Home > SMART TEMP > SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
Page 25
40066
40067
40068
Read Only
Read Only
Door Input Status
PIR Status
0: Open
1: Closed
0: No Movement detected
1: Movement detected
Value / 10 (e.g. 2.1V = 21)
(To write add 10 e.g. - to write2.1v send 1021
Read Only
Read Write
(3.09+)
0-10V Fan Value
40069
40070
40071
40072
40073
Read Only
0-10V Fan Max
Value
Digital Input logic
0-10v (@*10)
Read
Write
Read
Write
Read
Write
Read
Write
/
/
/
/
0: Normally Open
1: Normally Closed
Default Start Temp
Ver 3.3 firmware +
Beeper
0: Off
15-35c or 59-86F
0: Beeper OFF
1: Beeper On (Default)
0: Off (default)
1: On
Fan Relay Lock
(Version 40.1+)
This function locks the Fan relay logic to 0-10V
outputs – if enabled depending on other
settings it may cause fan to start and run
before heat or cool calls from the W & Y
relays.
40074
40075
Read
Write
/
/
Temperature
calibration offset
(Version 40.4+)
-9.9 to +10c
This register permits the room temperature to
be offset to correct for perceived room
temperature sensor inaccuracies.
Read
Write
Temperature
sensor speed of 1: Fast
0: Very Fast
response.
(Version 40.4+)
2: Normal
3: Slow (Default)
4: Very Slow
Page 26
| General | Details |
|---|---|
| Name | SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual |
| Make | SMART TEMP |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.34 MB |

SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual

Smart Temp SMT-850 Halo Thermostat User Guide

Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions