5.6 Installer instructions  
To determine if a problem is caused by the supply system or the  
control system, do these steps:  
Loosen the actuators from the manifold for the applicable room. Wait  
few minutes. Then examine if the flow pipe of the underfloor heating  
loop becomes warm.  
If the pipe does not become warm, the problem is in the heating  
system. If the loop becomes warm, the cause can be the room  
control system.  
A supply system malfunction can be identified by no warm water in  
the manifold. Do a check of the boiler and circulation pump.  
|
|
Uponor Smatrix Base thermostat D+RH T-247 BUS Operation manual  
13  