5.6 Installer instructions
To determine if a problem is caused by the supply system or the
control system, do these steps:
Loosen the actuators from the manifold for the applicable room. Wait
few minutes. Then examine if the flow pipe of the underfloor heating
loop becomes warm.
If the pipe does not become warm, the problem is in the heating
system. If the loop becomes warm, the cause can be the room
control system.
A supply system malfunction can be identified by no warm water in
the manifold. Do a check of the boiler and circulation pump.
|
|