GROUP CONTROL  
62  
GROUP CONTROL  
1
When installing more than 2 units of air  
conditioner to one Thermostat, please  
connect as pictured to the right.  
GND  
Signal wire  
12V  
- Set one indoor unit to master and the re-  
maining to slave.  
GND  
Signal wire  
When controlling multiple indoor units with one Thermostat, you must change the master/slave  
setting from the indoor unit.  
- Once DIP S/W is set, recycle power. When recycling power, please remain in OFF position for  
at least 1 minute for new settings to take effect.  
- For ceiling type cassette and duct product group, change the switch setting of the indoor PCB.  
#3 switch OFF: Master  
(Factory default setting)  
#3 switch ON: Slave  
- For wall-mount type and stand type product, change the master/slave setting with the wireless  
Thermostat. (Refer to wireless Thermostat manual for detail)  
When controlling the group, some advanced functions (excluding basic operation setting, fan  
level Low, med, high, Thermostat lock setting and time setting) may be limited.  