Installation Instructions  
SpaceLogic Thermostat TC900 Series Installation Instructions  
schneider-electric.com | 1  
schneider-electric.com | 2  
Precautions  
SpaceLogic Thermostat  
TC900 Series for Modulating Fan Coil Applications  
DANGER  
related to the construction and operation of this electrical  
equipment and installations, and has received safety  
training to recognize and avoid the hazards involved.  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC  
FLASH  
TC903-3A2P-24, TC903-3A4DPSA, TC903-3A4DPMSA, TC903-3A4DPMSA-24  
TC907-3A2P-24, TC907-3A4DPSA, TC907-3A4DPMSA, TC907-3A4DPMSA-24  
TC907-3A2P-24B, TC907-3A4DPSAB, TC907-3A4DPMSAB,  
TC907-3A4DPMSA-24B  
ꢀ Follow safe electrical work practices. See NFPA 70E in the  
USA, CSA Z462 in Canada, or applicable local codes.  
ꢀ Read and understand the instructions before installing the  
product. Follow the instructions during installation.  
ꢀ Installation, wiring, testing or service must be performed  
only by qualified persons in accordance with all applicable  
codes and regulations.  
ꢀ Do not use the product for life or safety applications.  
ꢀ Do not install the product in hazardous or classified locations.  
ꢀ Do not exceed the product’s ratings or maximum limits.  
ꢀ The product may use multiple voltage/power sources.  
ꢀ Turn off ALL power supplying equipment before working on  
or inside the equipment.  
manufacturer, the protection provided by the product may  
Electric for any consequences arising out of the use of this  
material.  
becomes dirty. Do not use any cleaning agent, especially  
alcohol.  
ꢀ Use a properly rated voltage sensing device to confirm that  
all power is off.  
ꢀ Do NOT depend on the product for voltage indication.  
ꢀ Products rated only for basic insulation must be installed on  
insulated conductors.  
TC907 Series  
TC903 Series  
Product Description  
ꢀ Current transformer secondaries (current mode) must be  
shorted or connected to a burden at all times.  
ꢀ Remove all wire scraps and tools, replace all doors, covers  
and protective devices before powering the equipment.  
Dimensions  
The TC900 Series fan coil thermostats are  
Hole pitch  
60 mm (standard)  
residential applications.  
Failure to follow these instructions will result in death or  
serious injury.  
Control pollution degree Pollution Degree 2  
The TC900 Series can be used for 2-pipe or 4-pipe  
applications.  
Operation type  
Terminal sizing  
Terminals torque*  
Type 1.B  
Dimensions mm (in.)  
TC907 Series  
conductors  
Front View  
Back View  
Side View  
39.0 (1.54)  
14.5 (0.57)  
Max: 0.44N.m  
86.0 (3.40)  
64.5 (2.54)  
68.0 (2.68)  
Built-in sensing element  
European conformance CE:  
Accuracy  
±1 °C  
Agency approvals  
UKCA (UK)  
Set-point range  
5 to 35 °C  
EAC (Russia)  
RCM (Australia)  
RoHS: 2011/65/EU, 2015/863/EU  
REACH: 1907/2006/EC  
0 to 50 °C (shown in 0.5 °C  
increments)  
Display range  
Operating temp.  
0 to 50 °C  
*Exceeding the maximum torque when tightening the terminal  
screw may lead to plastic cracking.  
