Home > Greystone > GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual
Flexible Copper Duct Average
Low Limit Thermostat
TLDC Series - Installation Instructions
INTRODUCTION
The flexible copper duct average temperature thermostat incorporates
numerous precision thermistor temperature sensors and provides a
Form C relay output (NO/NC) with an adjustable setpoint. The sensor is
encapsulated in a 7.94 mm (0.3125”) OD, soft copper tube and is available
in various lengths. All probes provide excellent heat transfer, fast response
and resist moisture penetration.
BEFORE INSTALLATION
Read these instructions carefully before installing and commissioning
the temperature sensor. Failure to follow these instructions may result in
product damage. Do not use in an explosive or hazardous environment,
with combustible or flammable gases, as a safety or emergency stop
device or in any other application where failure of the product could
result in personal injury. Do not exceed the device ratings.
MOUNTING
The sensor installs directly into any air duct with several lengths available for a wide range of duct widths/diameters. Select a suitable installation
area in the middle of the duct wall. To achieve the best reading, do not place in an area where air stratification may be present. Mount the sensor
at least 1.5 m (5 ‘) in either direction from elbows, dampers, filters or other duct restrictions. Avoid areas where the sensor is exposed to vibrations
or rapid temperature changes.
Once a suitable spot is selected, drill a 9.5 - 12 mm (3/8”- 1/2“) hole. Uncoil the copper probe and slide into the drilled hole until the enclosure is flush
against the duct. The airflow direction is not important. Secure the enclosure to the duct with #10 x 25 mm (1”) self tapping screws (not provided).
Tighten screws until the enclosure is tight against the duct and ensure that there is no movement of the enclosure as shown in Figure 1.
A foam gasket is provided on the back of the enclosure that provides a tight seal against
any air leaks.
Figure 1
The probe can easily be shaped to fit any duct size, but observe a minimum bend radius of
4” to prevent damage to the wire or sensors. Criss-cross the duct multiple times so that the
probe covers a large section of the duct. The probe needs to be fastened onto hangers using
tube clamps or wire ties. See Figure 2.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the
latch on the right side of the enclosure, at the same time pulling on the cover, as illustrated
in Figure 3.
A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw the
Hanger Straps
Figure 2
EMT connector or cable gland connector in until tight. See Figure 4. It is recommended that
weatherproof conduit or cable gland fittings be used. A 1/2" NPT to M16 thread adapter and
cable gland fitting is availble.
Make wiring connections as per the“Wiring”illustrations on Page 2.
Swing door closed until securely latched. For added security, 2 screws are provided that may
be installed in the integrated screw tabs. See Figure 5.
Figure 3
Figure 4
Figure 5
Thread adapter and
cable gland fitting
EMT Connector
Page 1
IN-GE-TLDCXXX-003
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
| General | Details |
|---|---|
| Name | GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual |
| Make | Greystone |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.19 MB |

GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual

GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual

GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual

GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual















