Home > WHITE RODGERS > White Rodgers 1F85-0422 Blue Universal Thermostat Instruction Manual

White Rodgers 1F85-0422 Blue Universal Thermostat Instruction Manual

INSTALLER/CONFIGURATION MENU  
1) Keypad Lockout – This menu selection will display “Lk”  
and “OFF” (default, keypad not locked out). The  
ment Recovery (E) On enables the thermostat to start  
heating or cooling early to make the building temperature  
reach the program setpoint at the time you specify. Heat-  
ing will start 5 minutes early for every 1° of temperature  
required to reach setpoint.  
and  
are used to toggle the selection between OFF and  
L(keypad locked out). When the keypad lockout selec-  
tion is enabled L, and the MENU button is pressed  
again, the display will indicate the number “0” (default,  
Example: E On is selected and your heating is pro-  
grammed to 65° at night and 70° at 7 AM. If the build-  
ing temperature is 65°, the difference between 65° and  
70° is 5°. Allowing 5 minutes per degree, the thermostat  
setpoint will change to 70° at 6:35 AM. Cooling allows  
more time per degree, because it takes longer to reach  
set temperature.  
still disabled) in the time digits. The  
and  
are  
used to set the combination number from 0 to 999. If a  
combination of 0 is selected and the MENU button is  
pressed, the menu will be exited and keypad will not be  
locked. If 1 to 999 is selected and the MENU button is  
pressed, the combination is stored into memory and the  
menu is exited. The “LOC” will display designating key-  
pad locked with a valid combination. The SYSTEM button  
will operate for 10 seconds after the menu mode is exited  
to allow the user to change the mode from “OFF” to the  
desired SYSTEM mode.  
6, 7 & 8) Cycle Rate Selection – The factory default setting  
for Heat and Cool modes, SS1 and MS2 is medium cycle  
(ME). For Heat Pump and HP1, the default setting is  
medium (ME). For Emer (Aux) the default setting is fast  
cycle (FA). To change cycle rate, press the  
key.  
Cycle rate differentials for different settings are:  
or  
While the keypad is locked out, a press of MENU will en-  
ter the configuration menu. The first menu item displayed  
is the combination code “0”. The  
or  
keys are  
Fast  
FA  
Medium Slow  
ME  
used to set the combination unlock number from 0 to  
999. If the unlock number matches exactly with the com-  
bination lock number stored in memory when the MENU  
button is pressed, the keypad is unlocked and the “LOC”  
is removed. If the unlock number does not match when  
the MENU button is pressed, the combination returns to  
“0” for another attempt to set the unlock code. To exit the  
menu without unlocking the keypad, press RUN SCHED.  
MODE  
SL  
Heat (SS1, MS2)  
Cool (SS1, MS2)  
Heat Pump (HP1)  
Emer (HP1)  
0.4°F  
0.9°F  
0.9°F  
0.6°F  
0.6°F  
1.2°F  
1.2°F  
-
1.7°F  
1.7°F  
1.7°F  
1.7°F  
9) Select Compressor Lockout CL OFF or ON – Select-  
ing CL ON will cause the thermostat to wait 5 minutes  
between cooling cycles. This is intended to help protect  
the compressor from short cycling. Some newer com-  
pressors already have a time delay built in and do not  
require this feature.Your compressor manufacturer can  
tell you if the lockout feature is already present in their  
system. When the thermostat compressor time delay oc-  
curs, it will flash the setpoint for up to five minutes.  
To reset the combination code and unlock the keypad if  
the code is forgotten, see troubleshooting section.  
2) This control can be configured for:  
MS 2 – Multi-Stage System (no heat pump)  
HP 1 – Heat Pump with one stage of compressor  
SS 1 – Single Stage System  
3) GAS or Electric (ELE) fan operation. If the heating sys-  
tem requires the thermostat to energize the fan, select  
ELE. Select GAS if the heating system energizes the fan  
on a call for heat.  
10) System Mode Configuration – This thermostat is con-  
figured for Heat and Cool (SYSTEM switch with Cool Off  
Heat) default. It can also be configured for Heat and Cool  
with Auto changeover (Heat, Auto, Cool, Off), Heat only  
4) Select Cool Savings™ value – Selects the amount  
of adjustment for the Cool Savings™ feature in Cool  
mode with 1 (1°) being the least amount of adjustment  
and 6 (6°) being the most amount of adjustment. Default  
value is 0 which disables this feature. Cool Savings is  
