Honeywell Communicating Fan Coil Thermostat Instruction Manual
TF428WNM/U
Communicating Fan Coil Thermostat
SPECIFICATION DATA
Specifications
Physical Layer
Protocol
Baud rate
Parity
EIA485
Modbus RTU
4800/9600(Default)/19200
None
Error checking mechanism CRC
Rated voltage & Frequency 220/230VAC, 50/60Hz
Power consumption
Control
Accuracy
Auto cycle times
Manual cycle times
Protection class
Setpoint range
Display range
<2W
PI, On/off output
±1°C at 21°C
100,000 times
10,000 times
IP20
10 ~ 32°C
0 ~ 37°C
Ambient operating limits
Ambient storage limits
Humidity limits
Action Type:
0~ 49°C
-30 ~ 60°C
5~90% RH, non-condensing
1
Pollution Degree
Protection against electric shock class Class II
Electronic control software class Class A
Rated impulse voltage:
Maximum temperature
For relay wiring
Wire sectional area
(Recommendation)
Applied altitude up to 2000m above sea level
Rating capacity
Working current for the whole product : 4(3)A
4A: When the load of the thermostat is resistance
3A: When the load of the thermostat is inductance
For Fan load 3(2)A
2
General
The TF428WNM/U communicating thermostat is designed for
2500V
3-speed fan and valve control in fan coil system, including:
155°C
2-pipe cooling only/heating only/manual changeover
4-pipe cooling/heating manual/automatic changeover
Ventilation mode
Manual or automatic 3-speed fan control
Water valve on/off control
1.0~1.5mm2
The TF428WNM/U is available in Modbus RTU protocol and
can be easily integrated into building automation system.
3A:when the load is resistance;
2A:When the load is inductance
For Valve load 2(1)A
2A: when the load is resistance;
1A: when the load is inductance
The valve need have overtravel-limit organ to turn off the
load.
Features
RS485 interface in Modbus RTU slave mode
Memorized time off
Cycle Per Hour (CPH)
Random startup
LCD display with simple user interface
Room temperature or setpoint temperature display
selectable
Manual or automatic fan speed selectable
Temperature units in either °C or °F
User setting can be stored when power loss
Freeze protection function available
Keypad lock options
E&ES-CDS-CT01-165-E01-EN
| General | Details |
|---|---|
| Name | Honeywell Communicating Fan Coil Thermostat Instruction Manual |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.39 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell D1-528 Direct Thermostat Installation Guide

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell Communicating Fan Coil Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Communicating Fan Coil Thermostat The TF428WNM/U communicating thermostat is designed for 3-speed fan and valve control in fan coil system. The TF428WNM/U is available in Modbus RTU protocol and can be easily integrated into building automation system. Features include RS485 interface in Modbus RTU slave mode, LCD display with simple user interface, and manual or automatic fan speed selectable. Setpoint range is 10 ~ 32°C and display range is 0 ~ 37°C. Power consumption is less than 2W with a control accuracy of ±1°C at 21°C. Protection class is IP20, and the ambient operating limits are 0~49°C. Humidity limits are 5~90% RH, non-condensing. User setting can be stored when power loss occurs, and freeze protection function is available. Keypad lock options are included for added security.
- Page 2: Model selection Model number Backlight Application Power supply Ventilation Mode Package Dimensions (mm) Product design
- Page 3: Backlight function allows the user to turn on the backlight by pressing any key, which will timeout after 8 seconds of inactivity. In ISU or installation test mode, the backlight will timeout after 60 seconds. The thermostat measures room temperature via an integrated sensor and maintains the setpoint through on/off valve control commands. Fan settings can be selected as manual or automatic 3-speed operation, with manual mode allowing selection of high, medium, or low speeds. In auto mode, fan speed adjusts based on the difference between room temperature and setpoint. Keypad lockout can be configured in ISU or over Modbus, with various options for locking buttons. The displayed temperature can be set to show either room temperature or setpoint during the ISU process. The Cycle Per Hour (CPH) function enables the thermostat to open the valve multiple times per hour as the room temperature approaches the setpoint. Comfort mode allows changes to setpoint and fan speed through corresponding buttons, applicable for various heating and cooling configurations. The time off feature automatically turns off the thermostat after a selectable duration, with a range from 0 to 12 hours.
- Page 4: Ventilation mode allows the fan to operate at the selected speed without output for the valve. Freeze protection mode can be enabled or disabled and activates heating when the temperature is below 6°C. The thermostat will heat until the temperature rises to 8°C in freeze protection mode. The unit can be installed in a standard 86 size junction box. Screws must be tightly locked to prevent wire breakage from terminals. The mounting box and wall temperature should be within the operating range.
- Page 5: Wiring diagram Terminal designations Terminal description Modbus 485 Low speed fan Medium speed fan High speed fan 4-pipe application Note: when in 4-pipe application, the thermostat cannot be connected with Honeywell VC6013/VN6013 series motorized valve
- Page 6: ISU (Installation Setup) Press and hold the “mode” and “up” buttons together for more than 3 seconds to enter or exit ISU. Change the ISU code by pressing the “mode” button and then change the option setting by pressing the “up” and “down” button. All keys are available (Default). Mode button locked out. Fan and mode buttons locked out. All buttons locked out except power button. Heating only. Cooling only. Enabled (Default). Previous status (Default).
- Page 7: Modbus Address Table When the thermostat is integrated into building automation system, please make configuration refer below list. Power Switch Room Temperature Setpoint Fan Speed System Mode V1 Valve Status V2 Valve Status Error Code Fan Status Modbus Address
- Page 8: Registers Parameters Keypad Lockout All keys are available (Default); Mode button locked out; Fan and mode buttons locked out; All buttons locked out except power button; All buttons locked out Freeze Protection Disabled; Enabled (Default) Power Recovery Status OFF; Previous Status (Default) Modbus Baud Rate 9600 (Default); 4800; 19200 Remain time to turn off The parameters are registers, 16 bit integer.