Parameter Settings  
Energy Saving Functions (cont.)  
Parameter Settings Table (cont.)  
place the device in an inoperative state and display  
the  
Number  
26  
Parameter  
Default  
00  
Description  
the mode button or Fan button to move forward  
or backward between the parameters shown in the  
switch selection  
Backlight standby brightness  
01: Key card switch  
00 = 0% brightness to 05 = 5% brightness  
E1: Sensor short-circuit alert  
E2: Sensor open-circuit alert  
27  
05  
table below. Press the up  
to adjust these parameters.  
and down  
buttons  
* For 2-pipe system with 3-wire motorized valve, the thermostat supports either Heating Mode or Cooling Mode, but not  
both Heating mode and Cooling mode simultaneously.  
is lower than 0 °C.  
Parameters 01 to 11 apply to all models.  
Parameter Settings Table  
Number  
Parameter  
Default  
Description  
01  
Low temperature protection  
On  
OF: Disabled, On: Enabled  
Parameter 27 only applies to TC907 models.  
Fan operation status after  
temperature setting is reached  
02  
03  
DA  
00  
This parameter table must be set by specialized installation personnel authorized by Schneider Electric. Any inconvenience  
or damage caused by unauthorized operation will not be covered by warranty.  
00: Power-down memory, 01: power-down do not remember,  
02: power-up power-on  
Power-on state  
04  
05  
06  
07  
08  
1°C  
2°C  
1~3°C  
1~5°C  
Wiring  
Provide an approved disconnecting means and  
overcurrent protection to supply conductors. The  
disconnecting device(s) shall meet the relevant  
Standalone  
requirements of IEC 60947-1 and IEC 60947-3 and  
shall be suitable for the application. Locate and  
mark per local requirements.  
Heating set-point upper limit  
Cooling set-point lower limit  
Auto deadband  
35°C 5 to 35°C  
5°C  
1°C  
5 to 35°C  
1 to 3°C (only for 4-pipe Auto mode)  
90 to 240Vac  
00: Heating only (heating, ventilation), 01: Cooling only (cooling,  
ventilation), 02: Heating and cooling (heating, cooling, ventilation)  
AC24V  
TC903(7)-3A4DPSA(B)  
TC903(7)-3A2P-24(B)  
N
L
Mode button selection (2-pipe)  
Mode button selection (4-pipe)  
02  
02  
R
C
Remote Sensor  
Input  
S1  
S2  
GND  
L
09  
Cooling Valve  
Heating Valve  
AO1  
AO2  
00: Heating only (heating, ventilation), 01: Cooling only (cooling,  
ventilation), 02: Heating and cooling (heating, cooling, ventilation),  
03: Auto, 04: 2-pipe mode*  
C1  
C2  
AO1  
Energy  
Saving Input  
Thermostat  
Thermostat  
N
OF: Fan Auto disabled - Fan mode setting can be High, Medium or  
Low, On: Fan Auto enabled - Fan mode setting can be High, Medi-  
10  
Auto fan setting  
On  
N
L
R
C
11  
12  
13  
14  
15  
16  
17  
18  
Show temperature selection  
Modbus connection  
Modbus address setting  
Modbus baud rate  
00  
On  
01  
01  
00  
On  
24  
On  
00: Room temperature, 01: Set-point  
OF: Disabled, On: Enabled  
01 to 64  
00: 4800 bps, 01: 9600 bps, 02: 19200 bps, 03: 38400 bps  
Modbus parity check  
Clock display  
90 to 240Vac  
AC24V  
AC24V  
TC903(7)-3A4DPMSA-24(B)  
TC903(7)-3A4DPMSA-24(B)  
OF: Disabled, On: Enabled  
TC903(7)-3A4DPMSA(B)  
S1  
RS-485  
Modbus  
RS-485  
Modbus  
RS-485  
Modbus  
N
L
Energy  
Saving  
R
C
R
C
Remote Sensor  
Input  
Remote Sensor  
S1  
C1  
C2  
A
A
A
Input  
S2  
S2  
12/24 hour clock  
12: 12-hour clock, 24: 24-hour clock  
OF: Disabled, On: Enabled  
B
B
B
Cooling Valve  
Heating Valve  
AO1  
AO2  
Cooling  
Valve  
Cooling  
Valve  
C1  
AO1  
AO2  
AO1  
AO2  
L
L
Sleep Energy Saving mode  
Heating  
