DAIKIN DKN510 Wireless VRV Communicating Thermostat Installation Guide
INSTALLATION GUIDE
DKN510 Wireless VRV
Communicating Thermostat
INTRODUCTION
The Daikin Wireless VRV Communicating Thermostat has onboard sensors. This device is
an all-in-one thermostat, humidistat, and IAQ sensing station. This device does not require
external power source as it works on the P1P2 communication bus.
PACKAGE CONTENTS
•
•
P1P2 wireless thermostat device
Mounting accessories
SPECIFICATIONS
Power
Power Source: 24V AC/DC input (+/- 15%)
Peak consumption: P1P2 variant can be powered by the Daikin
IDU, 1W nominal (1.3W maximum) power consumption
Operating range
Communication
Humidity 20-85% non-condensing.
Temperature 0 to 122°F (-17 to 50°C)
3-wire sensor bus for daisy-chained sensor communication and
low power 3V dc
4-wire interface for RS 485 communication @ 115200 baud and
5V DC, 100mA power source
900-928 MHz Mesh IEEE 802.15.4-compliant, for communications
to CCU
Bluetooth: BLE 4.1 for commissioning, triangulation and
communication to wireless sensors
Inputs
2 x 10K Type-2 thermistor inputs with 2% accuracy
2 x 0-10V analog voltage inputs with 2% detection accuracy (2-
10V)
Touch slider for temperature control along with 3 mechanical
buttons
Outputs
2 x Relays rated at 24V DC/1A
2 x 0-10V or 4-20mA analog outputs
2.8" 240x320 pixel TFT display
IM 1338-1 • DKN510 Wireless Thermostat
| General | Details |
|---|---|
| Name | DAIKIN DKN510 Wireless VRV Communicating Thermostat Installation Guide |
| Make | Daikin |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.16 MB |

DAIKIN One Lite Smart Thermostat User Guide

Daikin One Lite Smart Thermostat Instruction Manual

DAIKIN TRC-11 One Lite Connected Thermostat Instruction Manual

DAIKIN DTST-ONE-ADA-A One Touch Smart Thermostat Installation Guide

DAIKIN IM 1368 Vertical Stack WSHP Thermostat Instruction Manual

DAIKIN IM 1366 Remote Integrated Thermostat Instruction Manual

DAIKIN ONE Smart Thermostat Instructions

DAIKIN DKN509 Wireless Communicating Thermostat Instruction Manual

DAIKIN SQNSQ22 One Touch Smart Thermostat User Manual

EMSQ22 Daikin ONE Lite Smart Thermostat User Manual

DAIKIN DKN510 Wireless VRV Communicating Thermostat Installation Guide Overview
Summary of Contents
- Page 1: INSTALLATION GUIDE DKN510 Wireless VRV Communicating Thermostat INTRODUCTION The Daikin Wireless VRV Communicating Thermostat has onboard sensors. This device is an all-in-one thermostat, humidistat, and IAQ sensing station. This device does not require an external power source as it works on the P1P2 communication bus. PACKAGE CONTENTS P1P2 wireless thermostat device Mounting accessories SPECIFICATIONS Power Source: 24V AC/DC input (+/- 15%) Peak consumption: P1P2 variant can be powered by the Daikin IDU, 1W nominal (1.3W maximum) power consumption Humidity 20-85% non-condensing. Temperature 0 to 122°F (-17 to 50°C) 3-wire sensor bus for daisy-chained sensor communication and low power 3V dc 4-wire interface for RS 485 communication @ 115200 baud and 5V DC, 100mA power source 900-928 MHz Mesh IEEE 802.15.4-compliant, for communications to CCU Bluetooth: BLE 4.1 for commissioning, triangulation and communication to wireless sensors 2 x 10K Type-2 thermistor inputs with 2% accuracy 2 x 0-10V analog voltage inputs with 2% detection accuracy (2-10V) Touch slider for temperature control along with 3 mechanical buttons 2 x Relays rated at 24V DC/1A 2 x 0-10V or 4-20mA analog outputs 2.8 240x320 pixel TFT display
- Page 2: Onboard sensors include a CO2 sensor with a range of 0 - 40,000 ppm and an accuracy of +/-30ppm. The VOC sensor has a typical accuracy of 15% of the measured value and a detection range for TVOC of 0 - 60,000 ppb. The occupancy sensor operates based on passive infrared (PIR) with a detection range of 4m. The light sensor features high-accuracy UV index detection. The temperature sensor has a typical accuracy of +/- 0.2°C, while the humidity sensor's accuracy is +/- 2% RH. The sound sensor responds to a range of 40-120dB for frequencies from 100Hz to 10KHz. The PM2.5 and PM10 sensor has a detection range of 0-1000µg/m3 with specified accuracy limits. Warnings and disclaimers emphasize the importance of following installation and operation guidelines. Properly trained technicians should perform work on the system. Caution is advised regarding wiring devices for power with the correct polarity to avoid damage. It is crucial to turn off power before wiring and to avoid connecting components while the power is on.
- Page 3: Mounting P1P2 thermostat interface Thermostat/VRV controller interface Allen head screws Rubber cover 1 Rubber cover 2 Gang box PHP screws Back plate IM 1338-1 • DKN510 wireless thermostat
- Page 4: Place the P1P2 thermostat interface and the back plate on the gang box such that the back plate covers the gang box and fix these two items to the wall gang box with the PHP screws provided in the box. Align the thermostat main to lock onto the P1P2 thermostat interface. Use the Allen head screws to make this entire setup tamper-proof. Rubber covers must be fixed to cover the programming pins. Installations carried out by non-certified technicians/engineers would void warranty. For more information on wiring, commissioning, or usage of Daikin Wireless products, please refer to any documentation provided with the job. If no documentation was provided with the job, please use the Daikin Wireless Help Center for application specific wiring schematics and helpful user guides and videos. You can find instructional videos, installation guides, and more.