Home > Schneider Electric > Schneider Electric TC-2931 Changeover Thermostat Instruction Manual

Schneider Electric TC-2931 Changeover Thermostat Instruction Manual

TC-2931, TC-2942  
Changeover Thermostats, Strap-On Type,  
Summer/Winter  
General Instructions  
Application  
These thermostats are used primarily on combination  
heating and cooling air conditioning units to sense  
supply media temperature and reverse the control  
action of the room temperature sensing element.  
Units are hermetically sealed. TC-2942 is enclosed  
type and has 1/2” conduit adapter. Fast responding  
bimetal element actuates snap-acting SPDT with silver  
contacts. Units are supplied with three color coded 16  
gauge leads 3 ft. (914 mm) long.  
TC-2942  
Enclosed Type  
TC-2931  
Open Type  
Dimensions: 2 in. (51 mm) diameter x 1-1/2 in. (38  
mm) high.  
Table-1 Model Chart.  
Max.  
Switch Ratings (AC Only)  
Min. Hot  
Chilled  
Water  
Temp.  
°F (°C)  
Part  
Setpoint  
°F (°C)  
Differential  
°F (°C)  
Water  
Temp.  
°F (°C)  
Type  
Number  
Voltage  
(Vac)  
FLA  
LRA  
Pilot Duty  
(VA)  
(Amps)  
(Amps)  
TC-2931  
TC-2942  
Strap-On  
Fixed  
75 (24)  
Approx.  
Fixed 15  
(8)  
Approx.  
120  
240  
5.8  
2.9  
34.8  
17.4  
90 (32)  
60 (16)  
125  
Strap-On  
Encloseda  
a. Has 1/2” conduit connector  
Options  
TC-2931-204 with 10 ft. (3 m) cable and plug (which cannot  
be extended) for unit ventilator.  
TC-2931-205 with 3 ft. (914 mm) cable (which cannot be  
extended) for CP-5341.  
Accessories  
None.  
Pre-Installation  
The thermostats are shipped with an attached flange and two  
mounting springs for mounting on tubing or pipe up to 1-1/2”  
(38 mm).  
Before installing the thermostat, inspect the unit for any signs  
of damage.  
Printed in U.S.A. 8-08  
© Copyright 2008 TAC All Rights Reserved.  
F-12720-8  
GeneralDetails
NameSchneider Electric TC-2931 Changeover Thermostat Instruction Manual
MakeSchneider Electric
LanguageEnglish
FiletypePDF (Download)
File size0.07 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual
Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual
Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual

Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Get the free PDF manual for the Schneider Electric TC-2931 Changeover Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Schneider Electric TC-2931 Changeover Manual: Questions and Answers

How do I install the Schneider Electric TC-2931 Changeover on my pipe?

Hook one spring end in the flange hole on clean pipe, position the thermostat, pull the spring under the pipe, and hook the other end in the opposite flange hole.

  1. Choose a smooth, clean section of pipe or tubing.
  2. Hook one end of the spring into the hole on the flange.
  3. Position the thermostat on the pipe.
  4. Pull the spring around under the pipe.
  5. Hook the other spring end into the hole on the opposite side of the flange. Instruction Manual, p. 2

How can I tell the Schneider Electric TC-2931 Changeover is working correctly?

Below 62°F, a circuit forms between yellow and red leads. Above 88°F, a circuit forms between yellow and blue leads. Instruction Manual, p. 2

Schneider Electric thermostat won't switch between heating and cooling?

  • Do not attempt field repair; the unit is hermetically sealed.
  • If the system does not operate correctly and the thermostat is the cause, replace the unit. Instruction Manual, p. 2

Can the Schneider Electric TC-2931 Changeover be mounted on different pipe sizes?

Use one spring for pipe up to 1/2 inch diameter, or hook two springs together for pipe up to 1-1/2 inches diameter. Instruction Manual, p. 2

More Schneider Electric thermostat manuals