Operating humidity  
Power consumption  
5 to 95 %RH (non-condensing)  
< 1.7 W  
60.0 (2.36)  
90 to 240 Vac, 50/60Hz  
Power supply  
Relay & load  
TC903 Series  
Relay rating 5A  
Load rating 2A resistive, 1A  
inductive  
Front View  
Back View  
Side View  
39.0 (1.54)  
86.0 (3.40)  
64.5 (2.54)  
7)  
14.5 (0.5  
Protection class  
Housing  
IP20  
55.4 (2.18)  
Flame-retardant PC  
USA: +1 888-444-1311  
Europe: +46 10 478 2000  
Asia: +65 6484 7877  
60.0 (2.36)  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
January 2024  
F-28138-8 nk  
SpaceLogic Thermostat TC900 Series Installation Instructions  
Functions  
Set-point Adjustment  
SpaceLogic Thermostat TC900 Series Installation Instructions  
setting by 1 °C, the modulating control valve opens  
schneider-electric.com | 3  
models which only support one, but not both simul-  
schneider-electric.com | 4  
Sleep Energy Saving Mode  
At 12:00 a.m., Sleep Energy Saving mode turns on  
and displays at 1:00 a.m. The temperature  
according to the 0 to 10 Vdc analog output control  
signal. When room temperature reaches or is low-  
er than (higher than) the temperature setting, the  
modulating control valve closes, according to the 0  
to 10 Vdc analog output control signal.  
The set-point buttons allow users to adjust the set-  
point (in 0.5 °C increments) for the space.  
setpoint increases or decreases automatically  
Installation Guidelines  
Fan Speed  
thermostat is in cooling mode, the setpoint will in-  
crease 1 °C per hour until 3:00 a.m. then decreases  
1 °C per hour until the original setpoint is reached  
at 7:00 a.m. and  
is in heating mode, the setpoint will decrease 1°C  
per hour until 3:00 a.m. and then increases 1°C per  
hour until the original setpoint is reached at 7:00  
a.m. and  
ꢀ Install the thermostat about 1.5 m (59”) above  
Modulating Valve Control (4-Pipe Models)  
Users can select a fan speed (High, Medium, Low  
In Cooling mode, when the room temperature is  
higher than the temperature setting by 1°C, the  
modulating cooling control valve opens according  
to the 0 to 10 Vdc analog output control signal.  
When room temperature is less than or equal to the  
temperature setting, the modulating cooling control  
valve closes according to the 0 to 10 Vdc analog  
output control signal. The modulating heating con-  
trol valve remains closed.  
installation/service  
Mode Control  
Users can switch operating modes (Heating, Cool-  
ing, or Ventilation) by pressing the Mode button.  
by radiant heat or in places with high levels of  
sunlight  
not rise above 26°C and the heating setpoint will  
not drop below 18°C in Sleep Energy Saving mode.  
Eco Mode  
ꢀ Do not install thermostats behind doors or in  
corners  
Time Setting Function  
ECO button (TC903) or the ECO button (TC907)  
appears  
of the LCD display. In Cooling mode, the set-point  
is automatically adjusted to 26°C and the fan speed  
is set to Low. In Heating mode, the set-point is  
automatically adjusted to 18 °C and the fan speed  
ꢀ Protect from water/debris to avoid damaging the  
thermostat  
During power-on, press and hold  
to enter the Time Setting mode. Press the mode  
button again to select the hour, minute and week.  
In Heating mode, when the room temperature is  
lower than the temperature setting by 1 °C, the  
modulating heating control valve opens according  
to the 0 to 10 Vdc analog output control signal.  
When room temperature is greater than or equal to  
the room temperature setting, the modulating heat-  
ing control valve closes according to the 0 to 10  
Vdc analog output control signal. The modulating  
cooling control valve remains closed.  
Operation Instructions  
Press the up  
and down  
buttons to adjust this  
-
will turn  
Button Lockout Function  
Press and hold the up  
OFF button  
fan speed, as desired, or do a short press of the  
ECO button (TC907) to cancel Eco mode.  
motorized valve. If no buttons are pressed for 10  
and down  
buttons at  
-
any button to turn the backlight back on.  
Temperature Setting  
pad lockup function to prevent thermostat operation  
by others. While lockout is active, the lock icon  
will be displayed on the screen. To deactivate the  
Energy Saving Functions  
Energy Saving Mode  
Button Lockout Function  
This function allows the buttons to be deactivated to  
prevent thermostat operation by others.  
With the power on, press  
perature setting and  
to decrease the tem-  
to increase temperature in  
button on TC903 or the  
lockout function, press and hold the up  
down  
and  
ECO  
button on TC907 to turn on Eco mode.  
and icons. If the  
Low Temperature Protection  
steps of 0.5°C. The  
will appear on the display.  
is  
The display will show the  
to unlock the system.  
