Home > Schneider Electric > Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
TC-2931, TC-2942
Changeover Thermostats, Strap-On Type,
Summer/Winter
General Instructions
Application
These thermostats are used primarily on combination
heating and cooling air conditioning units to sense
supply media temperature and reverse the control
action of the room temperature sensing element.
Units are hermetically sealed. TC-2942 is enclosed
type and has 1/2” conduit adapter. Fast responding
bimetal element actuates snap-acting SPDT with silver
contacts. Units are supplied with three color coded 16
gauge leads 3 ft. (914 mm) long.
TC-2942
Enclosed Type
TC-2931
Open Type
Dimensions: 2 in. (51 mm) diameter x 1-1/2 in. (38
mm) high.
Table-1 Model Chart.
Max.
Switch Ratings (AC Only)
Min. Hot
Chilled
Water
Temp.
°F (°C)
Part
Setpoint
°F (°C)
Differential
°F (°C)
Water
Temp.
°F (°C)
Type
Number
Voltage
(Vac)
FLA
LRA
Pilot Duty
(VA)
(Amps)
(Amps)
TC-2931
TC-2942
Strap-On
Fixed
75 (24)
Approx.
Fixed 15
(8)
Approx.
120
240
5.8
2.9
34.8
17.4
90 (32)
60 (16)
125
Strap-On
Encloseda
a. Has 1/2” conduit connector
Options
TC-2931-204 with 10 ft. (3 m) cable and plug (which cannot
be extended) for unit ventilator.
TC-2931-205 with 3 ft. (914 mm) cable (which cannot be
extended) for CP-5341.
Accessories
None.
Pre-Installation
The thermostats are shipped with an attached flange and two
mounting springs for mounting on tubing or pipe up to 1-1/2”
(38 mm).
Before installing the thermostat, inspect the unit for any signs
of damage.
Printed in U.S.A. 8-08
© Copyright 2008 TAC All Rights Reserved.
F-12720-8
| General | Details |
|---|---|
| Name | Schneider Electric TC-2931 Changeover Thermostat Instruction Manual |
| Make | Schneider Electric |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.07 MB |

Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual

Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual

Schneider Electric Wiser Radiator Thermostat Instructions

Schneider Electric 2290B Programmable Room Thermostat Instruction Manual

Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual

Schneider Electric TC-2931 Changeover Manual: Questions and Answers
How do I install the Schneider Electric TC-2931 Changeover on my pipe?
Hook one spring end in the flange hole on clean pipe, position the thermostat, pull the spring under the pipe, and hook the other end in the opposite flange hole.
- Choose a smooth, clean section of pipe or tubing.
- Hook one end of the spring into the hole on the flange.
- Position the thermostat on the pipe.
- Pull the spring around under the pipe.
- Hook the other spring end into the hole on the opposite side of the flange. Instruction Manual, p. 2
How can I tell the Schneider Electric TC-2931 Changeover is working correctly?
Below 62°F, a circuit forms between yellow and red leads. Above 88°F, a circuit forms between yellow and blue leads. Instruction Manual, p. 2
Schneider Electric thermostat won't switch between heating and cooling?
- Do not attempt field repair; the unit is hermetically sealed.
- If the system does not operate correctly and the thermostat is the cause, replace the unit. Instruction Manual, p. 2
Can the Schneider Electric TC-2931 Changeover be mounted on different pipe sizes?
Use one spring for pipe up to 1/2 inch diameter, or hook two springs together for pipe up to 1-1/2 inches diameter. Instruction Manual, p. 2