an optional energy saving feature that can reduce your  
cooling costs. It is based on the principal that lower  
indoor humidity makes a slightly higher temperature  
feel more comfortable. Cool Savings operates during  
periods of high demand which normally occur on the  
hottest summer days when a cooling system may run  
for hours to reach the thermostat setting. Long cooling  
run times also lower the indoor humidity. Cool Savings,  
very slowly, adjusts the setpoint temperature to make the  
setpoint closer to the displayed room temperature, to a  
maximum of the number of degrees you select. Adjust-  
ing the setpoint temperature over a long cooling run time  
allows the system to reach your set temperature and turn  
off. The room temperature will actually be higher than  
the thermostat displays but the reduction in humidity will  
allow comfort at the slightly higher temperature.  
with fan (Off Heat), Heat only without fan, Auto only  
(Auto Off), and Cool only (Cool Off).  
11) Select Backlight Display – The display backlight im-  
proves display contrast in low lighting conditions. When  
the “C” terminal is powered, selecting backlight CdL ON  
will keep the light on continuously. Select backlight OFF  
will turn the light on momentarily after any key is pressed.  
When the “C” terminal is not powered, the light will be on  
momentarily after any key is pressed no matter whether  
the backlight is selected ON or OFF.  
12) Select Temperature Display Adjustment 4 LO to 4 HI  
– Allows you to adjust the room temperature display up  
to 4° higher or lower.Your thermostat was accurately cali-  
brated at the factory, but you have the option to change  
the display temperature to match your previous thermo-  
stat. The current or adjusted room temperature will be  
displayed.  
13) Select F° or C° Readout – Changes the display readout  
to Celsius or Fahrenheit as required.  
14) Limited Heat Range – This feature provides a maximum  
setpoint temperature for heat. The default setting is 90°F.  
It can be changed between 62°F and 89°F by pressing  
To turn this feature on in the Cool mode press Cool  
Savings. The display will show “Save” next to the  
setpoint temperature. When Cool Savings is making ad-  
justments to the room temperature display “Save” will be  
flashing and the displayed room temperature may vary  
within the adjustment range you selected.  
the  
or  
key.  
15) Limited Cool Range – This feature provide a minimum  
setpoint temperature for cool. The default setting is 45°F.  
It can be changed between 46°F and 82°F by pressing  
If “Save” is not displayed and this feature is OFF, no  
change will occur when the cooling system is continu-  
ously running during periods of high demand.  
the  
16) Program Options: 1F85 only, configured for 5/1/1 day or  
or  
key.  
5/2 day programming or non-programming mode. The  
default setting is P3, indicating 5/1/1 day programming.  
The programs per week can be changed to P2 or P0 by  
5) Energy Management Recovery: (this step is skipped if  
configured to be non-programmable). Energy Manage-  
5
GeneralDetails
NameWhite Rodgers 1F85-0422 Blue Universal Thermostat Instruction Manual
MakeWHITE RODGERS
LanguageEnglish
FiletypePDF (Download)
File size0.38 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual
White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual
White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual
White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual
White-Rodgers 1F56N-444 Thermostat User Manual
White-Rodgers 1F56N-444 Thermostat User Manual
White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual
White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual
White-Rodgers M30 Thermostat Instruction Manual
White-Rodgers M30 Thermostat Instruction Manual
WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual
WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual
White Rodgers 1F78-151 Non Programmable Thermostat Instructions
White Rodgers 1F78-151 Non Programmable Thermostat Instructions
WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual
WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual
WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual
WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual

White Rodgers 1F85-0422 Blue Universal Thermostat Instruction Manual