terminal 6 and the cooling output on terminal 7 Fig. 12c. In the case of two-pipe systems, only one
valve needs to be connected to the heating output. Connect it as shown in Fig. 12a. It is possible
to manage systems with two different kinds of valves for heating and cooling, for instance ON/OFF
heating output and 0..10V proportional cooling output. If the system is equipped with an electric
heater in addition to, or instead of the heating valve, connect according to the diagrams in Fig. 12e
or Fig. 12f.
TECHNICAL SPECIFICATIONS
Power supply:
24/230 V~ 50/60 Hz
Power consumption:
Room temperature
Regulation range:
Sensor type:
1.2 W
5°C .. 35°C (41°F .. 95 °F) configurable
NTC 10kΩ @ 25°C (77 °F) ±1%
± 1°C (± 1,8°F)
Precision:
Resolution:
0.1°C (0.1°F <100°F)
Display range:
-10°C .. +50°C (14°F .. 122 °F)
adjustable 0.2°C (0.4°F)
Hysteresis:
Supply water temperature
Sensor type:
NTC 10kΩ @ 25°C (77 °F) ±1%
± 1°C (± 1,8°F)
Precision:
Resolution:
± 1°C (± 1,8°F)
Display range:
0°C .. 99°C (32°F .. 210 °F)
2°C (4°F)
Hysteresis:
Proportional outputs
Signal range:
0..10 V
Signal precision:
Minimum actuator impedance:
1 x 0..10V output:
2 x 0..10V outputs:
3 x 0..10V outputs:
Relay contact capacity:
Remote probe (optional):
Protection rating:
Type of action:
± 0.26 V
1850 Ohm
3700 Ohm
5550 Ohm
3 (1) A 250 V~
NTC 10kΩ @ 25°C (77 °F) ±1%
IP 30
1
II
Voltage overload rating:
IT - 11
| General | Details |
|---|---|
| Name | OLIMPIA SPLENDID 9899 Thermostat User Manual |
| Make | OLIMPIA SPLENDID |
| Language | English |
| Filetype | PDF (Download) |
| File size | 5.17 MB |