iGATE 2 COMMUNICATING (AWC) THERMOSTAT – IOM  
System Settings  
Reference the System Configuration section for information on accessing System Settings.  
Table 5: System Configurations  
Available remotely (web/mobile) and at thermostat display.  
System Setting  
Description  
Range/Options  
Default  
Auto Mode  
Allowed  
Automatically switch from heating to cooling to maintain the  
temperature between the setpoints.  
Yes, No  
Yes  
Adjust the staging option using the up/down arrow buttons.  
Select Single Stage for control of a single stage compressor  
applications. Select Multi-Stage for control of multistage  
compressor applications.  
Compressor  
Stages1  
Single Stage,  
Multi-stage  
Multi-stage  
Configure the logic the unit control uses to meet the  
temperature setpoints. The Proportional Integral logic will use  
a combination of temperature differential and operating time  
to determine the appropriate heating or cooling stages for  
operation. The Proportional Integral (No Down Staging) logic  
includes the Proportional Integral logic, but in addition the logic  
keeps all active heating or cooling stages energized until the  
demand is fully satisfied.  
Temperature  
Control1  
Proportional Integral, Proportional  
Integral (No Down Staging)  
Proportional  
Integral  
Adjust the maximum number of on/off cycles per hour to maintain  
the desired indoor temperature. Select 4 to limit operation to start  
no sooner than 15 minutes after the previous call was initiated.  
Cycles per Hour1 Select 4 to limit operation to start no sooner than 20 minutes after  
the previous call was initiated. Select 6 to limit operation to start  
no sooner than 10 minutes after the previous call was initiated  
(can provide tighter temperature control).  
2, 4, 6  
6
Hawaii, Alaska, Pacific, Mountain,  
Central, Eastern, Atlantic,  
Newfoundland, Pierre & Miquelon, W.  
Greenland, E. Greenland, Greenwich  
Supplemental,  
Time Zone  
Configures the time zone of the thermostat.  
Configures the auxiliary heat mode.  
Central  
Auxiliary Heat  
Supplemental  
Residential  
2 hours  
Emergency, None  
Application  
Mode  
Configures the application of the thermostat.  
Commercial, Residential  
Select how long the iGate2 Communicating (AWC) Thermostatwill  
1 Hour, 2 Hours, 3 Hours, 4 Hours, 5  
hold the new temperature before reverting to the regular program. Hours, 6 Hours, Until Next Prog Event  
Hold Action  
Temperature  
Display  
Configures the temperature scale.  
Fahrenheit, Celsius  
Fahrenheit  
Transitions the conditioned space from one programmable  
temperature period to the next with 1°F increments of the  
heating setpoint or with 1°F decrements of the cooling setpoint,  
so that by the time the next period starts, the setpoints are at  
the desired temperature. The purpose of the gradual transition  
is to use less energy by preventing staging up (because of a  
higher demand) to higher stages. The transitions occur in a linear  
fashion over the smart recovery time period.  
Smart Recovery  
Mode  
(requires  
Programming  
to be enabled)  
No, 30 minutes,  
60 minutes,  
90 minutes  
30 minutes  
None, Space, Outdoor, Average,  
Occupancy  
Remote Sensor  
Configure the application of the remote sensor input.  
None  
Humidification, Dehumidification,  
Both, None  
Humidity Control Determines available humidity mode(s).  
1. Applies to Tranquility.  
Dehumidificaton  
Table continued on next page.  
Part#: 97B0132N01 | Revised: Februar y 06, 2025  
PAG E : 9  
w w w. c l i m a te m a s te r. c o m  
GeneralDetails
NameCLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide
MakeCLIMATE MASTER
LanguageEnglish
FiletypePDF (Download)
File size1.03 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide