Home > SMART TEMP > SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

40046  
Read  
Write  
/
Permitted Modes  
0: Off / Auto  
1: Off / Heat / Cool / Auto  
2: Off / Heat / Cool  
3: Off / Heat  
4: Off / Cool  
5: Off / Auto (display current mode in LCD)  
0: C/F Button hidden  
1: C/F button shown  
40047  
40048  
40049  
40050  
40051  
40052  
40053  
40054  
40055  
40056  
40057  
40058  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
/
/
/
/
/
/
/
/
/
/
/
/
Swap C/F display  
shown on display  
Fan Span  
0.5C-10 C 0.5C step 1.0F-20 F 1F steps  
Data format: Fan span * 10  
10-300 seconds in 10 second steps (60  
seconds default.  
0-10 Fan Interval  
0-10 Fan Direction  
0: 10V is 100% open (forward acting)  
1: 0V is 100% open (reverse acting)  
0-10v (Fan value x 10)  
0-10 Fan Minimum  
Voltage.  
0-10 Heat Interval  
10-300 seconds in 10 second steps (60  
seconds default.  
0-10 Heat Direction  
0: 10V is 100% open (forward acting)  
1: 0V is 100% open (reverse acting)  
0-10v (Heat value x 10)  
0-10 Heat  
Minimum Voltage  
0-10 Cool Interval  
10-300 seconds in 10 second steps (60  
seconds default.  
0-10 Cool Direction  
0: 10V is 100% open (forward acting)  
1: 0V is 100% open (reverse acting)  
0-10 Cool Minimum 0-10v (Cool value x 10)  
Voltage  
Window input logic  
0: Normally Open  
1: Normally closed  
2: Off (input disabled)  
3: Shows FLT (FAULT) shown on LCD  
alternating with temperature display.  
40059  
40060  
Read  
Write  
Read  
Write  
/
/
Window input  
Delay  
Door input logic  
0-300 seconds in 30 second steps  
0: Off  
1: Normally Open  
2: Normally closed  
0-300 seconds in 30 second steps  
40061  
40062  
Read  
Write  
Read  
Write  
Read  
Write  
/
/
/
Door input Delay  
PIR input Delay  
(Seek Time)  
Unit run time log  
0: Off  
1-60 minutes in 1-minute steps  
0-9999.9 hours  
40063  
40064  
Register 40063 & 40064 are to be used together to determine the total Heat & Cool run time in  
0.1 hours.  
For example, for a total run time of 15643.4 hours register 40064 will show 434 and register  
40063 will show 156  
40065  
Read Only  
Window Input  
Status  
0: Open  
1: Closed  
Page 24  
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual