated screw tabs. See Figure 4.
Figure 3
Figure 4
Thread adapter and
cable gland fitting
Conduit Connection
Page 1
IN-GE-TLOSXXX-004
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
| General | Details |
|---|---|
| Name | GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual |
| Make | Greystone |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.18 MB |

GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual

GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual

GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual

GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual

Greystone TLOSF24X01 TLOS Manual: Questions and Answers
Greystone TLOSF24X01 TLOS specifications
| Power supply | 12 to 28 Vac/dc |
| Differential | Low: 1.1°C (2°F) Mid: 2.8°C (5°F) High: 5.6°C (10°F) |
| Power consumption | 50 mA max |
Where is the setpoint potentiometer on Greystone TLOSF24X01?
On the PCB inside the enclosure. Turn it to set the desired temperature. Instruction Manual, p. 2
How do I connect Greystone TLOSF24X01 TLOS to a 24 Vdc power supply?
Connect the positive terminal to PWR and the common to COM. Pull at least six inches of control wire into the enclosure first.
- Deactivate the 24 Vdc power supply before making connections.
- Pull at least six inches of control wire into the enclosure.
- Connect DC positive to the PWR terminal.
- Connect supply common to the COM terminal.
- Set the jumper for setpoint differential (Low, Mid, or High).
- Turn the setpoint potentiometer to the desired temperature setting. Instruction Manual, p. 2
What is the adjustable setpoint range of Greystone TLOSF24X01 TLOS?
-4 to 10°C (25 to 50°F). Instruction Manual, p. 2