Home > CLIMATE MASTER > CLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide
CLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide
iGATE 2 COMMUNICATING (AWC) THERMOSTAT – IOM
System Settings
Reference the System Configuration section for information on accessing System Settings.
Table 5: System Configurations
Available remotely (web/mobile) and at thermostat display.
System Setting
Description
Range/Options
Default
Auto Mode
Allowed
Automatically switch from heating to cooling to maintain the
temperature between the setpoints.
Yes, No
Yes
Adjust the staging option using the up/down arrow buttons.
Select Single Stage for control of a single stage compressor
applications. Select Multi-Stage for control of multistage
compressor applications.
Compressor
Stages1
Single Stage,
Multi-stage
Multi-stage
Configure the logic the unit control uses to meet the
temperature setpoints. The Proportional Integral logic will use
a combination of temperature differential and operating time
to determine the appropriate heating or cooling stages for
operation. The Proportional Integral (No Down Staging) logic
includes the Proportional Integral logic, but in addition the logic
keeps all active heating or cooling stages energized until the
demand is fully satisfied.
Temperature
Control1
Proportional Integral, Proportional
Integral (No Down Staging)
Proportional
Integral
Adjust the maximum number of on/off cycles per hour to maintain
the desired indoor temperature. Select 4 to limit operation to start
no sooner than 15 minutes after the previous call was initiated.
Cycles per Hour1 Select 4 to limit operation to start no sooner than 20 minutes after
the previous call was initiated. Select 6 to limit operation to start
no sooner than 10 minutes after the previous call was initiated
(can provide tighter temperature control).
2, 4, 6
6
Hawaii, Alaska, Pacific, Mountain,
Central, Eastern, Atlantic,
Newfoundland, Pierre & Miquelon, W.
Greenland, E. Greenland, Greenwich
Supplemental,
Time Zone
Configures the time zone of the thermostat.
Configures the auxiliary heat mode.
Central
Auxiliary Heat
Supplemental
Residential
2 hours
Emergency, None
Application
Mode
Configures the application of the thermostat.
Commercial, Residential
Select how long the iGate2 Communicating (AWC) Thermostatwill
1 Hour, 2 Hours, 3 Hours, 4 Hours, 5
hold the new temperature before reverting to the regular program. Hours, 6 Hours, Until Next Prog Event
Hold Action
Temperature
Display
Configures the temperature scale.
Fahrenheit, Celsius
Fahrenheit
Transitions the conditioned space from one programmable
temperature period to the next with 1°F increments of the
heating setpoint or with 1°F decrements of the cooling setpoint,
so that by the time the next period starts, the setpoints are at
the desired temperature. The purpose of the gradual transition
is to use less energy by preventing staging up (because of a
higher demand) to higher stages. The transitions occur in a linear
fashion over the smart recovery time period.
Smart Recovery
Mode
(requires
Programming
to be enabled)
No, 30 minutes,
60 minutes,
90 minutes
30 minutes
None, Space, Outdoor, Average,
Occupancy
Remote Sensor
Configure the application of the remote sensor input.
None
Humidification, Dehumidification,
Both, None
Humidity Control Determines available humidity mode(s).
1. Applies to Tranquility.
Dehumidificaton
Table continued on next page.
Part#: 97B0132N01 | Revised: Februar y 06, 2025
PAG E : 9