White Rodgers 1F95-1277 Big Blue Universal Thermostat Instruction Manual

INSTALLER/CONFIGURATIONMENU  
1) This control can be configured for:  
11) Select Continuous Backlight – In low lighting condi-  
tions, display backlight improves the display contrast.  
When C terminal is connected, selecting dL On will turn  
the backlight on continuously. Selecting dL Off will turn  
the backlight on momentarily after any key is pressed.  
When C terminal is not powered (battery only), dL On  
enables the momentary backlight whenever a key is  
pressed.  
MS2 – Multi-Stage System (2 heat/2 cool)  
HP1 – Heat Pump with one stage of compressor  
(2 heat/1 cool)  
HP2 – Heat Pump with two stage compressor or two  
compressor system, Gas or Electric backup; (Dual Fuel  
see menu item 26) (3 heat/2 cool)  
SS1 – Single Stage System (3 wire zone see wiring  
diagram 37-6808A)  
12) Select Backlight Intensity – This thermostat has the  
ability to provide two selectable intensities of the back-  
2) GAS or Electric (ELE) fan operation. If the heating  
system requires the thermostat to energize the fan,  
select ELE. Select GAS if the heating system energizes  
the fan on a call for heat. Note: Resetting the thermo-  
stat switches the option to ELE.  
light: HI and LO. Using  
or  
toggle the selection between HI and LO.  
touch keys you can  
13) Select Temperature Display Adjustment 4 LO to 4 HI  
This allows you to adjust the room temperature display  
by an amount in the range of -4°F to +4°F in 1° steps by  
3) Programs per week – This control can be configured for  
7 independent day or 5/1/1 day programming or non-  
programmable modes. Default is 7-day mode. The  
display indicates "7 Days" as default. Other options "5  
Days" or "0 Days" can be selected by pressing touch  
using the  
or  
touch keys. Your thermostat was  
accurately calibrated at the factory, however you have the  
option to change the display temperature value to match  
your previous thermostat, if you so prefer.  
keys,  
or  
. If "0 Days" is selected for non-program-  
14) Select °F or °C Readout – Select the desired temper-  
ature unit by pressing  
mable mode, the step for EMR will be skipped, as this  
feature will not be available in this mode.  
or . Factory default is °F.  
15) Select Audio Prompting (Beeper) On or Off – Factory  
default setting is on (b, On). If you wish to turn off the  
beeper select OFF.  
4) Program Steps per day – This control can be config-  
ured for 4 or 2 program steps per day. Default is "4 PS"  
and can be toggled between 4 PS and 2 PS by pressing  
16) Select Daylight Saving Time Calculation – This feature  
will allow the thermostat to calculate the DST automati-  
cally and apply it to the Real Time Clock display. Default  
the  
or  
touch keys.  
5) System Switch Configuration (MS2/SS1) – This  
thermostat is configured for Heat and Cool with Auto  
changeover default (Cool-Off-Heat-Auto). Can be  
configured as Heat & Cool (Cool-Off-Heat), or Heat Only  
(Off-Heat), or Cool Only (Cool-Off).  
On. Use  
or  
touch keys to select the feature, OFF.  
17 & 18) Select Automatic Schedule – This feature allows  
programming a “Comfort Temperature” into all program  
periods with the Auto Schedule key. When Heat AS (for  
Heat mode) or Cool AS (for Cool mode) is selected On,  
the Auto Schedule feature is ready to be set. Off  
indicates that the feature is not ready to be used or a  
“Comfort Temperature is already set. See Auto Schedule  
in Programming section.  
When the control is in heat pump configuration (HP1/  
HP2), the system switch configuration will have an  
additional mode available namely, Emer for Emergency  
Mode.  
6) Energy Management Recovery (EMR) – (this step is  
skipped if configured as non-programmable).  
When set to "On" causes the thermostat to start heating  
or cooling early to make the building temperature reach  
the program setpoint at the time you specify.  
19) Select Cool Savings™: With Cool Savings™ enabled,  
the thermostat will make small adjustments to the  
setpoint temperature during periods of high demand to  
reduce AC system running time and save energy. When  
the cooling system has been running for more than 20  
minutes, humidity in the home will be lower and a higher  
temperature will feel comfortable. After 20 minutes of run  
time, the thermostat will start increasing the setpoint  
temperature in steps of less than one degree as the  
system continues to run. These adjustments will eventu-  
ally cause the system to satisfy the thermostat to turn the  
system off and reduce the energy consumption. When  
the Cool Savings™ feature is active and making adjust-  
ments, the display will flash “Cool Savings”. The amount  
of the adjustments to the setpoint temperature is depen-  
dent on the Cool Savings™ value that is set, 1 being the  
least adjustment and 6 being the most adjustment. With  
this feature set to OFF, no change will occur when the AC  
system is continuously running during the periods of high  
demand. Periods of high demand will normally occur  
during the late afternoon and early evening on the hottest  
days of the summer. As demand lessens the adjustments  
to setpoint temperature are reversed until setpoint  
temperature returns to normal and “Cool Savings” no  
longer flashes.  
Example: Let us say, the heating program is 65°F at  
night and 70° at 7 AM. If the building temperature is 65°F,  
the difference is 5°F. Allowing 5 minutes per °F rise, the  
thermostat setpoint will change to 70° at 6:35 AM.  
Cooling allows more time per °F, because it takes  
longer to reach temperature.  
7, 8 & 9) Cycle Rate Selection – The factory default setting  
is fast cycle (FA Cr) in all modes (Heat, Cool, Emer). To  
slow cycling (SL, Cr), press touch keys  
or  
toggle  
between FA & SL. The cycle rates are as below different  
selections:  
Mode  
Heat  
Cool  
Fast rate  
0.6°F  
1.2°F  
Slow rate  
1.2°F  
1.7°F  
Emer  
1.2°F  
1.7°F  
10) Select Compressor Lockout (CL) – Selecting CL On  
will cause the thermostat to wait 5 minutes between  
cooling cycles. This is intended to help protect the  
compressor from short cycling. Some of the newer  
compressors have already got a time delay built in and  
do not require this feature to be activated in the thermo-  
stat. Your compressor manufacturer can tell you if  
this lockout feature is already present in their system.  
When the thermostat compressor time delay is activated,  
it will flash the set point for up to five minutes.  
5
GeneralDetails
NameWhite Rodgers 1F95-1277 Big Blue Universal Thermostat Instruction Manual
MakeWHITE RODGERS
LanguageEnglish
FiletypePDF (Download)
File size0.4 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual
White-Rodgers 1E78 Non Programmable Heat Only Thermostat User Manual
White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual
White-Rodgers 1F97-1277 Big Blue Single Stage Thermostat User Manual
White-Rodgers 1F56N-444 Thermostat User Manual
White-Rodgers 1F56N-444 Thermostat User Manual
White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual
White-Rodgers 1F83-277 Heating & Air Conditioning Auto Changeover Heat Pump Thermostat User Manual
White-Rodgers M30 Thermostat Instruction Manual
White-Rodgers M30 Thermostat Instruction Manual
WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual
WHITE-RODGERS 1F51N-619 Low Voltage Evaporative Cooler Thermostat Instruction Manual
White Rodgers 1F78-151 Non Programmable Thermostat Instructions
White Rodgers 1F78-151 Non Programmable Thermostat Instructions
WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual
WHITE RODGERS 1F80-51 Programmable Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual
WHITE-RODGERS 1F86-0471 Blue Single 1 1 Stage Thermostat Instruction Manual
WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual
WHITE-RODGERS 1F90-71 5-Day 2-Day Electronic Digital Thermostat Instruction Manual

White Rodgers 1F95-1277 Big Blue Universal Thermostat Instruction Manual