Home > SMART TEMP > SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

40024  
Read  
Write  
/
Unoccupied Fan  
Mode  
3 Fan Speed Mode  
1 = Low (Fan Auto)  
2 = Med (Fan Auto)  
3 = High (Fan Auto)  
4 = Low (Fan On)  
5 = Med (Fan On)  
6 = High (Fan On)  
1 Fan Speed Mode  
0 = Fan Auto  
4 = Fan On  
40025  
40026  
Read  
Write  
/
/
Backlight  
0 = On with Button Press only  
1 = Always On (High)  
2 = Always On Low - High With Button Press  
0 = Replace On Board Sensor with Remote  
1 = Average On board Sensor with Remote  
Read  
Write  
Remote “SI & Com  
0-V Temperature  
Input Function  
2
Monitor)  
=
Modbus Use Only (e.g. Coil Temp  
3: 2 pipe monitor  
0 = Occupancy Initiate  
1 = Chime Door Bell  
40027  
Read  
Write  
/
Digital Input  
Function  
2 = Input Disabled (Ver 3.09+)  
0 = Leave fan mode unchanged  
1 = Reset fan to Auto at switch off  
0 = Standard 0-10V Valve Logic  
1 = Belimo 6V = Off 3 Way Valve Logic  
1 to 255  
40028  
40029  
40030  
40031  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
/
/
/
/
Reset Fan Mode  
Belimo Mode  
Modbus Address  
Baud Rate  
1 = 4.8Kbs  
2 = 9.6kbs  
3 = 19.2Kbs  
0 = Open  
1 = Closed  
Value / 10 (e.g. 23.3°C = 233)  
40032  
40033  
40034  
Read Only  
Read Only  
Read Only  
Digital Input Status  
Internal Sensor  
Value  
Remote Sensor  
Value  
Value / 10 (e.g. 21.8°C = 218)  
Version 3.09+ firmware provides the ability for Modbus to override all the SMT-131 outputs.  
(5 x relays & 3 x 0-10v).  
Note - To protect equipment functions the following rules apply.  
To override register 40035 (W relay).  
The anticycle timer must be OFF. (SW 5=Off).  
To override register 40036 (Y relay)  
The mode must be Heat Cool (Sw2=OFF) and the anticycle timer must be OFF. (SW 5 = Off)  
To override register 40037 (High fan relay)  
Single fan speed (Sw1=OFF) must be selected and the mode must be Heat Cool (Sw2=OFF)  
To override register 40038 (Med fan relay)  
Single fan speed (Sw1=OFF) must be selected and the mode must be Heat Cool (Sw2=OFF)  
To override register 40039 (Low fan relay)  
The mode must be Heat Cool (Sw2=OFF)  
Page 21  
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual