Home > PERRY > PERRY TE541 Digital Thermostat User Manual

PERRY TE541 Digital Thermostat User Manual

1 - TECHNICAL DATA  
Power supply:  
230V~ +/- 10% 50Hz  
timed 6 secs. / always on / always off / brightness reduction after 6 sec.  
Display and key back-lighting:  
Type of action, disconnection and device:  
1 B / Electronic  
voltage free relay with COM / NO / NC changeover contact,  
max 5(3)A/250 V ~  
Type of output:  
Keeping memory setting during power failure:  
Yes  
Software:  
Rated impulse voltage:  
Cross-section of wires to terminals:  
Contact input for remote thermostat deactivation:  
Type of insulation:  
class A  
4 kV  
1,5 mm2 ÷ 2,5 mm2  
for contact free from potential, minimum insulation 250V~, maximum cable length 15 m.  
class II  
Degree of protection:  
Pollution rating:  
Operating mode:  
Number of temperature levels:  
Ambient temperature display range:  
Relay ON signal:  
(recessed wall-mounted with wall plate)  
IP 30  
2
heating (default) / Summer cooling  
Winter  
n° 2 « t1 = CONFORT», «t2 = ECONOMY» + OFF antifreeze/thermal protection  
0 °C ÷ +45 °C  
+ ON (Winter) o + ON (Summer)  
0.1 °C  
+4 °C ÷ +37.7 °C (limitable with Max and Min temperature blocks)  
a step di 0.1 °C  
Room temperature indicator resolution:  
Temperature Set adjustment range:  
Setting temperature Set:  
Temperature correction (Offset) separated by seasons:  
Antifreeze Tset temperature OFF (Winter):  
Thermal protection Tset temperature OFF (Summer):  
Type of temperature adjustment:  
- Proportional with control period (default)  
- DIFFERENTIAL ON/OFF  
adjustable from -6.0 °C to +6.0 °C (default 0.0 °C)  
adjustable from + 4 °C to t2 (default 5 °C)  
adjustable from t2 included to +37,7 °C (default «disabled»)  
cycles adjustable from 7 to 20 minutes (default 7 minutes)  
adjustable from 0.2 °C to 1.2 °C (default 0,3 °C)  
max 1°K / 15 min  
1°C  
Thermal gradient:  
Temperature reading tolerance:  
Operating temperature limits::  
Storing temperature limits:  
Type of installation:  
Type of use:  
ErP energy classification:  
0 °C ÷ +45 °C  
-10 °C ÷ +60 °C  
Built-in  
civil and tertiary sectors  
ErP: Class I; 1% Reg. EU 811/2013  
Reference regulations for CE markings:  
4
LVD - EMC EN60730-1 EN60730-2-9  
GeneralDetails
NamePERRY TE541 Digital Thermostat User Manual
MakePERRY
LanguageEnglish
FiletypePDF (Download)
File size1.4 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

PERRY TE541 Digital Thermostat User Manual