Floor temperature sensor icon is
displayed in the alarm list
Outdoor temperature sensor icon is
displayed in the alarm list
CD0000781
CD0000783
Figure 3. Example from a heating system operating in eco
mode without demand, in control mode RFT
Figure 5. Example from a heating system operating in comfort
mode with demand, in control mode RO
•
Defective temperature sensor
•
Defective temperature sensor
–
–
Make sure that the floor sensor is connected correctly.
–
–
Make sure that the outdoor sensor is connected correctly.
Disconnect the temperature sensor and examine it with an
ohmmeter. Make sure that the value agrees with the
temperature sensor diagram.
Disconnect the temperature sensor and examine it with an
ohmmeter. Make sure that the value agrees with the
temperature sensor diagram.
•
•
Incorrect thermostat control mode
•
•
Incorrect thermostat control mode
–
Select the correct thermostat control mode (settings
menu 4).
–
Select the correct thermostat control mode (settings
menu 4).
Temperature sensor not connected
Connect the temperature sensor.
Temperature sensor not connected
Connect the temperature sensor.
–
–
Remote temperature sensor icon is
shown in the alarm list
Relative humidity icon is displayed in
the alarm list
CD0000784
CD0000782
Figure 4. Example from a cooling system operating in comfort Figure 6. Example from a cooling system operating in comfort
mode without demand, in control mode RS
mode without demand, in control mode RT
•
Defective temperature sensor
Note
–
–
Make sure that the remote sensor is connected correctly.
Relative humidity control is activated in the Uponor
Smatrix Pulse app (requires communication module).
Disconnect the remote temperature sensor and examine it
with an ohmmeter. Make sure that the value agrees with the
temperature sensor diagram.
•
The relative humidity limit is reached
–
Start a dehumidifier or increase the supply temperature
setpoint to lower the humidity level.
•
•
Incorrect thermostat control mode
–
Select the correct thermostat control mode (settings
menu 4).
Temperature sensor not connected
Connect the temperature sensor.
5.5 Speak to the installer
For the installer’s contact information, refer to the installation report.
Prepare this information before you speak to an installer:
–
•
•
•
Installation report
Drawings of the underfloor heating system (if available)
List of all alarms, including times and dates
|
|
12 Uponor Smatrix Base thermostat D+RH T-247 BUS Operation manual