Home > SMART TEMP > SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual

5
6
7
High temp set limit  
Low temp set limit  
Dead band  
5C-30C or 41F-86F (Ver41.0+ 5-50c or 41-122F)  
5C-30C or 41F-86F  
0C-5.0C or 0F-10.0F in 0.1C/0.1F steps.  
Depending on Option 3 above.  
Data format: Dead band * 10  
0: OFF  
8
Fan Purge / Run On Period  
1: Fan purge - 1 min  
2: Fan purge - 3 min  
3: Fan purge - 5 min  
4: Fan purge - 10 min  
5: Heat only fan purge - 1 min  
6: Heat only fan purge - 3 min  
7: Heat only fan purge - 5 min  
8: Heat only fan purge - 10 min  
9: Cool only fan purge - 1 min  
10: Cool only fan purge - 3 min  
11: Cool only fan purge - 5 min  
12: Cool only fan purge - 10 min  
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps  
Data format: Fan span * 10  
10-300 seconds 10 seconds' steps (60 seconds default)  
0: 0 - 10V slow to fast (Forward Acting)  
1: 10 to 0V slow to fast (Reverse Acting)  
0 -10V  
9
Fan span  
10 0-10V Fan Interval (PI)  
11 0-10V Fan direction  
12 0-10V Fan minimum value  
(Starting fan voltage when Data format: 0-10V Fan minimum value * 10  
running)  
13 0-10V Fan Maximum value  
0 -10V  
(Maximum fan voltage Data format: 0-10V Fan minimum value * 10  
when running)  
14 Heat span  
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps  
Data format: Fan span * 10  
10-300 seconds 10 seconds' steps (60 seconds default)  
15 0-10V Heat interval (PI)  
16 0-10V Heat direction  
0: 10V is 100% open (forward acting)  
1: 0V is 100% open (reverse acting)  
17 0-10V Heat minimum 0 -10V  
Voltage  
18 Cool span  
Data format: 0-10V Heat minimum value * 10  
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps  
Data format: Fan span * 10  
10-300 seconds 10 seconds' steps (60 seconds default)  
19 0-10V Cool interval (PI)  
20 0-10V Cool direction  
0: 10V is 100% open (forward acting)  
1: 0V is 100% open (reverse acting)  
21 0-10V Cool minimum 0 -10V  
Voltage  
22 Auto Off Timer  
Data format: 0-10V Cool minimum value * 10  
0: No auto off timer  
1-10hours 0.5 hour increments.  
Data format: hour * 10  
0: OFF  
5C-30C/41F-86F 0.5C/1F steps  
0: OFF  
23 Un-occupied heat  
Set point  
24 Un-occupied cool  
Set point  
5C-30C/41F-86F 0.5C/1F steps  
Page 16  
       
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual