6.ꢀINSTALLER MENU
Touch the “ ” button for 5 seconds to enter the installer Menu
#
Description
Range
Default setting
1
Sensing mode selection
Floor sensing mode
Floor Sensing mode
Room sensing mode
Room sensing mode with floor temperature limiter
2
3
12 vs 24 hours display
12 / 24
ON / OFF
24
ON
Motion sensor. When getting close
to the thermostat (5cm range)
the display lights up automatically
4
5
Offset for floor sensor calibration
Room sensor calibration
Offset of 0 .. 10°C
Measured sensor temperature +/- 5°C
4°C
Measured sensor
temperature
6
Minimum temperature
set point for the Floor Sensor
Floor sensing mode: 5 .. 15°C
Room sensing mode: OFF
Room sensing mode with floor temperature
limiter: OFF
5°C
OFF
OFF
7
Maximum temperature
set point for the Floor Sensor
Floor sensing mode: Minimum temperature
set point floor sensor (installer menu 6)
+5°C .. 35°C
35°C
OFF
Room sensing mode: OFF
Room sensing mode with floor temperature limiter: 27°C
10 .. 35°C
8
9
Minimum temperature
Floor sensing mode: OFF
Room sensing mode: 5 .. 15°C
Room sensing mode with floor temperature limiter: 5°C
5 .. 15°C
Floor sensing mode: OFF
OFF
5°C
set point for the Room Sensor
Maximum temperature
set point for the Room Sensor
OFF
40°C
Room sensing mode: Minimum temperature set
point room sensor (installer menu 8)
+5°C .. 40°C
Room sensing mode with floor temperature limiter: 40°C
Minimum temperature set point room sensor
(installer menu 8)
+5°C .. 40°C
10
11
Adjustable hysteresis
Open window function
0.5 .. 2.0°C
ON/OFF
1.0°C
ON
Floor sensor calibration
The temperature of the floor surface can differ from the temperature measured by the floor sensor due to the floor construction,
the floor type and the position of the floor sensor. In order to calibrate your thermostat to this difference you can use the floor
sensor calibration OFFSET in installer Menu 4.
After the temperature on the floor is stabilized, place a thermometer on the floor surface in order to sense the real temperature
on the surface (Tsurface). Read the floor sensor temperature (Tsensor) on the thermostat and adjust the OFFSET accordingly to
the formula:
OFFSET = Tsensor - Tsurface
Tsurface
Tsensor
Room sensor calibration
If the value measured by the room sensor in the thermostat differs from the real room temperature, it is possible to calibrate the
room sensor using the installer Menu 5.
After the temperature in the room is stabilized, place a thermometer close to the wall in order to sense the real room
temperature. If this value differs from the one shown by the thermostat, adjust Menu 5 using the “ ” or the “ ” until the
thermostat shows the same value as the reference thermometer.
8 | nVent.com/RAYCHEM
| General | Details |
|---|---|
| Name | nVent RAYCHEM Green Leaf Programmable Thermostat Instruction Manual |
| Make | nVent RAYCHEM |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.43 MB |

nVent RAYCHEM ETS-05 Electronic Thermostat Instruction Manual

nVent RAYCHEM RAYSTAT-EX-02 Mechanical Thermostat Installation Guide

nVent RAYCHEM Elexant 3500i Electronic Thermostat Installation Guide

nVent RAYCHEM RayStat-M2 Thermostat Instruction Manual

nVent RAYCHEM AT-TS-13 Surface Sensing Thermostat Instruction Manual

nVent RAYCHEM SENZ Wifi Programmable Floor Heating Thermostat User Guide

nVent RAYCHEM GM-TA Thermostat Instruction Manual