40066  
40067  
40068  
Read Only  
Read Only  
Door Input Status  
PIR Status  
0: Open  
1: Closed  
0: No Movement detected  
1: Movement detected  
Value / 10 (e.g. 2.1V = 21)  
(To write add 10 e.g. - to write2.1v send 1021  
Read Only  
Read Write  
(3.09+)  
0-10V Fan Value  
40069  
40070  
40071  
40072  
40073  
Read Only  
0-10V Fan Max  
Value  
Digital Input logic  
0-10v (@*10)  
Read  
Write  
Read  
Write  
Read  
Write  
Read  
Write  
/
/
/
/
0: Normally Open  
1: Normally Closed  
Default Start Temp  
Ver 3.3 firmware +  
Beeper  
0: Off  
15-35c or 59-86F  
0: Beeper OFF  
1: Beeper On (Default)  
0: Off (default)  
1: On  
Fan Relay Lock  
(Version 40.1+)  
This function locks the Fan relay logic to 0-10V  
outputs if enabled depending on other  
settings it may cause fan to start and run  
before heat or cool calls from the W & Y  
relays.  
40074  
40075  
Read  
Write  
/
/
Temperature  
calibration offset  
(Version 40.4+)  
-9.9 to +10c  
This register permits the room temperature to  
be offset to correct for perceived room  
temperature sensor inaccuracies.  
Read  
Write  
Temperature  
sensor speed of 1: Fast  
0: Very Fast  
response.  
(Version 40.4+)  
2: Normal  
3: Slow (Default)  
4: Very Slow  
Page 26  
 
GeneralDetails
NameSMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
MakeSMART TEMP
LanguageEnglish
FiletypePDF (Download)
File size0.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
SMT-2W5 Smart Temp Wifi Thermostat Instruction Manual
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-850 Halo Thermostat User Guide
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions
Smart Temp SMT-450 Flexistat WiFi Thermostat Instructions

SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual