Home > CLIMATE MASTER > CLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide

CLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide

iGATE 2 COMMUNICATING (AWC) THERMOSTAT – IOM  
Diagnostics  
Blower Diagnostics  
OPERATING INFORMATION  
Data  
Unit  
Description  
The Diagnostics data set allows the service  
technician to view the real time status of all physical  
Instantaneous power  
consumption of the blower.  
ECM Blower Power1  
W
CV ECM Blower Speed  
rpm Current blower speed.  
inputs, switches, temperature sensor readings, as  
well as the operational status of the heat pump from  
the myUplink mobile app and web portal. Available  
data will depend on the unit/model installed.  
CV ECM Target Airflow  
cfm Current blower target airflow.  
Current temperature of the air  
entering the unit.  
Entering Air Temperature1  
F
Current temperature of the air  
leaving the unit.  
Leaving Air Temperature  
1. Applies to Trilogy only.  
F
Compressor Diagnostics  
Data  
Unit  
Description  
Refrigerant Diagnostics  
Compressor Current1  
A
Current compressor amperage.  
Data  
Unit  
Description  
Current DC bus voltage from  
the inverter.  
Current temperature of the  
inverter heat sink.  
Current power consumption of  
the compressor.  
Current amperage draw of  
the inverter.  
Compressor DC Voltage1  
Compressor Heat Sink1  
Compressor Input Power1  
V
F
Current temperature of the refrigerant liquid  
line between the air coil and the electronic  
expansion valve.  
Air Coil Liquid  
Temperature  
F
Current temperature of the refrigerant  
vapor line between the heat/cool reversing  
valve and the air coil.  
Air Coil Vapor  
Temperature1  
W
A
F
Compressor Inverter Current1  
Compressor Speed1  
Compressor  
Discharge  
Pressure1  
psi Current refrigerant discharge pressure.  
rps Current compressor speed.  
Current operating capacity  
as a percentage of the max  
capacity.  
Compressor  
Discharge  
Saturation  
Temperature1  
Compressor  
Discharge  
Superheat  
Temperature1  
Compressor  
Discharge  
Temperature  
Compressor  
Subcool  
Unit Capacity1  
%
Current saturation temperature of the  
refrigerant discharge pressure.  
F
CC2  
CCH2  
Compressor contactor output.  
Contactor high speed output.  
Current calculation of superheat  
temperature at the discharge of the  
compressor.  
F
1. Applies to Trilogy only.  
2. Applies to Tranquility only.  
Current temperature of the compressor  
discharge line.  
Loop Diagnostics  
F
F
Available data will depend on the unit/model installed.  
Current calculation of subcool temperature  
at the liquid line of  
the compressor.  
Temperature1  
Compressor  
Suction  
Data  
Unit  
Description  
Current voltage output at the  
configurable analog output.  
Current voltage output at the  
configurable analog output.  
Current temperature of the  
water entering the source heat  
exchanger.  
Current temperature of the  
water leaving the source heat  
exchanger.  
A1 Analog Output2  
V
psi Current refrigerant suction pressure.  
Pressure1  
A2 Analog Output2  
V
F
Compressor  
Suction  
Saturation  
Temperature1  
Compressor  
Suction  
Current saturation temperature of the  
refrigerant suction pressure.  
F
Entering Water Temperature  
Current calculation of superheat at the  
suction to the compressor.  
Leaving Water Temperature  
F
F
Superheat  
Temperature1  
Compressor  
Suction  
Current feedback signal of the  
loop pump.  
Loop Pump Feedback  
Loop Pump Flow Rate  
Loop Pump Power  
%
Current temperature of the compressor  
suction line.  
F
gpm Current source flow rate.  
Temperature1  
Instantaneous power  
W
Current temperature of the refrigerant  
liquid line leaving the potable water heat  
exchanger.  
Current temperature of the refrigerant liquid  
line between the source heat exchanger  
and the electronic expansion valve.  
Current temperature of the refrigerant  
vapor line between the heat/cool reversing  
valve and the source heat exchanger.  
HW Coil Liquid  
Temperature1  
consumption of the loop pump.  
Current speed of the  
loop pump.  
F
F
F
Loop Pump Speed  
Water Pressure1  
%
Water Coil  
Liquid  
Current pressure of the water  
psi as it leaves the source heat  
exchanger.  
Temperature  
Water Coil  
Vapor  
1. Applies to Trilogy only.  
2. Applies to Tranquility only.  
Temperature1  
Note 1: Applies to Trilogy only.  
PAG E : 1 6  
Part#: 97B0132N01 | Revised: Februar y 06, 2025  
w w w. c l i m a te m a s te r. c o m  
GeneralDetails
NameCLIMATE MASTER CXM2 Communicating Awc Thermostat Installation Guide
MakeCLIMATE MASTER
LanguageEnglish
FiletypePDF (Download)
File size1.03 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...