PERRY TE541 Digital Thermostat User Manual
10 - CONFIGURATION MENU (Installer)
10.6.2 - RESETTABLE COMMAND on N.C. external contact “Normally Closed”
Confirmed screen for the management of the resettableN.C. external contact with a command on the thermostat
aspertheprocedureinparagraph10.6, thefollowingoperationisobtained:
Do not enable the item prior to connecting a switch or other device that allows change of state
from OFF mode to current operating mode and vice versa to terminals 1 and 2 (AUX)..
Thermostat operation
e.g. external contact N.C.
Contact opening
activates level and Tset OFF ANTI-FREEZE if in WINTER ( ) or THERMAL PROTECTION in SUMMER (
)
return to the level and Tset active before closing the contact
Contact closure
For the operating principle procedure and the displays on the display when the state of the external contact changes and/or reset with control directly on the
thermostat, see images shown in the previous paragraph 10.6.1. taking into account that the contact is normally closed N.C. and not N.A.
10.6.3 - NON-RESETCABLE COMMAND on external N.O. contact. «Normally Open»
Confirmedscreen
ofexternalcontactmanagementN.A. aspertheprocedureinparagraph10.6thefollowingoperationisobtained:
Thermostat operation
e.g. external contact N.A.
Contact closure
Contact opening
activates level and Tset OFF ANTI-FREEZE if in WINTER ( ) or THERMAL PROTECTION in SUMMER (
)
return to the level and Tset active before closing the contact
Livello OFF
Return to the level
before contact closure
example from mode: WINTER
flashes
example with open window
which closes the N.O. contact.
Closing the window
opens the N.A. contact.
Note:
a
flashing “bLOC” will
appear when any button is
pressed.
contact opening and closure controls are operative within max 60 sec.
The change of state from open remote contact to closed contact causes forcing into the permanent manual OFF state (antifreeze or thermal
protection) with the display of the flashing “ “ icon (to indicate an active forcing situation). The OFF level can result in actual temperature control
atacertainTsetvalue(e.g. 5°C)ortemperaturecontrolswitchedoff, seepar. 10.5.
The subsequent change of state from closed contact to open contact causes the end of the manual forcing OFF and the automatic loading of the
levelthatwasactivebeforetheforcing;theicon
22
willbeswitchedoff.