Valve  
Heating  
Valve  
C2  
Energy  
Saving Input  
Cooling temperature, Unoccu-  
pied Energy Saving mode  
Thermostat  
Thermostat  
Thermostat  
19  
20  
21  
28°C 22 to 32°C  
16°C 10 to 21°C  
N
N
R
C
R
C
N
L
Heating temperature, Unoccu-  
pied Energy Saving mode  
Fan speed, Unoccupied  
Energy Saving mode  
02  
00: High speed, 01: Medium speed, 02: Low speed  
22  
23  
Temperature sensor selection  
Low-speed fan output voltage  
00  
3.3V  
Range: 0V to medium-speed setting  
Medium-speed fan output  
voltage  
24  
25  
6.6V  
10V  
Range: Low-speed setting to high-speed setting  
Range: Medium-speed setting to 10V  
High-speed fan output voltage  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
SpaceLogic Thermostat TC900 Series Installation Instructions  
SpaceLogic Thermostat TC900 Series Installation Instructions  
schneider-electric.com | 7  
schneider-electric.com | 8  
Modbus Transport Protocols (cont.)  
Mounting  
Reg.  
Description  
12 = 12-hour clock  
24 = 24-hour clock  
TC903 Series  
Function Code 03/06 (cont.)  
30 12/24-hour clock  
Reg.  
Description  
Set-point  
00 = Occupied  
when short-circuit,  
unoccupied when  
open-circuit  
01 = Unoccupied  
when short-circuit,  
occupied when  
open-circuit  
4
5 to 35 °C  
00 = High,  
01 = Medium,  
02 = Low, 03 = Auto  
5
Fan mode  
31  
close/open  
6
7
Heating set-point, upper limit 5 to 35°C  
Cooling set-point, lower limit 5 to 35°C  
0 = Disable  
8
9
ECO mode  
1 = Enable  
TC907 Series  
Unoccupied mode, cooling  
setpoint  
32  
33  
22 to 32°C  
10 to 21°C  
ECO mode, cooling set-point 22 to 32°C  
Unoccupied mode, heating  
setpoint  
10 ECO mode, heating set-point 10 to 21°C  
11 Temperature compensation -5 to 5°C  
00 = High  
01 = Medium  
02 = Low  
Unoccupied mode, fan  
speed  
12 Setpoint, upper limit  
13 Setpoint, lower limit  
2 to 49.5°C  
0 to 47.5°C  
34  
0 = Disable  
1 = Enable  
00 = Local device  
35 Temp. value from connection 01 = Modbus  
connection  
14 Sleep mode  
2. Remove the display 3. Connect the wires  
head screwdriver along from the base module. according to the appro- module onto the wall  
4. Mount the base  
5. Fit the display module  
onto the base module.  
Align upper hooks be-  
tween the two modules.  
Carefully replace the  
wiring connection if it  
has been removed.  
0 = Disable  
1 = Enable  
15 Low temperature protection  
36 Temp. input  
the bevel into the slot. Carefully remove the  
Pry upwards with appro- wire connections, if  
priate force to release required.  
the two hooks.  
priate wiring diagram  
Fan operation after setting  
16  
37 Heating mode KP  
38 Cooling mode KP  
39 PID sampling time  
40 KI  
1 to 99  
1 to 99  
1 to 99 s  
0 to 99  
1 to 99  
shown above. Ensure screws supplied.  
the polarity of the mains  
supply is correct.  
temperature is reached  
1 = Fan on  
00 = Power-down  
memory  
17 Power-on state  
Click display module  
onto base module using  
the two lower hooks.  
41 Span  
memory  
02 = Display on  
when powered  
Heating valve 2, output  
voltage  
42*  
is displayed)  
Modbus Transport Protocols  
Code  
Register Type  
Data  
Format  
18  
1 to 3°C  
1 to 5°C  
1 to 3°C  
Read holding  
registers  
16-bit unsigned  
integer  
19  
Cooling valve 1, output  
voltage  
The TC900 Series thermostats come with the  
option of Modbus communication. The support of  
Modbus communication allows simple integration  
of the TC900 Series thermostats with a building  
management system using standard Modbus serial  
communication.  
