Home > neptronic > neptronic TMA54-EXT1 Thermostat Instruction Manual

neptronic TMA54-EXT1 Thermostat Instruction Manual

TMA54-EXT1  
Specification & Installation Instructions  
Values  
Step  
Display  
Description  
Locking the set point (cont’d):  
Select the desired locked set point temperature. Note: This value must  
respect the temperature range of the selected temperature sensor – either  
internal or external at step #11A (see Technical Data table on page 1).  
Once locked set point temperature is selected, please go directly to step #5  
Minimum set point:  
Set point range : 0 to 60ºC [32 to 140ºF]  
Increment: 1ºC [1ºF]  
Default value: 22ºC [72ºF]  
2B  
Display switches between “Stp” and the minimum set point temperature. MIN  
symbol is also displayed. Select the desired minimum set point temperature.  
Note 1: The minimum value cannot be set higher than the maximum value  
set in step #4. Note 2: When adjusting this value, please consider the  
selected temperature sensor’s range – either internal or external at step  
#11A (for range, see Technical Data table on page 1).  
Maximum set point  
Display switches between “Stp” and the maximum set point temperature.  
MAX symbol is also displayed. Select the desired maximum set point  
temperature. Note 1: The maximum value cannot be set higher than the  
minimum value set in step #3. Note 2: When adjusting this value, please  
consider the selected temperature sensor’s range. Set to either internal or  
external at step #11A (for range, see Technical Data table on page 1).  
Locking the control mode:  
Range for Minimum  
0 to 60ºC [32 to 140ºF]  
Incrément1ºC [1ºF]  
3
4
Default value: 0ºC [32ºF]  
Range for Maximum  
0 to 60ºC [32 to 140ºF]  
Increment1ºC [1ºF]  
Default value: 60ºC [140ºF]  
Display switches between “LOC” and “CtL”.  
You can lock or unlock selection of control mode by end user. If locked the  
lock symbol will appear.  
If you do not want to lock selection of control mode by end user, go directly  
to step #6.  
Locking the control mode (cont’d):  
Display switches between “CtL” and “Aut”.  
Select which control mode you want to authorize: Automatic cooling and  
heating, OFF cooling and heating, heating only or cooling only.  
5A  
5B  
Default value: Unlocked  
Default value: Automatic cooling and heating  
Proportional band:  
Display switches between “Pbd” and the value of the proportional band.  
Please select the desired value of proportional band.  
Proportional band range :  
0.5 to 20ºC [1.0 to 40ºF]  
Increment: 0.5ºC [1.0ºF]  
Default value: 2.0ºC [4.0ºF]  
6
7
Integral time:  
Range: 0 to 250 seconds  
Increment: 5 seconds  
Default value: 0  
Display switches between “Int” and the value of the integral time in  
seconds. Set the desired value for the integration factor compensation.  
Differential time:  
Range: 0 to 250 seconds  
Increment: 5 seconds  
Default value: 0  
Display switches between “dif” and the value of the differential time in  
seconds. Set the desired value for the differential time.  
8
Minimum position of 1st cooling ramp:  
Display switches between “CL.” and the value of the minimum position of the  
1st cooling ramp. MIN and cooling symbols are also displayed.  
Please select the desired value of the minimum position of the 1st cooling  
ramp.  
Range: 0.0 to 5.0 Volt.  
Increment: 0.2 Volt.  
Default value: 0.0 Volt  
9
Minimum position of 1st heating ramp:  
Range: 0.0 to 5.0 Volt.  
Increment: 0.2 Volt.  
Default value: 0.0 Volt  
Display switches between “ht.” and the value of the minimum position of the  
1st heating ramp. MIN and heating symbols are also displayed.  
Select the desired value of the minimum position of the 1st heating ramp.  
10  
11A  
11B  
Internal/external temperature sensor selection:  
Display switches between “tS” and “in” or “out”.  
Please select internal or external sensor.  
Default value: Out  
(External temperature  
sensor)  
If you select internal temperature sensor, go directly to step #12.  
External temperature sensor Calibration:  
Display switches between “tS2” and the temperature read by the external  
temperature sensor (if connected).  
You can adjust the calibration of the external sensor by comparison with a  
known thermometer.  
Night set back derogation time :  
Range: -40 to 100ºC [-40 to 212ºF]  
Increment:1ºC [1ºF]  
-40ºC [-40ºF]: resistance = infinite.  
100ºC [212ºF]: resistance = short  
circuited (alarm [!] is displayed).  
Display switches between “nSb” and the derogation time in minute. MIN and  
NSB symbol is also displayed.  
Please select the desired derogation time, if no derogation time is desired  
select “OFF”.  
Cooling Set point during Night set back:  
Display switches between “Stp” and the value of the cooling set point  
temperature during night set back. NSB and cooling symbols are also  
displayed. Select the cooling set point temperature during night set back.  
Range: OFF or 30 to 180min.  
Increment: 15min.  
Default value: 120 min.  
12  
13  
14  
Range: 22 to 35ºC [72 to 95ºF]  
Increment: 1ºC [1ºF]  
Default value: 28ºC [83ºF]  
Heating Set point during Night set back:  
Display switches between “Stp” and the value of the heating set point  
temperature during night set back. NSB and heating symbols are also  
displayed.  
Range: 10 to 22ºC [50 to 72ºF]  
Increment: 1ºC [1ºF]  
Default value: 16ºC [61ºF]  
Please select the heating set point temperature during night set back.  
3
GeneralDetails
Nameneptronic TMA54-EXT1 Thermostat Instruction Manual
Makeneptronic
LanguageEnglish
FiletypePDF (Download)
File size0.28 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
neptronic STS3 Series Wall Thermostat Instruction Manual
neptronic STS3 Series Wall Thermostat Instruction Manual
neptronic ITO3-C Wall Thermostat Owner’s Manual
neptronic ITO3-C Wall Thermostat Owner’s Manual
neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide
neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide

neptronic TMA54-EXT1 Thermostat Instruction Manual