neptronic TMA54-EXT1 Thermostat Instruction Manual
Thermostat (Make-Up Air)
Specification & Installation Instructions
Thermostat for controlling an electric heater in a Make-Up Air unit.
Features:
TMA54-EXT1
Selectable analog output
Selectable Fahrenheit or Celsius scale
Manual Night Set Back override
Multi level lockable access menu
Lockable Set point
Selectable internal or external temperature sensor
(10k Ω type 3)
Selectable proportional control band
Proportional-integral-derivative (PID) controller
Technical Data
TMA54-EXT1
2 Analog Cooling outputs (0-10Vdc)
2 Analog Heating outputs (0-10Vdc)
0 or 22 Vdc, TPM, (Time proportional modulation) 250 mA max.
22 to 26 Vac 50/60Hz
Outputs
Power supply
Power consumption
Set point range
2 VA
0ºC to +60ºC [32ºF to +140ºF]
Range: 0ºC to +50ºC [32ºF to +122ºF]
10k Ω type 3 | Range: -40ºC to +100ºC [-40ºF to +212ºF]
Temperature: +/-0.2ºC [0.4ºF]
0.5 ºC to 20ºC [1 ºC to 40ºF] adjustable
0.8 mm2 [18 AWG] minimum
Internal Temperature Sensor
External Temperature Sensor
Control accuracy
Proportional band
Electrical connection
Operating temperature
Storage temperature
Relative Humidity
0ºC to +50ºC [32ºF to +122ºF]
-30ºC to +50ºC [-22ºF to +122ºF]
5 to 95 % non condensing
Degree of protection of housing
IP 30 to EN 60529
Weight
85 g. [0.2 lb]
Dimensions
A = 3.00” | 78mm
B = 3.00” | 78mm
C = 1.00” | 24mm
D = 2.36” | 60mm
B
D
A
C
Presentation
Legend
Cooling ON
A: Automatic
Menu set-up Lock ON
Programming mode
Heating ON
A: Automatic
Minimum/Maximum
set points
Energy saving mode ON
ºC: Celsius scale
ºF: Fahrenheit scale
or
TMA54-EXT-131217-ESA.docx
1
| General | Details |
|---|---|
| Name | neptronic TMA54-EXT1 Thermostat Instruction Manual |
| Make | neptronic |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.28 MB |

neptronic STS3 Series Wall Thermostat Instruction Manual

neptronic ITO3-C Wall Thermostat Owner’s Manual

neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide

neptronic TMA54-EXT1 Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Thermostat for controlling an electric heater in a Make-Up Air unit. Features include selectable analog output, selectable Fahrenheit or Celsius scale, manual night set back override, multi-level lockable access menu, and lockable set point. Selectable internal or external temperature sensor (10k Ω type 3) and selectable proportional control band. Proportional-integral-derivative (PID) controller. Set point range is 0ºC to +60ºC [32ºF to +140ºF]. Control accuracy is +/-0.2ºC [0.4ºF]. Operating temperature range is 0ºC to +50ºC [32ºF to +122ºF]. Relative humidity range is 5 to 95 % non-condensing. Degree of protection of housing is IP 30 to EN 60529. Weight is 85 g. [0.2 lb].
- Page 2: Specification & installation instructions Mounting instructions Remove power prior to separate thermostat cover from its base. Remove the screw holding the base and the front cover of the thermostat. Lift the front cover of the thermostat to separate it from the base. Pull wire through the base hole. Secure the base to the wall using wall anchors and screws. Mount the control module on the base and secure using the screw. Terminal descriptions include common, 24 Vac, exterior temperature sensor, and various heating and cooling ramps. Mode selection involves setting the thermostat in operation mode or programming mode.
- Page 3: Specification & installation instructions Select the desired locked set point temperature. This value must respect the temperature range of the selected temperature sensor. Minimum set point range: 0 to 60ºC [32 to 140ºF]. Maximum set point range: 0 to 60ºC [32 to 140ºF]. You can lock or unlock selection of control mode by end user. Select which control mode you want to authorize: Automatic cooling and heating, OFF cooling and heating, heating only or cooling only. Proportional band range: 0.5 to 20ºC [1.0 to 40ºF]. Integral time range: 0 to 250 seconds. Minimum position of 1st cooling ramp range: 0.0 to 5.0 Volt. Select internal or external sensor. Default value: Out (External temperature sensor).
- Page 4: Specification & installation instructions At powering up, the thermostat will light the display and activate all LCD segments for 2 seconds. To illuminate the LCD, push any of the 3 buttons. The LCD will light for 8 seconds. In operation mode, the thermostat will automatically display the temperature read. To change the scale between ºC and ºF, press both the up and down buttons for 3 seconds. To display the set point, press twice on the up or down button. The set point is displayed for 5 seconds. To adjust the set point, press on the up or down button while the temperature set point is displayed. When the thermostat is in night set back mode, the NSB symbol is displayed. To verify which control mode is set, press once on the control mode button. Control mode will be displayed for 5 seconds. You can choose from automatic cooling or heating, cooling and heating off, cooling only, or heating only. At the end of life, please return the thermostat to your local distributor for recycling.