03  
Word  
43*  
20 Auto deadband  
is displayed)  
Read input  
registers  
16-bit unsigned  
integer  
0 = Heat only (heat  
& vent)  
1 = Cool only (cool  
& vent)  
2 = Heat and cool  
(heat, cool & vent)  
3 = Auto  
04  
06  
Word  
Word  
Range: 0V to  
medium-speed  
setting  
Low-speed fan output  
voltage  
44  
Write single  
register  
16-bit unsigned  
integer  
Operation mode  
21  
Range: Low-speed  
setting to high-speed  
setting  
Medium-speed fan output  
voltage  
Function Code 01  
45  
The TC900 Series thermostats communicate as  
a Modbus RTU secondary device over a serial  
RS-485 connection, allowing for the transfer of  
real-time data. The RS-485 communication para-  
meters, such as baud rate, parity check and Mod-  
bus address, can be adjusted.  
Reg.  
Description  
Cooling valve (4-pipe)  
High-speed fan output  
voltage  
Range: Medium-  
speed setting to 10V  
4 = 2-pipe mode  
46  
0
4
5
6
7
0 = Disable  
1 = Enable  
22 Auto fan  
Fan speed status high  
Fan speed status medium  
Fan speed status low  
Heating valve (4-pipe)  
0 = Unlocked  
1 = Locked  
47 Keypad status  
00 = Room temp.  
01 = Set-point  
23 Display temperature  
24 Temperature sensor  
0 = Unoccupied  
1 = Occupied  
48* Occupancy status  
00 = Built-in sensor  
1 = Occupied  
2 = Unoccupied  
in the Parameter Settings Table. If required, adjust  
the settings to disable the Modbus connection. All  
of these settings can be completed under menu  
items 12 to 15. Connection to the RS-485 network  
is made via dedicated terminals on the back of  
the thermostat and marked A (+) and B (-). The  
following Modbus register types and formats are  
supported:  
Function Code 02  
49 Occupancy override  
50* Keycard status  
0 - Disable  
1 - Enable  
1 to 64  
25 Modbus connection  
Reg.  
Description  
26 Modbus address setting  
2
3
Temp sensor, short circuit  
Temp sensor, open circuit  
0 = OK, 1 = Fault  
0 = OK, 1 = Fault  
1 = Present  
00 = 4800 bps  
01 = 9600 bps  
02 = 19200 bps  
03 = 38400 bps  
Brightness values  
0 to 5% in 1%  
increments.  
Backlight brightness  
(TC907 only)  
51  
27 Modbus baud rate  
Function Code 03/06  
Reg.  
Description  
*Read only.  
00 = Odd check  
01 = Even check  
28 Modbus parity check  
29 RTC clock display  
2
Thermostat mode  
Function Code 04  
02=Frost protection*  
Code  
Register Type  
Data  
Format  
1 = Cool, 2 = Heat,  
3 = Ventilation,  
4 = Auto  
01 Read coils  
Boolean Binary/digital  
0 = Disable  
1 = Enable  
Register  
Description  
3
Operation mode  
Read discrete  
inputs  
0
Actual room temperature  
0 to 50°C  
02  
Boolean Binary/digital  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
© 2024 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.  
Schneider Electric, 35 rue Joseph Monier, F - 92500 Rueil-Malmaison  
GeneralDetails
NameSchneider Electric TC900 Series Space Logic Thermostat Instruction Manual
MakeSchneider Electric
LanguageEnglish
FiletypePDF (Download)
File size1.38 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CCTFR6100Z3 Wiser Radiator Thermostat User Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric Wiser Radiator Thermostat Instructions
Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Schneider Electric TC-2931 Changeover Thermostat Instruction Manual
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual
Schneider Electric 2290B Programmable Room Thermostat Instruction Manual

Schneider Electric TC900 Series Space Logic Thermostat Instruction Manual