the room to remain in “Occupied Mode”. This ensures that the room remains a conditioned space  
even if the occupant stops moving or sleeps for example. Next time the door is opened and then  
closed again the SMT-131 will again begin its occupancy detection process.  
Note - even when the SMT-131 is in “un-occupied mode” it will continue to use the PIR input to  
determine room occupancy. For example in a hotel a couple may be staying in the room and  
one leaves the room leaving the other asleep in bed. As the door closes the SMT-131 will seek  
movement and when none is found it will enter “un-occupied mode". As the sleeper wakes and  
then moves the SMT-131 will automatically re-enter Occupied Mode” even though it may have  
been some time since the door was closed.  
Installer option “PIR Input Delay” (page 17 ) sets the PIR mode (On or Off) and the seek time value  
(1 to 15 minutes).  
Using a PIR Only for occupancy Detection  
(Typically used in meeting or class room applications)  
When you require the SMT-131 to turn the Heating and  
Cooling on when people enter a room and off when  
people exit the room such as maybe the case in a  
conference or class room.  
Wire the PIR directly to the DS (door switch input) of the  
SMT-131. When movement is detected by the PIR sensor  
the SMT-131 will turn the Air conditioning on maintain  
the set point. After the last person has left the room the  
SMT-131 will wait an installer defined time and then  
switch to "Un-Occupied Mode"  
Steps to use the SMT-131 in automatic occupancy detection mode.  
1. Wire the PIR movement detector into the DS (Door Switch) input.  
2. Set the PIR input delay period (See page 17 for information on setting the  
PIR input delay) to the number of minutes that you wish the Airconditioning  
to run after the last movement has detected in the space.  
3. Place a link permanently shorting the PIR input to Com 0V.  
Manual Occupancy Input  
The DI (Digital Input) & Com 0-10 terminals within the SMT-131 can be used to instantly force the  
SMT-131 into “Un-occupied Mode”. This input can be wired to a simple card reader or other 3rd  
party system that may be pre-installed for room occupancy detection.  
When the SMT-131 is in “Un-occupied Mode” the display will go completely blank except for the  
words “Unoccupied” in the top left corner. If the optional HOT-243 hall way panel is installed its  
display backlight will go out to let housekeeping know the room is empty. Modbus register 40004  
also indicates occupancy status.  
Doorbell  
A built-in doorbell feature is included with the  
SMT-131 thermostat. This is normally activated by  
the optional outside door station as described  
above or via Modbus data link. In circumstances  
where this is not convenient the Digital Input (DI)  
terminals can be reassigned as  
a
doorbell  
Page 12  
   
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual