neptronic ITO3-C Wall Thermostat Owner’s Manual
Wall Thermostat
Specification & Installation instructions
Features:
ITO3-C
ITO3-F
ITO3-11C
ITO3-11F
•
•
Celsius or Fahrenheit scale
Sensor 3.3 KΩ or 10 KΩ
ITO3-C
ITO3-F
ITO3-11C
ITO3-11F
Technical Data
Scale
Set point range
Celsius
14ºC to 30ºC
Fahrenheit
57ºF to 86ºF
Celsius
14ºC to 30ºC
Fahrenheit
57ºF to 86ºF
Sensor NTC
3.3 KΩ
10 KΩ
Electrical connection
Operating temperature
Storage temperature
Potentiometer
2 wires or 3 wires 0.8 mm2 [18 AWG] minimum
2ºC to 35ºC (35ºF to 95ºF)
0ºC to 50ºC (32ºF to 122ºF)
2.5 K ohms
Relative Humidity
Ingress protection
Weight
5 to 95 % non condensing
IP 30 (EN 60529)
68 g. [0.15 lb]
The temperature set point adjustment without sensor ITO3 series must be used with a duct
Application temperature sensor from Neptronic® to control a DF series Duct heater, a BM023C actuator or a
TCA or VVC controller from Neptronic®
Dimensions
PCB
Duct Heater
B
D
Calibration
potentiometer
A
C
Connecting strip
(pin 3 is only on
STC8 or STR1
Dimension Inches Metric (mm)
ITO3-11 models)
A
B
C
D
3.00
3.00
1.00
2.36
78
78
24
60
= Only on ITO3-11
models
Factory calibrated
Mounting Instructions
A
B
C
D
E
A. Remove the screw (captive) holding the base and the front cover of the room set point sensor enclosure.
B. Lift the front cover of the enclosure to separate it from the base.
C. Pull wire through the base hole.
D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
E. Mount the control module on the base and secure using the screw.
Recycling at end of life
At end of life, please return the electronic control to your Neptronic® local distributor for recycling. If you need to find the nearest
ITO3-BIL-240130
Page | 1
| General | Details |
|---|---|
| Name | neptronic ITO3-C Wall Thermostat Owner’s Manual |
| Make | neptronic |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.55 MB |

neptronic STS3 Series Wall Thermostat Instruction Manual

neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide

neptronic TMA54-EXT1 Thermostat Instruction Manual

neptronic ITO3-C Wall Thermostat Owner’s Manual Overview
Summary of Contents
- Page 1: Wall thermostat specification and installation instructions. Celsius or Fahrenheit scale available. Set point range is 14ºC to 30ºC or 57ºF to 86ºF. Sensor options include 3.3 KΩ and 10 KΩ. Operating temperature range is 2ºC to 35ºC (35ºF to 95ºF). Storage temperature range is 0ºC to 50ºC (32ºF to 122ºF). Relative humidity tolerance is 5 to 95% non-condensing. Mounting instructions include securing the base to the wall and connecting the control module. At end of life, return the electronic control for recycling. Factory calibrated for accuracy.