Home > Schneider Electric > Schneider Electric TC-2931 Changeover Thermostat Instruction Manual

Schneider Electric TC-2931 Changeover Thermostat Instruction Manual

TC-2931, TC-2942  
Changeover Thermostats, Strap-On Type,  
Summer/Winter  
General Instructions  
Application  
These thermostats are used primarily on combination  
heating and cooling air conditioning units to sense  
supply media temperature and reverse the control  
action of the room temperature sensing element.  
Units are hermetically sealed. TC-2942 is enclosed  
type and has 1/2” conduit adapter. Fast responding  
bimetal element actuates snap-acting SPDT with silver  
contacts. Units are supplied with three color coded 16  
gauge leads 3 ft. (914 mm) long.  
TC-2942  
Enclosed Type  
TC-2931  
Open Type  
Dimensions: 2 in. (51 mm) diameter x 1-1/2 in. (38  
mm) high.  
Table-1 Model Chart.  
Max.  
Switch Ratings (AC Only)  
Min. Hot  
Chilled  
Water  
Temp.  
°F (°C)  
Part  
Setpoint  
°F (°C)  
Differential  
°F (°C)  
Water  
Temp.  
°F (°C)  
Type  
Number  
Voltage  
(Vac)  
FLA  
LRA  
Pilot Duty  
(VA)  
(Amps)  
(Amps)  
TC-2931  
TC-2942  
Strap-On  
Fixed  
75 (24)  
Approx.  
Fixed 15  
(8)  
Approx.  
120  
240  
5.8  
2.9  
34.8  
17.4  
90 (32)  
60 (16)  
125  
Strap-On  
Encloseda  
a. Has 1/2” conduit connector  
Options  
TC-2931-204 with 10 ft. (3 m) cable and plug (which cannot  
be extended) for unit ventilator.  
TC-2931-205 with 3 ft. (914 mm) cable (which cannot be  
extended) for CP-5341.  
Accessories  
None.  
Pre-Installation  
The thermostats are shipped with an attached flange and two  
mounting springs for mounting on tubing or pipe up to 1-1/2”  
(38 mm).  
Before installing the thermostat, inspect the unit for any signs  
of damage.  
Printed in U.S.A. 8-08  
© Copyright 2008 TAC All Rights Reserved.  
F-12720-8  
GeneralDetails
NameSchneider Electric TC-2931 Changeover Thermostat Instruction Manual
MakeSchneider Electric
LanguageEnglish
FiletypePDF (Download)
File size0.07 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual
Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual
Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual

Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Get the free PDF manual for the Schneider Electric TC-2931 Changeover Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Schneider Electric TC-2931 Changeover Thermostat Instruction Manual Overview

Summary of Contents

  • Page 1: Changeover thermostats, strap-on type, are primarily used on combination heating and cooling air conditioning units to sense supply media temperature and reverse the control action of the room temperature sensing element. Units are hermetically sealed. TC-2942 is an enclosed type and has a 1/2” conduit adapter. Fast responding bimetal element actuates snap-acting SPDT with silver contacts. Units are supplied with three color coded 16 gauge leads 3 ft. (914 mm) long. Dimensions are 2 in. (51 mm) diameter x 1-1/2 in. (38 mm) high. The thermostats are shipped with an attached flange and two mounting springs for mounting on tubing or pipe up to 1-1/2” (38 mm). Before installing the thermostat, inspect the unit for any signs of damage. Options include TC-2931-204 with 10 ft. (3 m) cable and plug, and TC-2931-205 with 3 ft. (914 mm) cable. Accessories are not included.
  • Page 2: Requirements for thermostat installation include mounting in any position with specific spring configurations for different pipe sizes. The unit must be exposed to temperatures below 62°F (17°C) or above 88°F (31°C) to establish necessary circuits. Caution is advised against disassembling the thermostat due to its hermetically sealed design. Maintenance involves cleaning and applying silicone lubricant if excessive corrosion occurs between sensing elements and the pipe. Installation procedure requires hooking the spring to the flange on a clean section of the pipe and insulating only after installation on insulated pipes. Field repairs on the thermostat are not recommended; replacement is advised if malfunctioning. Electrical connections must comply with job diagrams and national and local electrical codes. Standard units come with color-coded leads for easy connection to other equipment. The document contains copyright information and notes that details are subject to change without notice.