7.ꢀTROUBLESHOOTING  
In the event of damage or malfunction of one of the temperature sensors, the heating output cuts off (fail safe) and an error  
code is displayed.  
Error Code  
ER1  
ER2  
ER3  
ER4  
Description  
Short circuit on floor sensor  
Open circuit on floor sensor / Missing floor sensor  
Short circuit on room sensor  
Open circuit on room sensor  
Check sensing mode  
ER5  
The floor sensor can be replaced by a new. In the event of malfunction of the room sensor, the entire thermostat must be  
replaced (Error 3 or Error 4).  
Error 5 occurs if the thermostat is set in Room Sensing Mode and the floor sensor is installed.  
To resolve the error change the sensing mode in Floor sensing or Room sensing with floor temperature limiter. Otherwise,  
remove the floor sensor to work in room sensing mode. The floor sensor has got the following temperature/resistance values:  
Temperature  
15°C  
20°C  
25°C  
30°C  
Resistance  
15.8 kΩ  
12.5 kΩ  
10.0 kΩ  
8.0 kΩ  
35°C  
6.5 kΩ  
8.ꢀTECHNICAL SPECIFICATION  
Supply voltage  
230VAC, +10%, –15%, 50Hz  
Power consumption (Stand-by)  
Relay output  
3 VA  
230V, maximum 13A resistive load (max. 3000W)  
Ambient temperature – operation  
Ambient temperature – transport  
Temperature range, floor sensor  
Temperature range, room sensor  
Switching hysteresis  
0 .. 40°C, 5-95% RH (non condensing)  
–10 .. +60°C  
+5 .. +35°C  
+5 .. +40°C  
1°C (Factory settings adjustable between  
0.5-2.0°C)  
Control modes  
Floor sensing  
Room sensing  
Room sensing with floor temperature limiter  
Manual ON/OFF  
Temperature control  
Timer programme  
Protection class  
IP 21  
Terminals  
Max. 2,5 mm²  
Floor sensor with 3 m cable  
Maximum length of floor sensor Cable  
Approvals  
NTC, 10KΩ / 25°C  
100 m, 2 x 1,5 mm² (230VAC cable type)  
Type of action  
Control pollution degree  
Rated impulse voltage  
Temperature for the ball pressure test  
SELV limits realized  
1.B. (39)*  
2 (49)*  
4kV (75)*  
125°C (77)*  
22 VDC (86)*  
* According to the EN 60730-1 table 1  
nVent.com/RAYCHEM | 9  
GeneralDetails
NamenVent RAYCHEM Green Leaf Programmable Thermostat Instruction Manual
MakenVent RAYCHEM
LanguageEnglish
FiletypePDF (Download)
File size0.43 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
nVent RAYCHEM ETS-05 Electronic Thermostat Instruction Manual
nVent RAYCHEM ETS-05 Electronic Thermostat Instruction Manual
nVent RAYCHEM RAYSTAT-EX-02 Mechanical Thermostat Installation Guide
nVent RAYCHEM RAYSTAT-EX-02 Mechanical Thermostat Installation Guide
nVent RAYCHEM Elexant 3500i Electronic Thermostat Installation Guide
nVent RAYCHEM Elexant 3500i Electronic Thermostat Installation Guide
nVent RAYCHEM RayStat-M2 Thermostat Instruction Manual
nVent RAYCHEM RayStat-M2 Thermostat Instruction Manual
nVent RAYCHEM AT-TS-13 Surface Sensing Thermostat Instruction Manual
nVent RAYCHEM AT-TS-13 Surface Sensing Thermostat Instruction Manual
nVent RAYCHEM SENZ Wifi Programmable Floor Heating Thermostat User Guide
nVent RAYCHEM SENZ Wifi Programmable Floor Heating Thermostat User Guide
nVent RAYCHEM GM-TA Thermostat Instruction Manual
nVent RAYCHEM GM-TA Thermostat Instruction Manual

nVent RAYCHEM Green Leaf Programmable Thermostat Instruction Manual