If the room temperature drops below 5 °C, Heating  
mode will start automatically and the fan speed will  
be set to High. Once the temperature reaches 7 °C,  
thermostat is in Cooling mode, the temperature is  
automatically set to 26 °C with the fan running at  
low speed. If the thermostat is in Heating mode,  
the temperature is automatically set to 18 °C with  
Low Temperature Protection Function  
Mode Selection  
temperature drops below 5 °C, the thermostat will  
start automatically for heating and display the  
symbol. The fan will run at high speed automati-  
cally and the motorized valve will be opened (hot  
water valve will be opened for 4-pipe models).  
When the room temperature rises to 7 °C, the low  
temperature protection function is canceled and the  
thermostat will stop automatically, returning to its  
With the power on, press to switch the operation  
mode. The display indicates cooling with , heating  
Alert  
press the up  
or down  
buttons to change the  
or  
with  
and ventilation with . Auto mode can be  
-
stat will attempt to command the valve to close and  
place the device in an inoperative state. The display  
-
selected in the parameter settings and is indicated  
ECO buttons.  
on the display with  
.
Unoccupied Energy Saving Mode  
Fan Speed Selection  
nostic messages:  
Unoccupied Energy Saving mode can be entered  
With the power on, press  
TC907 to select a fan wind/air speed of high  
medium , low or automatic . In automatic  
on TC903 or  
on  
after a hotel room key card is removed from the  
Alert Function  
reader  
and  
are displayed. If the thermostat  
mode, the fan speed changes automatically. For a  
is in cooling mode, the temperature is automatically  
set to 28 °C with the fan running at low speed. If  
the thermostat is in heating mode, the temperature  
is automatically set to 16 °C with the fan running  
at low speed. When the key card is returned to the  
depending on which is selected), the thermostat  
will attempt to command the fan and valve to close,  
will automatically switch to medium fan speed. For  
-
Remote Sensor/Key Card  
cally switch to high wind speed.  
reader, the indoor  
display and ECO  
icon turn  
Modulating Valve Control (2-Pipe Models)  
terminals are utilized for a remote temperature  
In Cooling (Heating) mode, when the room temper-  
ature is higher than (lower than) the temperature  
mode.  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
hneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
GeneralDetails
NameSchneider Electric TC900 Series Space Logic Thermostat Instruction Manual
MakeSchneider Electric
LanguageEnglish
FiletypePDF (Download)
File size1.38 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual

Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual
Get the free PDF manual for the Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual Overview

Summary of Contents

  • Page 1: Installation instructions for SpaceLogic Thermostat TC900 Series are provided. Precautions include following safe electrical work practices and ensuring qualified personnel perform installation. The product is not intended for life or safety applications and must not be installed in hazardous locations. The TC900 Series can be used for 2-pipe or 4-pipe applications. Set-point adjustment allows users to modify the temperature in 0.5 °C increments. Sleep Energy Saving mode adjusts the temperature automatically during the night. Users can select fan speed and switch operating modes (Heating, Cooling, or Ventilation). Low temperature protection function activates heating mode automatically if the temperature drops below 5 °C. Unoccupied Energy Saving mode can be activated after a hotel room key card is removed. The thermostat features a button lockout function to prevent unauthorized operation.
  • Page 2: SpaceLogic Thermostat TC900 Series Installation Instructions Parameter Settings Energy Saving Functions The mode button or Fan button allows navigation between parameters. Low temperature protection can be enabled or disabled. This parameter table must be set by specialized installation personnel authorized by Schneider Electric. Provide an approved disconnecting means and overcurrent protection to supply conductors. The TC900 Series thermostats come with the option of Modbus communication. The RS-485 communication parameters can be adjusted. The TC900 Series thermostats communicate as a Modbus RTU secondary device. Brightness values for backlight can be adjusted from 0 to 5% in 1% increments. Ensure the polarity of the mains supply is correct during installation.