Table 6: Parameter C23 - Output 8 function.
VALUE
DESCRIPTION
No function
0
1
Fan logic; relay closed when the proportional fan is on.
Inverted fan logic; relay closed when the proportional fan is off.
Valve logic; relay closed when the valve is open.
Inverted valve logic; relay closed when the valve is closed.
ON/OFF logic; the output is active when the thermostat is on.
Inverted ON/OFF logic; the output is active when the thermostat is off.
Economy logic; the output is active when the thermostat is in economy mode or off.
2
3
4
5
6
7
Inverted Economy logic; the output is active when the thermostat is on and NOT in economy
mode.
8
9
Summer/Winter logic; the output is active when the thermostat is in heating (winter) mode.
Inverted Summer/Winter logic; the output is active when the thermostat is in cooling (sum-
mer) mode.
10
Duplicate input 3; this output is active when input 3 is closed.
Inverted duplicate input 3; this output is active when input 3 is open.
Duplicate input 4; this output is active when input 4 is closed.
Inverted duplicate input 4; this output is active when input 4 is open.
Duplicate input 16; this output is active when input 16 is closed.
Inverted duplicate input 16; this output is active when input 16 is open.
11
12
13
14
15
16