10 - CONFIGURATION MENU (Installer)
10.6 - MANAGEMENT OF EXTERNAL CONTACT for remote thermostat switching on/off
The thermostat is equipped with an input (AUX) for an external contact, it will
be possible to connect accessory equipment (e.g. time switch, switch,
window contact, etc.) that can deactivate the thermostat remotely, whose
control must necessarily be potential-free.
A typical use is the window contact that can be connected to this input e.g. to
switch off the temperature control in Winter (or Summer) when a window is
opened.
Before enabling any item of the «Set GAtE» menu listed below ensure
you have connected an external contact potential-free to the terminals
1 and 2 (AUX) see par. 5.4.
WARNING: only connect switches and contacts with insulation
suitabletoworkat230Vacmainsvoltagetoterminals1and2AUX.
MULTIPLE INSTALLATIONS: It is NOT permitted to connect the remote
contact on more than one thermostat; each thermostat must have its
AUXinputoperatedindependentlyoftheothers.
•From normal operation of the thermostat, access the menus by holding down
the “Mode” button as described in Chap. 9.
The SEtGAtEscreenisdisplayed.
•Confirmbypressing OK, thedashes
flash.
Press the OK button
to confirm the desired
management of the
external contact
•Using the buttons select the desired external contact management
,
modescreen (seetablebelow).
•press OK to confirm.
•press the Mode button to exit the menus and return to normal thermostat operation.
= No external contact enable (default);
= RESETTABLE command on N.O. external contact “Normally Open”
= RESETTABLE command on N.C. external contact “Normally Closed”
= Command NOT RESETTABLE on N.O. external contact “Normally Open”
= Command NOT RESETTABLE on N.C. external contact “Normally Closed”
20